HomeMy WebLinkAboutShed
Town of Montville
Building Department
310 Norwich-New London Tpke.
Uncasvilie, CT 06382
Tel. 860-848-3030, Ext. 382 Fax. 860-848-7231
7/18/07
Todd M Frechette
7 Allison's Way
Oakdale Ct. 06370
Dear Todd Frechette
During a resent review of our files it was established that permit # B 2006 - 0611 dated November 9 2006
for construction of a shed has: not been closed out because it didn't pass the final inspection please
correct the deficiencies and contact our office between 8:OOAM and 4:30 PM to schedule a re-inspection
Please be informed that the use of this shed without the required inspections and issuance of a Certificate
of occupancy would constitute a violation under the Connecticut Building Code.
Respectfully yours
Charles Corell
Building Inspector
cc: File
Field Inspection Notice
Town of Montville
Building Department
January 8, 2009
Address: 7 Allison's Way
Job Description: Shed 12'x 16'
Permit Number(s): B2006-0611 Permit Date: 11/9/06
Not Approved Approval
INSPECTION Date: Deficiencies Special Date
Conditions
Anchors 11128106 DJ • Anchors not in lace. °
Certificate of 11/28/06 DJ • Tie down anchors required to be in place for C/O •
inspection.
occupancy
Rev. Date: 1/18/06 Page 1 of t
STATE OF CONNECT" BUT
P DEPARTMENT OF PUBLIC SAFETY
DIVISION OF FIRE, EMERGENCY AND BUILDING SERVICES'
.x OFFICE OF THE STATE BUILDING INSPECTOR
October 13, 2006
Mr. Todd Frechette .
7 Allisons Way
Oakdale, CT 06370
RE: M-1280-06R 7 Allisons Way
Oakdale, Connecticut
Dear Mr. Fre.chette:
1 have revised the referenced request for modification of Section R301.2.1.1, of
the 2003 International Residential Code portion of the 2005 State Building Code,
which states in part that construction in regions where the basic wind speeds
equal or exceed 110 mph shall be designed in accordance with the provisions of
this section.
It is illy decision to approve this modification, as requested, and allow a
192 square foot accessory structure (shed) to be. exempt.from the above code.
requirement. This decision is based on the size and use of such shed.
If you have. any questions, please contact Daniel Tierney, Deputy State Building
Inspector, at (860) 685-8310.
e
Christopher R. Laux, AIA
State Building Inspector
CRL:DT:pm
cc: Vernon Vesey, Montville Building. Official
Telephone (860) 685-8310
1111 Country Club Road
Middletown; CT 06457
http://www.ct.gov/dps.
Equal Opportunity Employer
;FATE OF CONNECTJT
DEPARTMENT OF PUBLIC SAFETY
DIVISION OF FIRE, EMERGENCY AND BUILDING SERVICES
Y OFFICE OF THE STATE BUILDING INSPECTOR
October 13, 2006
Mr. Todd Frechette
7 Allisons Way
Oakdale, CT 06370
RE: M-1280-06R 7 Allisons Way
Oakdale, Connecticut
Dear Mr. Frechette:
I have revised the referenced request for modification of Section R301.2.1.1, of
the 2003 International Residential Code portion of the 2005 State Building Code,
which states in part that construction in regions where the basic wind speeds
equal or exceed 110 mph shall be designed in accordance with the provisions of
this section.
It is my decision to approve this modification, as requested, and allow a
192 square foot accessory structure (shed) to be exempt from the above code
requirement. This decision is based on the size and use of such shed.
If you have any questions, please contact Daniel Tierney, Deputy State Building
Inspector, at (860) 685-8310.
e ,
Christopher R. Laux, AIA
State Building Inspector
CRL:DT:pm
cc: Vernon Vesey, Montville Building Official
Telephone (860) 685-8310
I l I I Country Club Road
Middletown, CT 06457
http_//www,ct.gov/dps
An Equal Opportunity Employer
`7 TATE OF CONNECT`-UT
DEPARTMENT OF PUBLIC SAFETY
A.
