Loading...
HomeMy WebLinkAboutSingle Family Residence g , Town of Montville BUILDING DEPARTMENT 310 Norwich-New London Turnpike Uncasville, CT 06382 (860) 848-3030, Ext. 382 Building Permit Permit Number: 82004-0051 Date: 27-Feb-04 Map/Lot: 043/009-021 Owner ID 1761 Job Location: , 20 ~1 i~ISO WAY Unit Job Description: Single Family Residence Owner: Contractor: RTT Development RTT Development 35 Blais Road 35 Blais Road Uncasville Ct. 06382- Uncasville CT 06382 Telephone: (860) 889-1662 Lic/Reg Type/No. NHC 1795 Exp Date: 30-Sep-05 Tenant: Self Telephone: Construction Values Permit Fees Construction Information Building Value: $161,067.00 Building Fee: $970.00 Use Group: R4 Plumbing Value: $11,088.00 Plumbing Fee: $70.00 Code: 1995 CABO Mechanical Value: $6,072.00 Mechanical Fee: $40.00 Construction Type: 5B Electrical Value: $11,362.00 Electrical Fee: $70.00 Permit Code: R2 Other Value: $0.00 Other Fee: $0.00 Comments: Total Value: $189,579.00 CO Fee: $10.00 Plan Review Fee: $97.00 State Ed Fee: $30.33 Total Fees: $1,287.33 It is the owners responsibility to schedule the following inspections (minimum 48 hours notice required): F-/-l Footing - Prior to pouring concrete V Rough HVAC 0 Backfill - Footing drains and waterproofing ❑ Fireplace Throat W-1 Concrete Slab - Prior to pouring concrete ❑ Chimney - One flue above thimble R Rough Framing W Firestopping/draftstopping Rough Electrical Insulation ❑d Electrical Service CRS 0 ❑ Final Inspection ~/W Rough plumbing and leak test Certificate of Occupany ❑ Gas piping and test Building Official's Signature: Town of Montville ~ t Residential Plan Review Date:' $3 . ZOO Job Address: 7 f9 S 171 SAY Job Description: 100'W 5r-f2-.- We have received a building permit application for the above referenced property. In accordance with Connecticut General Statute 29-263, your application is being rejected for the following reason(s) that are checked-off or commented on: • Supporting Documentation Ventilation (409.1) Access 18"x24" (409.2) Plans are to be drawn to s cale i ncluding d imensions o f r ooms a nd spaces and all framing information (112.1) • an Building permit ap licaton not completed, signed, dWd Floor pl(S) -4 Permit fee $ Plans required Worker's comp. Affidavit or worker' comp. InsuranDimensions .Copy Contractor's registration or license Finish floor elevation Construction permit sign-off sheet Minimum room sizes (304.1) Provide all documentation to show compliance with the 161odel Door and window sizes Energy Code (1995 MEC). Contact your insulation contractor, Kitchen layout Northeast Smart Living Center (1-800-228-7764) or your local Bathroom layouts, tub sizes in gallons, space clearances building official for information. Stair location (min. width 36") (311.1) Street address of project on all drawings and documents Attic access location and size Field set of approved plans need to be picked up from our office Identify the use of each room Total square footage for each level of the structure Indicate required light (8% of floor area per room) and ventilation • Site plan (4% of floor area per room) for each habitable room or space (303. L) Plans required Indicate safety glazing in areas required such as: doors, windows, tub Finish floor elevation & shower enclosures, etc. (308.4.) Signed y by P&Z, lines nes not providWetlands,ed Uncas health, WPCA Indicate bedroom egress windows (5.7 sf net clear opening, 24" clear opening height, 20" clear opening width) (310.2.1.) Property l Distance from property to structure Egress window maximum sill height 44" (310.2) Structure dimensions Are basement stairs enclosed/accessible? If so, protect with Driveway minimum W' sheetrock (310.3.) Topography (existing and proposed) Designate which door is the required exit (36" minimum, hinged) Footing drain inverts, outlet and separation Garage Proposed utilities Minimum 518" Type X gypsum board