Loading...
HomeMy WebLinkAboutReplace Gas Furnace & A/C System Field Inspection Notice Town of Montville Building Department 860-848-3030 Ext.382 Address: 54 Connecticut Blvd. Job Description: Replace Gas Furnace&A/C System Permit Number(s) M2014-0124 Permit Date: July 25,2014 Not Approved Approval INSPECTION Date: Comments Special Date Conditions 4/11/17 DJ • The duplex receptacle mounted on the furnace is • Electric required to be GFCI protected. 9/25/17 DJ • • The Flue pipe is required to have a minimum of 6"of • Exhaust pipe 4/11/17 DJ clearance from combustibles.Presently there is less 9125/17 DJ clearances than 6"from combustibles.Correction required. • • Final inspection and • 9125/17 DJ certificate of approval • • Rev.Date: 1/18/06 Page 1 of 1