I
~ DIVISION OF FIRE, EMERGENCY AND BUILDING SERVICES
A OFFICE OF THE STATE BUILDING INSPECTOR
. October 5, 200
Mr. Todd Frechette
7 Allisons Way
Oakdale, CT 06370
RE: M-1780-06 7 Allisons Way
Oakdale, Connecticut
Dear Mr. Frechette:
I have reviewed the referenced request for modification of Section R301.2.1.1 of
the 2003 International Residential Code portion of the 2005 State Building Code,
which states in part that construction in regions where the basic wind speeds
equal or exceed 110 mph shall be designed in accordance with the provisions of
this section.
It is my decision to approve this modification, as requested, and allow a
120 square foot accessory structure (shed) to be exempt from the above code
requirement. This decision is based. on the size and use of such shed.
If you have any.questions, please contact Daniel Tierney, Deputy State Building
Inspector, at (860) 685-8310.
Vst rR. Laux, ;CIA
State Building Inspector
CRL:DT:pm
cc: Vernon Vesey, Montville Building Official -
Telephone (860) 685-8310
I I I.I Country Club Road
Middletown., CT 06457. .
http://www.ct.gov/dps
An Equal Opportunity Employer
STATE OF CONNECT0 FILE #
DEPARTMENT OF PUBLIC SAFETY
OFFICE OF THE STATE BUILDING INSPECTOR
1111 COUNTRY CLUB ROAD
MIDDLETOWN, CT 06457
TELEPHONE: (860) 685-8310
FAX: (860) 685-8365
REQUEST FOR MODIFICATION
OF THE STATE BUILDING CODE FOR OFFICE USE ONLY
1. Name and Location of Building: Residential Storage Shed - 12'X 16'
7 Allisons Way Oakdale T 06370
Number Street City State Zip
2. Building Owner: Todd M. Frechette
3. Applicant's Name: Todd M. Frechette Telephone:(860) 889-2888
Applicant's Address: 7 Allisons Way Oakdale CT 06370
Number Street City State Zip
(Include Firm Name if Applicable):
Name of Person to Contact: Todd M. Frechette Telephone:(860) 625-9199
(For information if required)
4. A. Date of Application for Building Permit: October 03, 2006
B..Applicable Code (Title and Date): Requirement for a CT State Registered Engineer 1 S .T/ZC;
5. Use Group: Storage Shed St r~1 "~rT i L
A. Was there a change of occupancy: ❑ Yes ® No
B. If yes from to
6. Building Construction Classification:Wood Frame Shed
7. Square Foot Area of Building (Total): 192
Largest Square Foot Area per Floor: 192
8. Number of Stories: 1
9. Check Applicable Designation:
® New Building ❑ Existing ❑ Addition ❑ Other (Explain)
10. Fire Protection at subject premises (Check appropriate headings)
❑ Smoke Detection ❑ Heat Detection ❑ Extinguishers
❑ Sprinklers ❑ Standpipes
❑ Other (identify): NONE
11. Describe alarm system(s) at premises: NONE
12. Building Code Section that modification is requested from: 2003 IRC, Appendix M
13. Modification Sought: Allow the attached New Hampshire Registered Engineer's Report
14. Reason Modification is Sought: CT Registered Engineer Report not available
15. Applicant's Signature Date Signed D'1 d6
16. Important Requirement Failure to provide the following information will delay modification
process. The Building Official must comment below on the modification request as per
Connecticut General Statute 29-254 (b). ❑*Note: Must signed by Chief Building
Official, Acting Building Official or Provisional Building Official of the municipality
where the construction is being done.
❑ Support Request
❑ Do Not Support Request
Al The decision on this request is left to the Office of the State Building Inspector.
❑ Please contact the undersigned.
Building Official's written comments, if desired.
