HomeMy WebLinkAboutBuilding Plans 10-29-252" MINIMUM
SIDE COVER
BC6
POST
CAP
"SIMPSON" BC
CONNECTORAT EACHPOST TOP TO
BEAMCONNECTION-TYPICAL
"SIMPSON"
STRONG-TIEBC
CONNECTOR
AT ALL POSTBASES-TYPICAL
DETAIL 3BC6
POST
BASE
DETAIL 4H2.5ADETAIL 2HIGH WIND LOAD CONNECTION DETAILS
TOTAL ROOF WIDTH
(INCL.1' OVERHANG)
40'
REQUIRED STRENGTH OF RAFTER
TIE-DOWN CONNECTION TO
RESIST WIND UPLIFT FORCES
(Pounds per tie-down connection)
24'
649
435
H2.5A with (5) 8d x 1 1/2 nails into each
rafter, (5) into plates: Uplift=600 lbs.
O.C.
RAFTER
SPACING
(in.)
ROOF ASSEMBLY TO TOP PLATE ASSEMBLY
BASED ON TABLE 2.2A OF THE 2001 WFCM
16"
24"
32'36'28'
416
279
474
318
532
356
591
396
IMPORTANT NOTE:
ALL DESIGNS, NOTES AND DETAILS BASED ON THE
2021 INTERNATIONAL RESIDENTIAL CODE AND THE
2022 CONNECTICUT STATE BUILDING CODE.
1.ALL FOUNDATION WALLS SHALL BE 8" THICK W/16"x
8" CONTINUOUS FOOTINGS. WALLS <8' TALL SHALL
HAVE ONE #4 BAR WITHIN 12 INCHES OF THE TOP OF
THE WALL STORY AND ONE #4 BAR NEAR MID-
HEIGHT OF THE WALL STORY. WALLS > 8' TALL
SHALL HAVE ONE #4 BAR WITHIN 12 INCHES OF THE
TOP OF THE WALL STORY AND ONE #4 BAR NEAR
THIRD POINTS IN THE WALL STORY.
1 PROVIDE ADEQUATE DRAIN TILING, CRUSHED
STONE AND FILTER FABRIC AROUND PERIMETER OF
FOUNDATION AT OR BELOW THE TOP OF THE
FOOTING.
2.WOOD SOLE PLATES AT ALL EXTERIOR WALLS,
WOOD SOLES OF BRACED WALL PANELS AND ALL
WOOD SILL PLATES SHALL BE ANCHORED TO THE
FOUNDATION WITH ANCHOR BOLTS SPACED A
MAXIMUM OF 4 FEET ON CENTER. BOLTS SHALL BE
AT LEAST 1/2 INCH IN DIAMETER AND SHALL EXTEND
A MINIMUM OF 7 INCHES INTO CONCRETE. A NUT
AND 3" WASHER SHALL BE TIGHTENED ON EACH
ANCHOR BOLT. THERE SHALL BE A MINIMUM OF TWO
BOLTS PER PLATE SECTION WITH ONE BOLT
LOCATED NOT MORE THAN 12 INCHES FROM EACH
END OF THE PLATE SECTION.
EXCEPTION: FOUNDATION ANCHOR STRAPS, SPACED AS
REQUIRED TO PROVIDE EQUIVALENT ANCHORAGE TO 1/2-
INCH DIAMETER ANCHOR BOLTS.
FOUNDATION NOTES 2025
2. EMERGENCY EGRESS OPENING
3. STAIRS
1. DESIGN LOADS
Design Criteria 2025
SNOW 30#/S.F.
WIND 130 MPH Velocity Ultimate Wind Speed
1ST FL. L.L. 40#/S.F.
2ND FL. L.L. 30#/S.F.
ATTIC L.L. 20#/S.F.
SLEEPING ROOMS: SILL HEIGHT< 44"
NET GLASS OPENING >/= 5.7
S.F. NET GLASS OPENING HEIGHT >/=24"
NET GLASS OPENING WIDTH >/=20"
10" MIN. TREADS
8-1/4" MAX. RISERS
3/4" MAX. TREAD PROJECTION OF CLOSED
RISER
6'-8" MIN. CLEAR @ CEILING ABOVE STAIRS
3'-0" MIN. WIDTH OF STAIRS
TYPICAL DECK DETAIL DF-1
PER AWC PRESCRIPTIVE WOOD DECK CONSTRUCTION GUIDE
TYPICAL DECK DETAIL DF-2
PER AWC PRESCRIPTIVE WOOD DECK CONSTRUCTION GUIDE
TYPICAL DECK DETAIL DF-4
PER AWC PRESCRIPTIVE WOOD DECK CONSTRUCTION GUIDE
TYPICAL DECK DETAIL DF-3
PER AWC PRESCRIPTIVE WOOD DECK CONSTRUCTION GUIDE
TYPICAL DECK DETAIL DF-5
PER AWC PRESCRIPTIVE WOOD DECK CONSTRUCTION GUIDE
OPTIONAL
OVERHANG
RIM JOIST
BEAM (see detail
D-6)
L0 OR L/4 MAX.