separation (on garage side) to Wetlands and flood zone limits and elevations all living spaces - all combustible support framing to be covered with minimum 5/8" Type X gypsum board if it supports habitable rooms • Foundation Plan (309.2) Plans required Indicate minimum 1 solid wood door, 1 '/4" solid core steel door, 1 Dimensions honeycomb core steel door, or 20 minute rated door from the Wall thickness garage to the house and its basement or attic (309.1) Footing sizes Indicate self-closing devices on all doors from garage to the house Frost protection required and its basement or attic (309.1) Window and door sizes and locations Indicate slope for garage floor (309.3.) Hatchway Foundation - indicate the assumed soil conditions that the system has • Elevations been d esigned for or provide engineering data. If presumptive soil Plans required conditions cannot be met, provide soil bearing engineering data (401) Type of siding Concrete strength - foundation, floors, exterior porches, walks, slabs Type of roofing (402.2) Other finishes Basement- finished of unfinished? Finish grades Vapor barrier between sub-grade and concrete basement floor Building heights ( - (505.2.3) Dimension height of chimney above roof Minimum height of foundation walls above finished grade (404.1.3) Roof pitches Perimeter insulation, if conditioned space Anchor bolts - size and location (403. La) • Building Section(s) & Details Floor thickness and control joint location (403. La) Lally column size, attachment and spacing (408) Plans required Column footings - size (403) Floor-to-floor heights Waterproofing details (406) Handrails and guardrails - detail, 4ncluding height and maximum Rebar if required - wall length, unbalanced fill, or soil conditions will opening, handrail cross-section, continuity and required returns determine this. Provide engineering data for complex design. Riser height (8 '/V max), tread depth (9" min.), and nosing (3/4" - i Fireplace/chimney base '/I') Concrete piers and anchor details - decks Show minimum headroom in stairways - 6'-8" measured from nosing Foundation drainage - sump, drain to grade, or town storm system; plane to lowest point of ceiling indicate pitch (405.1) Stud size and spacing, species and grade (or minimum Fb and E) Beam pockets - minimum clearances Sheathing - size, thickness, type Crawl Spaces Siding, material, type, style - underlayment per mfg. Crawl space data - clearance to joists, slab thickness (if provided), Insulation - R-value, type - including basement walls if applicable vapor barrier (409) Flashing detail - windows and doors - type, material, Town of Montville' - • Framing plans Decks/Porches Plans required Plans required Bearing partitions Joists - size, span, spacing, direction, species and grade (or minimum Direction of framing Fb and E) Beam spans, size, species, grade Ledger - show attachment and flashing to house Framed openings Decking material and size. Sheathing type and thickness Beam - design data if required Window and door header sizes Posts - size, material, and height Joists - species and grade (minimum Fb and E), size, direction, and Piers -size, material, depth below grade (minimum 42" required) spacing Indicate joist hangers at flush framing and ledger Joists over-spanned Stairs, handrails, and guardrails Headers/beams overspanned Double joists at parallel bearing partitions, bathtubs, etc. (502.3.2) • Chimneys and Fireplaces Details of framing for plumbing, such as headers and trimmers at Indicate clearance of masonry to combustible framing materials and traps, etc. clearance from fireplace opening to finished trim Joist hangers for flush framing conditions or ledger (502.4.2) Show data for mechanical flue sizing Deck material, type, size, and span Show exterior combustion air source Floor insulation - R-value, type, vapor barrier location Flue sizes Provide design data for all