)/ZfzjU0)V ~
Building Official (Printe Town *Building Official Signature D Signed
Building Official's Telephone Number Best Time to Contact
The Office of the State Building Inspector cannot accept this form electronically. Please
mail a paper copy of the signed form, with the local Building Official's written comments
and signature, to the Office of the State Building Inspector. ❑
MODAPP_NET
Rev. 1/5/06
Town of Montville
t Buitding bey artment
310 Norwich-New Landon Tpke.
Tel. 860-848-3030, Ext 382 Uncasville, CT 06382 Fax. 860-848-7231
RESIDENTIAL PERMIT APPLICATION FORM Permit No.: 6
Type of Work Occupancy Type P rmit Type
❑ New Construction Single Family Building
❑ Addition ❑ Two-Family ❑ Plumbing
n Alteration ❑ Townhouse ❑ Mechanical
❑ Accessory Structure ❑ Electrical CRS#:
Job Address: A ~(1 0C l5A
(Numbe (Street) (Unit)
Job Description:
Owner:
11► v~
Address: `7 City:
State: 1 Zip Code:
Telephone:
Contractor:
DBA: 1,~ C
Address: Y JO
City: State: Y Zip Code: G
Telephone: 7q 4- License Type: License No.: Expiration Date:
I hereby certify that the proposed work will conform to the State Building Code and all other codes as adopted by the State of Connecticut and the Town
of Montville and further attest that the proposed work is authorized by the owner in fee and that I am authorized to make application for a permit for such
work as described above.
r~KlBy checking this box, I will follow the requirements of the 2005 NEC as the alternative compliance per section E3301.2.1 of the Residential Code,
instead of the electrical requirements in chapters 33 through 42 of the Residential Code.
Owner /Agent Signature: Date: ~
Construction Value Permit'Fees
Building Value: Building Fee:
Plumbing Value: Plumbing Fee:
Mechanical Value: Mechanical Fee:
Electrical Value: Electrical Fee:
Total Value: Penalty Fee:
C of 0 Fee:
Plan Review Fee:
State Ed Fee:
Total Fee:
Rfviserl Decem6es31, 2005
- '-list
Rec°-~ential Permit Requirements Che k
ry ~
This list is to be used as a guide only and is not all-inclusive, additional information may be required for your particular
project. Two complete sets of construction documents required.
Provided Not
Applicable Item
Provided Not Item
Supporting Documentation Applicable
Completed, signed and dated Building Permit Building Section & Details
Application Floor-to-floor heights
Completed worker's compensation affidavit for Material type, size, andspacing
property owners or sole proprietors or copy of Stair details (rise, run, treads, nosing, width,
workers compensation insurance headroom
Co of Contractor Registration or license Handrail details
Construction permit sign-off sheet signed by all Guardrail details
departments Roof ventilation
Documentation showing compliance with the Framing Plans
Energy Conservation Code
www.ener codes. ov or Chapter 11 Design loads - for floors, ceilings, roofs
Street address of project on all drawings and Bearing partitions identified on the plan
documents Direction of framing
-Spans, beam _
Wind Limitations Criteria Woodspecies and grade
Documentation showing compliance with the Framed openings
requirements for construction in 110 mph wind Wall framing size andspacing identified
zone -Sheathing type and thickness
Design publication identified; WFCM-2001, Window and door header sizes
chapter 2; WFCM-2001, chapter 3; SSTD 10-99; Decking material, size, spacing
ASCE 7-02, AISI, COFS/FM Engineering data for engineered lumber (LVL's
and I= oists
Site Plan Framing plan for engineered lumber
Property lines Engineering data for steel beams, signed and
Distance from property structure sealed b a CT re istered design professional
Structure dimensions Engineering data for trusses, signed and sealed
Driveway b a CT registered Professional Engineer
To o ra h existing and proposed) Note: Unusual structural conditions may require
Footin drain inverts, outlet and separation that additional engineering back u be submitted