OVERHANG
JOIST
BLOCKING (@
OVERHANGING JOISTS
ONLY)
JOIST HANGER
LEDGER BOARD (see
detail D-5)
POST
JOIST SPAN (L < LJ)HOUSE WALL_
DRIP EDGE
HURRICANE CLIP
5/4" FASCIA
SCALE: 1/4" = 1'-0"
TYP. WALL SECTION
P.T. 2x6 SILL
5/8" DIA. ANCHOR BOLT
@ 48" O.C.
APPROX. GRADE - V.I.F.
8" CONC. WALL W/ SPRAYED ON
RUBBER MOISTURE BARRIER
4" DIA. PERF. FTG. DRAIN W/
8" MIN. CRUSHED STONE
AND FILTER FABRIC
16" X 8" CONT. FOOTING MIN.
3/4" T&G SUB FLOOR
1/2" GYP. BD. @
WALLS AND CLG. (TYP.)
SEE DETAIL 2
THIS SHEET
30 YEAR FIBERGLASS
ARCHITECTURAL SHINGLES
15# ROOFING FELT
1/2" CDX PLYWOOD
ROOF SHEATHING
CONT. RIDGE VENT
(TYP.)
ICE & WATER SHIELD MIN. 3' UP
ROOF SLOPED >3:12
4" CONCRETE FLOOR SLAB W/
W.W.M. AND VAPOR BARRIER
(SOIL-GAS-RETARDER
MEMBRANE (MIN. 6-MIL
POLYETHYLENE SHEETING OR
EQUIVALENT), OVER 8" MINIMUM
CRUSHED STONE.
LOWER FLOOR
MAIN FLOOR
"ACCU-VENT"
ROOF TRUSSES BY OTHERS
7" CLOSED CELL
SPRAY FOAM
INSULATION = R-49
4.5" CLOSED CELL
SPRAY FOAM BLOCKER
ATTIC
R-60 BLOWN-IN CELLULOSE
INSULATION IN FLAT CLG.
1/2" CDX. PLYWOOD
SHEATHING
2x6 STUDS @ 16" O.C.
2 1/2" (R-15) CLOSED CELL
SPRAY FOAM W/ VAPOR
BARRIER
R-15 UNFACED F.G. BATT
INSULATION
R-30 KRAFT FACED F.G. BATT
INSULATION IN GARAGE CLG.
1/2" GYP. BD.
2x4 STUDS @ 16"
O.C. W/ R-13 BATT
INSULATION
3/4" R-5 FOAM
BOARD, TAPE ALL
SEAMS
Decks supporting large concentrated loads such as hot tubs are beyond
the scope of this document.
All decking material shall be composed of dimension lumber (2" nominal
thickness) or span rated decking in accordance with the American Lumber
Standard Committee Policy for Evaluation of Recommended Spans for
Span Rated Decking Products (November 5, 2004).
Attach decking to each joist with 2-8d threaded nails or 2-#8 screws.
Space decking boards approximately 1/8" apart.
Each segment of decking must bear on a minimum of 3 joists (or 3
supports).
All posts, framing lumber and stringers shall be approved preservative
treated wood suitable for ground contact. [R317.1.2] All cut ends and
notches of posts shall be field treated with an approved preservative
(such as copper naphthenate) [R402.1.2]
Fasteners and connectors exposed to salt water or located within 300 feet
of a salt water shoreline shall be stainless steel grade 304 or 316 or rated
for use in a salt water environment.
Fasteners and connectors shall be of the same corrosion-resistant
material.
Composite Decking material must be labeled as complying with ASTM
D7032.
Provide diagonal bracing parallel to the beam at each corner post greater
than 2'-0" in height, see detail DF-2.
Provide minimum of 2-1500lb. (or 4-750lb. min.) lateral tie downs per deck
section, see detail DF-5.
For further information, please refer to the American Wood Councils
publication DCA-6 or section R507 of the 2021 IRC.
DECKING REQUIREMENTS 2025
THESE DRAWINGS ARE THE PROPRIETARY WORK PRODUCT AND PROPERTY OF Cornerstone Designs, llc. ,DEVELOPED FOR THE EXCLUSIVE USE OF Cornerstone Designs, llc.. USE OF THESE DRAWINGS AND CONCEPTSCONTAINED THEREIN WITHOUT THE WRITTEN PERMISSION OF Cornerstone Designs, llc. IS PROHIBITED AND MAY SUBJECT YOU TO A CLAIM FOR DAMAGES FROM $100,000.5036 CASE EGRESS
PORCH
7
12
NOTE: P.T. OR BETTER, 36"
HIGH (MIN.) HANDRAIL
(GUARD) REQUIRED WHERE
DECK OR STEPS ARE >30"
ABOVE FINISHED GRADE.