unaligned wall and floor bearing points. Manufactures data and installation instructions for metal fireplaces Indicate location of all point loads Cantilevered framing less than 18" to grade to be pressure treated or . Electrical Plan(s) decay resistant Engineering data for steel beams, engineered lumber, roof trusses or Plan() required any other engineered product or design Panell location(s) with main size Roofs/ceilings Meter socket location Provide roof framing plan for roof geometry Outlet locations Ceiling joists - spacing, span, direction, species and grade (or GFCI outlet locations minimum Fb and E) Lights and switches Rafters - p itch, spacing, span, species, and grade (or minimum Fb Appliance/equipment circuits and E) Stair illumination Insulation - R-value, type - including basement walls if applicable Stairway light activation at both top and bottom of stair (303.4) Ventilation - ridge, gable, soffit Show required AC/DC smoke detectors (316) Provide minimum net ventilation data Attic access (22"00" minimum) for any attic with 30" or more clear • Mechanical plan(s) height Pplan(s) required Roof sheathing - type, size, thickness Dryer vent Collar ties - size, placement, spacing Bathroom exhaust ventilation (natural or mechanical) type and size Roof covering - shingles - type, nailing, provide proper with calculations underlayment - show interior horizontal distance of double Hood exhaust underlayment at eave, etc. Type of heat Overhang detail Heating, ventilation, and air conditioning plant locations Provide framing details of trayed/vaulted ceilings Oil/LP-gas tank size, location and piping Provide detail of cathedral ceiling structure and venting Make-up air requirements Indicate connection of lower chord of roof trusses and ceiling joists to Manufactures data for equipment the top plates of interior and exterior walls. Calculate roof tie-down Heat loss/gain calculations sizes when required by wind conditions Show framing for gables in cathedral ceiling construction e Plumbing plan(s) Provide engineering data for all roof trusses - (truss drawings must be plan(s) required signed and sealed by a Connecticut Licensed Professional Engineer) Building trap location Roof rafters over-spanned Sewer location Ceiling joists over-spanned Domestic water location Manufacturers data for whirlpools, corner tubs, & larger tubs Water heater size, type, and location Comments: d' g 1C' i Town of Montville , T- Building Department Permit 310 Norwich-New London Tpke. Tel. 848-3030, Ext 382 Uncasville, CT 06382 Fax. 848-7231 One & Two Family Building Permit Application Form ( New Construction Fj Addition E] Afteration F-1 Accessory Structure 'OT Other Job.Location m Job Description/Materials 2 Owner r T n Mailing Address 3 sr- 644 ° ea C city State Zip Tel Ate/ Contractor Mailing Address City State Zip Tel G Contractor's License/Registration Type & Number > Exp. Date 61 -t/ 3J / c> I hereby certify that the proposed work will conform to the Basic Building Code and all other codes as adopted by the State of Connecticut and the Town of Montville and further attest that the proposed work is authorized by the owner in fee and that I am authorized to make application for a permit for such work as descri ove. Owner /Agent Signature Date Construction Value Fee Building $ $ Plumbing $ $ Mechanical $ $ Electrical $ $ Other $ $ Certificate of Occupancy $ Plan Review Fee $ State Education $ Total $ $ (See *verse side for additionaf requirements) Town of Montville Residential Permit Requirements ' ❑ Two (2) complete sets of construction documents (to scale) are required and shall show the following information if applicable. This list is not all-inclusive, additional information may be required for your particular project. • Supporting Documentation • Building Section(s) & Details Coin Ip eted, signed and dated Building Permit Application Floor-to-floor