Proposed utilities Chimneys & Fireplaces
Wetlands and flood zone limits and elevation Clearances to combustible materials
Septic sstem shown and located on the plan Manufactures data for metal flues
Well and piping shown and located on the plan Exterior fresh air source for fireplaces
Foundation Information Flue sizes
Assumed soil bearing pressure Manufacturers data and installation instructions
for metal fire laces
Dimensions Electrical Information
Wall thickness
Footing sizes Panel locations with main size
Frost protection n Meter socket location
Foundation anchor type, size, locations GFCI outlet locations
Window and door sizes and locations Smoke detector locations
Hatchwa Li hts and switches
Columns Mechanical Information
Drainage details Dryer vent
Waterproofing details Bathroom exhaust ventilation (natural or
Crawls ace ventilation size and location mechanical type and size
Crawls ace access size and location Hood exhaust
Concrete strengths Type of heat oil, electric, as
Floor Plan Information Heating, ventilation, and air conditioning plant
location
Dimensions Oil tank size, location, and piping
Door and window sizes, egress window LP-Gas tank location, size, and piping
Glazing in hazardous locations Combustion air requirements
Gara edwellin opening protection Manufacturers data forequipment
Gara e/dwellin separation Heat loss, Heat gain calculations
Kitchen layout Plumbing Information
Bathroom layouts, tub sizes in gallons, space
clearances Building trap location if on municipal sewer
Indicate use of all rooms Sewer location
Stair location Domestic water location
Attic access location and size Water heater size, !ype, and location
Square footage for each habitable level of the Manufacturers data for whirlpools, corner tubs, &
structure ---tlarger tubs
Required light and ventilation for each habitable
room
Elevations
Type of siding
Roofing
Other finishes
Finish rades
Building heights
Heigh t of chimney above roof
Roof itch
Town of Montville
Building Department
File.Receipt
Receipt No: 1843
Date: 09-Nov-06
Received From: Todd Frechette
Job Address: 7 Allison's Wa
Fees Collected State Educational Training Fee
Cash: $0.57
Cash: $45.77
Check: $0.00
Check: $0'00
Check No: 0
Short/Over: $0.00 $3,552.00
Construction Value:
$0.00
Demolition Value:
Received By Sandra Pandora le,~
.rress•
TOTAL
ITEM QTY $/UNIT Building Plumbing Mechanical Electrical
BUILDING AREA $
Now Construction SF $ 114.17 $
Basement, Finished SF $ 2087 $ $ _
Basement, Unfinished SF $ 1128 $ $
Crawl Sppce S SF $ 8.46 $
Interior Renovations SF $ 31.90 $ - $ - $
MANUFACTURED HOMES $
Ground Anchors SF $ 5.86 $ $ -
Basement SF $ 11.28 $ - $ $
Crawl Space SF $ 8.46 $ - $ - $
AMENITIES $ _
Kitchen EA $ - $
Full Bathroom EA $ _ $ _
Half-Bathroom EA $ $
GARAGE $
Attached SF $ 49.41 $ - -
Detached SF $ 63.21 $ - $
Under SF $ 9.12 $ - $
Carport SF $ 18.08 $ -
MECHANICAL
Warm-Air Y' Y/N $
Hot Water Nr Y/N $ _
Electric N I;I Y/N $
Air Conditioning "-.11 Y/N $
ELECTRICAL SERVICE $
Upgrade Amps
Overhead, new 6 Amps $
Underground, new ; Amps $
Subpanel EA $ 545.00 $
Gen Set EA $ 3,500.00 $
SOLID FUEL BURNING APPLIANCES
Prefab Metal Fireplace EA $ 5,907.00 $
Masonry w11 fireplace EA $ 6,451.50 $
Masonry w/2 fireplaces EA $ 10,087.00 $
Wood Stove, tree standing S EA $ 2,447.50 $
Wood stove insert EA $ 1,690.70 $
DECKS, PORCHES, SUNROOMS
Deck SF $ 39.16 $
Porch SF $ 135.80 $
Sunroom SF $ 160.82 $ - $
POOLS 8 HOT TUBS $
Hot Tub I'. EA $ 7,287.50 $
$
Inground Pool S'. EA $ 19,430.40 $ -
Above Ground Round EA $ 4,635.88 $ $
Above Ground Oval EA $ 5,472.50 $ - $ -
Pool Heater EA $ 8,167.50 $
Inflatable Type Pool FA $ 1,542.42 $
SHEDS
w/o electrical 192.. SF $ 18.50 $ 3,551.81
w/electrical SF $ 18.50 $ $
RENOVATIONS
Roofing, Overlay SF $ 3.38 $
Roofing, Strip & reroof SF $ 3.76 $
RoofSheathing SF $ 1.19 $
Siding SF $ 2.30 $
Windows EA $ 423.50 $ -
Skylights EA $ 955.54 $
Doors, Exterior EA $ 401.50 $
Oil Tank, 275 Gallon FA $
Oil Tank, 550 Gallon EA
MISCELLANEOUS CALCULATIONS
TOTALS $ 3,551.81 $ $ $
PERMIT FEE CALCULATIONS
Construction Value Fee
Building $ 3,552.00 $ 32.00
Plumbing Y $ - $
Mechanical Y- $ $
Electrical Y_J $ - $
Working before Permit Issuance _N ` $
Certificate of Occupancy Fee $ 10.00
Plan Review Fee $ 3.20
State Education Fee $ 0.57
TOTALS $ 3,552.00 $ 45.77
Figures are based on the 2006 RS Means Residential Cost Data
i
A
State of Connecticut
Workers' Compensation Commission - ■
Please TYPE or PRINT IN INK
~rwsyy
Proof of Workers' Compensation Coverage when Applying
for a Building Permit for the Sole Proprietor or Property Owner
who WILL act as General Contractor or Principal Employer
Applicant for .Permit
Name of Applicant for Building Pere-
Pro rty located at ,j S6t JS rCr~/-v 7 7 ~^y
If you are the owner of the above-named property or the sole proprietor of a business doing work on the site of the construction project at the above-named
property and you WILL act as the general contractor or principal employer, you must provide proof of workers' compensation insurance coverage for all
employees.
Complete this form and, if applicable, sign the Affidavit below in the presence of a Notary Public or a Commissioner of the Superior Court.
CHECK ONE (1) BOX ONLY, provide the appropriate information, and sign:
* am the OWNER of the above-named property. t WILL act as the general contractor or principal employer and, as such, will submit proof of workers'
compensation insurance coverage for all employees who are doing work o the construction project at the above-named property.
Signature of OWNER Applicant 4;
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
❑ I am the SOLE PROPRIETOR of a business doing work at the above-named property. I WILL act as the general contractor or principal employer and, as
such, will submit proof of workers' compensation insurance coverage for all employees who are doing work on the site of the construction project at the above-
named property.
Signature of SOLE PROPRIETOR Applicant
❑ 1 am the OWNER of the above-named property or the SOLE PROPRIETOR of a business doing work at the above-named property. I will not personally
submit proof of workers' compensation insurance coverage, but I will attest to the. following:
AFFIDAVIT
hereby swear and attest that I will require proof of workers' compensation insurance for every contractor,
subcontractor, or other worker before he or she does work on the site of the construction project at the
above-named property in accordance with Section 31-286b of the Workers' Compensation Act.
Signature of OWNER or SOLE PROPRIETOR Applicant
Name of Business-if applicable
Federal Employer ID# (FEINy4fappticable
Subscribed and swom to before me this day of 200
Signature of Notary Public / Commissioner of the Superior Court
Town of Montville
Buildiria Department
310 Norwich-New London Tpke.
Tel. 860-848-3030, Ext 382 Uncasville, CT 06382 Fax. 860-848-7231
CONSTRUCTION PERMIT APPROVAL
I I i~i-Aa
roperty Address
Job Description
The applicant is responsible for obtaining all of the required approvals checked off on this form. No building
permit will be issued until all of the required signatures have been obtained.
Required Department Permit Issuance Approval
Approval
Tax Collector 10L3 O G
Signature/ date
Comments:
❑ WPCA, Administrative
Signature/ date
Comments:
❑ WPCA, Operations
Signature/ date
Comments:
mid
Planning & Zoning
Signature/ date
Comments:
jk-
Health Department
Sign Lure/ date
Comments: /o cry ever` ls~ c~u~ f.+
❑ Department of Public Works
Signature/ date
Comments:
❑ State Dept. of Transportation
Signature/ date
Comments:
Fire Marshal 2N
Signature/ date
Comments: IV L~
4svUedAugust 5, 2005
1010312006 20:37 16033823087 POSTWOODWORKING PAGE 02
1 2x16 Storage Shed
Main Wind Force Resisting System
And Overturning Moments
i, STEVEN q.