heights Permit fee - calculated upon completion of plan review Material type, size, and spacing Completed building permit affidavit for property owners or sole Stair details (rise, run, treads, nosing, width, headroom) proprietors or copy of workers compensation insurance Handrail details Copy of Contractor Registration or license Guardrail details Construction permit sign-off sheet signed by all departments Roof ventilation Model Energy Code Analysis Heat loss calculations • Framing plans Engineering data for steel beams, engineered lumber, roof trusses or any other engineered products or design Design loads -for floors, ceilings, roofs Street address of project on all drawings and documents Bearing partitions Direction of framing Spans, beam • Site plan Wood species and grade Property lines Framed openings Distance from property to structure Sheathing type and thickness Structure dimensions Window and door header sizes Driveway Decking material, size, spacing Topography (existing and proposed) Note: Unusual structural conditions may require that additional Footing drain inverts, outlet and separation engineering back up be submitted Proposed utilities Wetlands and flood zone limits and elevation • Chimneys and Fireplaces Signed by P & Z, Wetlands, Uncas Health, WPCA Clearances to combustible materials Manufactures data for metal flues • Foundation Plan Exterior fresh air source for fireplaces Assumed soil bearing pressure Flue sizes Dimensions Manufacturers data and installation instructions for metal fireplaces Wall thickness Footing sizes • Electrical Plan(s) Anchor bolts, size and spacing Window and door sizes and locations Panel location(s) with main size Hatchways Meter socket location Columns Outlet locations Floor construction data GFCI outlet locations Drainage details Smoke detector locations Waterproofing details Lights and switches Crawl space ventilation Apr ipment circuits Crawl space access Stair illumination Concrete strengths • Mechanical plan(s) • Floor plan(s) Dryer vent Dimensions Bathroom exhaust ventilation (natural or mechanical) type and size Door and window sizes, egress window Hood exhaust Glazing in hazardous locations Type of heat Garage/dwelling opening protection Heating, ventilation, and air conditioning plant location Garageldwelling separation Oil tank size, location, and piping Kitchen layout LP-Gas tank location, size, and piping Bathroom layouts, tub sizes in gallons, space clearances Make-air requirements Indicate use of all rooms Manufacturers data for equipment Stair location Attic access location and size • Plumbing plan(s) Square footage for each habitable level of the structure Building trap location if on municipal sewer Required fight and ventilation for each habitable room Sewer location Domestic water location • Elevations - minimum of two required Manufacturers data for whirlpools, comer tubs, & larger tubs Type of siding Water heater size, type, and location Roofing Other finishes Finish grades Note: One set of annroved plans is required to be kept on Building heights site at all times. Height of chimney above roof Roof pitch ' Permit Fee Calculation Spreadsheet RESIDENTIAL PERMIT CALCULATION (2 STORY) House Construction A (E=Economy, A=Average, C=Custom) QTY $/UNIT $/UNIT $/UNIT TOTAL Living Area 2200 SF $ - $ 72.08 $ - $ 158,576.00 Finished Basement SF $ - $ 16.01 $ - $ - Unfinished Basement 11'00" SF $ - $ 5.72 $ - $ 6,292.00 Kitchen EA $ - $ - $ - $ - Plumbing F 4,229.40 $ - $ 4,229.40 Bath 2 EA $ $ Full - Half Bath -17 EA $ - $ 2,691.15 $ - $ 2,691.15 Garages Attached, 1 car EA $ - $ 8,885.10 $ - $ - Attached, 2 car -I-EA $ - $ 15,113.70 $ - $ 15,11370 Attached, 3 car EA $ - $ 20,913.90 $ - $ - Detached, 1 car EA $ - $ 11,657.10 $ $ - Detached, 2 car EA $ - $ 17,456.25 $ - $ - Detached, 3 car EA $ - $ 23,256.45 $ - $ - Under, 1 car EA $ - $ 1,304.10 $ - $ - Under, 2 car