Cummoft
10/03/2006 20:37 16033823087 POSTWOODWORKING PAGE 03
This Design is for Mrtd I! oading ONLY! No Lure, Dead or Snow Loads were considered in
this analysis for the given structure. Results have been determined from IBC ZOOM Code and
National Design Specifications for Wood Construction, 1997 Edition. Stud Grade
Spruce-Fine-Fr 2x4 construction and Maximum New England-Wind Speed of 124 mph (3
Second Gust) was used in the analysis. Normal Moisture and Temperature conditions applied.
Buildin Dimensions
Width :=,V Fa%c = T3, Peak IT. Weight 3980.1b
I..angtb :
L 16-ft W :m 12-ft Hs:= 6.25.11 T.•~p:^ 9.1-ft
fTm + (Hy H/ 11m = 7.675 ft
L 2
Horizontal End Zone Distance
Zone 1 - Transverse
a1 30.0 a1= 112ft
a 40-Ha aZ = 2-fl *Not Less Than a=3 ft
as'~ .04V a3 = 0.49ft
a:= if(a3 ~t:i•ft,a ,340
a= aft
F7,D I a EZD = 6 ft.
a
WEROR ZONE
i 2
~T
„ 3E
X
+N~NObI~tECn~ttfahNGF.
Wind Analysis- 12x16 Page 79
Post Woodworking Storage Shed W6101
1010312006 20:37 16033823087 POSTWOODWORKING PAGE 04
Wind Lead
w
W
TRANSVERSE ELEVAIM
120•mph
V38=:
Sasic Wind Speed, 3 second gust, lBC 2000, Figure 16M
(Roof Angie, degrees Rise 14P -11, Rise = 2-83A
Run= W Raga = 6 ft
-
2
RR;'tsa l i30
4;=at A=0.443 D_:=L1•~W-)
Run 3.14
6 = 25.421
Main Windforce Loadings, IBC 2000, Figure 1809.6(1)
ISO 2000, Table 1609.6.2.10) for 3-Second Wind Gust of 120 MPH, Tnsverse Wind
Direction (Roof Angle Values to be interpolated)
for 01.10L.5*
W=5 = 22.8 Re15 --11.9 WR 5 -274 LR,$ -15.6
Rln„15 17.3 F4,,,.5:=•-13.4
for 20°
We _ 31.6 112D -8.3 WRstzo -27.4 L12e:_ -19. Y
E1,,i.,20 = 21.5 E4ma~v -18.4
forfor 300to. 4S_°45°
W 25.7 RezA5 17.6 W1,,A5 9.9 LR,Z45 -15.G
F11111145;= 19" E4m x45 : ~ -145
Wind Analysis-12x16 Page 8o
Post Woodworking Storage Shed 5!25101
10/0312006 20:37 16033823087 POSTWOODWORKING PAGE 05
Horizontal Wind Loads
zone 19 Wail 11
20~deg~ + ~e~,3, "NEhT"J~~
Wcz:= 8 s 5 dcg, Wez3a = 20, Wc~a, i 5 0 •c 20, 15
Wex "NF?CT"
(c owdr,45 (0 - 20)
wcz ° ~30-dcg <d5-deg, WoA5,Wd7.20-~ 10
_
WE:,. 213-402
Zone I E - Roo
8 = 20,Rc a,' S a 0 20, ~RezZ(s15 R.cz5) (A - 20)] A. &,5, "NFXT"l]l
Rc"N "NEXT„ Rez45) All
R.:= 30-deg ~ 8 <45-deg,Rez45,Rez2o - A -
- 10
I = 5.739
Vertical Wind Loads
Zone 2E - Nndward ft&
- ' 9 5•deia,WRZs, P1 T 20, ,.20, <0 <20, (WR ao - Wk9s) 0 20•dcgl +'VVltC731 „Nk'XT" l
pdi~z : 15
fez T "NEXT"
4s~ -l]
Wea.:~ ' 30 deg S 8 45•deg, WRCzgS, ao (tea - 10 20}
Wp, CZ . -•7.181
Zo ?3E- E.ee d Roof l1
LRc.20 - LR..5 (0 - 20- deg)J + L1~„ "NEXT'
fez = 9 s 5 deg, s,' 6 = 2o,z. ~ a, s 6 <20,~ 15 J
Lilt, _ „NEXT"
(jRim-2e - L J.",,41) 20}1
TAY ' 30-deg 0 < 45-deg,LRcz45,LR,7jo - 1D 1~
_ -17.203
LRc=
Page
Wind AnalySiS- 12x16 5125 81
post Woodworking Storage Shed 5125!01
10/03/2006 20:37 16033823087 POSTWOODWORKING PAGE 06
Maximum Horizontal Wall Loads for Transverse Wind
Storage Building, IBC 2000 1, 0.87
Wind Importance Factor,
lb
lb lb WRa W&~ lb LRd TRIM. w:= we l'
W,:= W.Z. 2 R. Rez ft2 ft e
It
WTI _ -7.181 1b X -17.203 1 R.:.,25.739 lb
ft e
T, HC A RiseZ + Rim' -T. 100ft2
Landhw Wd Logd i,, (lip s) T, ) JAS, = 106.28 ftz
L aad Le Tw} T oad,~ L (L+rw)
2 2
Load,,,, = 24711b Load = 227.692 lb
Load„T 599.7691b a4;=--14371b
pverturrling Moment Calculation
H0 1-Ttise~ + k~8
Ybar = 3.67•ft 3'wau 2 Yro~:_ ~3 l
,,,.U = 3.12511t
Yrove = 7.21t
Loady,25W)l
W ) + tLoa~,•75-W) + (J
T + ~T..aadlm•Yroo~e -W
W~~t. ~ ~ + ~~►~hw•Ywa„)
T = 1.1 x 103 th
Post Woodworking Wind Analysis- 12x16 Page 82
5125/01
Storage Shed
10/03/2006 20:37 16033823087 POSTWOODWORKING PAGE 07
a «
Bending Stress in Illfll turfs
Considering Wind Loading Of Maim 5tnict' 0'71yd
Actual Sending Stress in Wdil Studs
1.333.0 w = 24.71 1b Wtdb 00•x' wlxib = 32.938
oc:-
160.831b. R
wall 6.25-ft Ivim~ 8
b:= 1.5-in b.:= 3.54a NTm' = 1.93 x I(Y 1b. in
Lb ! f b fb = 630.189 1 2
S 6 b S m
Allowable Bending Stress in Wall Studs
Lumber Type: Spruce-Pine-Fir Stud Grade Assumed
Load Duration Factor, Permanent Lifespan, Wind Loading CD 1.6
Wet Service Factor, Moisture S 1 cm 1.0
Temperature Factor, T e- 1000 F Ct 1.0
Beam Stability Factor, End Support Provided CT, 1.0
Form Factor, Rectangular Cross Sedon cf = 1.0
Volume Factor, Applies only to Glu-Lam Cv :T 1.0
Flat Use Factor, Load Applied to Narrow Face Cfv:= 1.0
Incising Factor, No Incising performed ci 1.0
Repetitive Member Factor, Stud Placed 18" On Center, Not Lass Than 3 in Number,
Joined by Floor and Roof Plates
Cr 1.15
Curvature Factor, Curved Glu-Lam Only C,:= 1.0
Wind Analysis-12x16 Page 83
Post Woodworkicg Storage Shed 5125101
10183/2806 28:37 16033823087 POSTWOODWORKING PAGE 08
Allowable Sending Stress in Wall Studs (Continued)
Size Factor, Depends on Lumber Type CF 1.0
Sending Stress for Specified Species, Spruce-Pine-Fir Assumed, Stud Graded
Fb 675. lb
m
F'b:m Fb'CD'CM'Ct'C?: Cf'CV'C;F„1C`-Cs C..CF F*b = 1242 1b
2
in.
Check Actual Sending Stress vs. Allowable Sending Stress
Sufrioient if(fb s F'1„"TR.UO,"FALSE")
Soffioient "TRITE"
Wind Analysis- 12x16 Page 84
Post Woodworking Storage Shed 5125101
i