EA $ - $ 1,757.70 $ - $ - Fireplace & Chimney Prefab EA $ - $ 3,963.75 $ - $ - Masonry, exterior EA $ $ 3,963.75 $ - $ - Masonry, interior EA $ - $ 3,701.25 $ - $ - W/2 fireplaces EA $ - $ 6,746.25 $ - $ - Breezeway/Decks Open 120 SF $ - $ 22.31 $ - $ 2,677.20 Enclosed SF $ - $ 94.76 $ - $ - Porches Open SF $ - $ 62.69 $ - $ - Enclosed SF $ - $ 123.90 $ - $ Heating Adjustment 2200 SF $ - $ (2.76) $ - $ (6,072.00) Air Conditioning 2200 SF $ - $ 2.84 $ $ - Electrical 2200 SF $ - $ (5.16) $ - $ (11,352.00) Plumbing 2200 SF $ - $ (5.04) $ - $ (11,088.00) TOTAL BUILDING CONSTRUCTION COST, LESS MEP $ 161,067.45 Is air conditioning included (YIN)? $ - PERMIT FEE Building $ 161,067 $ 970.00 Y Plumbing $ 11,088 $ 70.00 Y Mechanical $ 6,072 $ 40.00 Y Electrical $ 11,352 $ 70.00 Other $ - CO Fee $ 10.00 Plan Review $ 97.00 State Ed Fee $ 189,579 $ 30.33 Total Fees $ 1,287.33 Based on 2003 RS Means REsidential Cost Data 2/9/2004 I_ i NEW HOME CONSTRUCTION CONTRACTOR RTT DEVELOPMENT 35 BLAIS RD UNCASVILLE, CT 06332 LIC./REG NO. - EFFECTIVE EXPIRES 1795 10/01/2003 09 /2005 SIGNED tl A STATE OF CONNECTICUT'S WOicKERS' COMPENSATION COMMISSION Building Permit Affidavit for Property Owners or Sole Proprietors (Conn. Gen. Stat. § 31-286b) Property located at: w y rit~L In the town of Name of building permit applicant: Please check one: 1. A I am the owner of the above property. 2. I am the sole proprietor of a business. 2A. Name of business: 2B. Federal Employer Identification Number (FEIN) - - - - - - - - - - - - - - - - - - - - Pursuant to § 31-286b, "a property owner or sole proprietor [who] intends to act as a general contractor or principal employer" may provide either a certificate of workers' compensation insurance or a "sworn affidavit... stating that he will require proof of workers' compensation insurance for all those employed on the job site in accordance with this chapter." Please check one: 1. I do not intend to act as a general contractor or principal employer. [Sign and stop here] Signature of applicant 2. --4- I intend to act as a general contractor or principal employer. Applicant must either provide a certificate of workers' compensation insurance or sign the affidavit below. - - - - - Affidavit I hereby swear and attest that I will require proof of workers' compensation insurance for every contractor, subcontractor, or other worker before he/she engages in work on the above property in accordance with the Workers' Compensation Act (Chapter 568). I understand that pursuant to § 31-275 C.G.S., officers of a corporation and partners in a partnership may elect to be excluded from coverage by filing a waiver with the appropriate ice; and that a sole proprietor of a business is not required to have coverage unless he file 1 acce coverage - Signature of applicant - S Sub bed and sworn to before me this day of Vs ~ . 200 ~l. - (Notary Public/Commissioner of the Supei nor-C:aurt) LISA TERRY NoTA Y PUBLIC My comMISSION EXP RES OCT. 31, 2007 Town of Montville Building Department 848-3030, Ext 382 ONE & TWO FAMILY CONSTRUCTION PERMIT SIGN-OFF SHEET .2- 0 Property Address Job Description: The owner/agent shall be responsible for the completion of the form, no certificate of occupancy will be issued until all signatures below have been obtained. HEALTH DISTRICT 848-3030-339 Approved /I a Not Permit 1 ' J r 7 Permit Required ptic S s Date Approved Not Permit ❑ Permit ❑ Required Private Well Date WPCA DEPARTMENT 848-3030, Ext 376 Approved Not Permit ❑ Permit ❑ Required Municipal Sewer Date House Trap ❑ Outside ❑ Inside Approved Not Permit ❑ Permit # ❑ Required Municipal Water Date DEPARTMENT OF PUBLIC WORKS 848-7473 Approved Not Permit El Permit El Required Director Date PLANNING ZONING DEPARTMENT 848-3030. Ext. 379 Approved Not Permit Required /zltt,~ Z / Z ©tV ❑ Permit ' Zoning Date Approved Not Permit ❑ Permit ❑ Required Inland-Wetlands Date