NO OPENINGS IN GUARD
SHALL ALLOW A 4" SPHERE
TO PASS THROUGH-TYP.
7
12
1'
O.H.
SEE DETAILS 3 & 4, THIS
SHEET FOR CONNECTOR
INFORMATION - TYP. ALL
POST TO PIER AND POST
TO BEAM CONNECTIONS.
P.T. 6x6 SUPPORT POST
(TYP.) ON 12" PIER OR10" PIER W/BF20"BIGFOOT SYSTEMS"FOOTING TO 42" BELOWGRADE (TYP.) PROVIDE4-# 4 REBARS VERT.
VINYL LAP SIDING
VINYL FASCIAS, CORNER
TRIM & WINDOW CASING
-TYP.
PRECAST CONC. STEPS
APPROX. GRADE
5036 CASE EGRESS
PORCH
LEFT ELEVATION
7 : 12
3049 EGRESS
2030 SAFETY3030
6068
SEE DETAILS 3 & 4,
THIS SHEET FOR
CONNECTOR
INFORMATION - TYP.
ALL POST TO PIER
AND POST TO BEAM
CONNECTIONS.
7 : 12
3049 EGRESS
2030 SAFETY3030
6068
BACK ELEVATION
3049 EGRESS
PORCH
7
12
7
12
1' CANT.
3049 EGRESS
PORCH
RIGHT ELEVATION
3046-2
3049 EGRESS3049 EGRESS
PORCH
30493049
8070 8070
3068
7 : 12
30493049
97 1/8"10"97 1/8"2'-1 1/4"25'-6 15/16" +/-INSIDESILL STOP3046-2
3049 EGRESS3049 EGRESS
PORCH
30493049
8070 8070
3068
7 : 12
30493049
FRONT ELEVATION
Lisa Kobar
PO Box 1
Yantic
CT 06389
860-287-1025
Lisa@CSDplans.com
1/4"=1'-0"
SHEET:
SCALE:
DRAWINGS
PROVIDED BY:DESCRIPTIONCornerstone
Designs
DATE:DATENO.PROJECT DESCRIPTION:SHEET TITLE:A-1
10/24/2025Heller DevelopmentPRELIMINARY ONLYP R E LIM IN A R Y
GENERAL NOTES & REQUIREMENTS 2025 ALL DESIGNS, NOTES AND DETAILS BASED ON THE 2021 INTERNATIONAL
RESIDENTIAL CODE / 2022 CONNECTICUT STATE BUILDING CODE.
ALL LUMBER SHALL BE NO. 2 DOUGLAS FIR, OR BETTER. ALL CARPENTRY SHALL BE PERFORMED IN ACCORDANCE WITH APPROPRIATE CODES AND STANDARD PRACTICES. ALL STRUCTURAL LUMBER SHALL
BE GRADE STAMPED.
ALL CONCRETE CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF A.C.I. "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS", A.C.I. 301, LATEST EDITION.
ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS AS FOLLOWS: SLABS ON GRADE:...............3500 psi (EXPOSED TO WEATHER), FOOTINGS AND FOUNDATIONS:.........................3000 psi
(NOT EXPOSED TO WEATHER) FOR CONCRETE MIX AS REQUIRED BY A.C.I. "STANDARD PRACTICE FOR MEASURING, MIXING, AND TRANSPORTING CONCRETE, A.C.I. 304, LATEST EDITION.
ALL EXTERIOR FOOTINGS SHALL BE 8" THICK BY 16" WIDE (MIN. FOR 8" WALL) AND 10" THICK BY 20" WIDE (MIN. FOR 10" WALL) AND SHALL EXTEND TO 42" BELOW FINISHED GRADE (FROST LINE).FOOTINGS ARE
TO REST ON UNDISTURBED/NATURAL SOIL.
NAILING SHALL CONFORM TO THE 2021 IRC, TABLE R602.3(1) OR R602.3(2) UNLESS MORE STRINGENT REQUIREMENTS ARE SHOWN ON THE DRAWINGS.
FLOORING SHEATHING SHALL BE GLUED AND NAILED.
SILL PLATES IN CONTACT WITH MASONRY OR CONCRETE SHALL BE PRESSURE TREATED.
ANCHOR BOLTS SHALL BE ASTM A-307 STEEL
PROVIDE SOLID BLOCKING AT END OF ALL 2x10 OR LARGER JOISTS AND AT MID HEIGHT OF ALL STUD WALLS OVER 9' IN HEIGHT. PROVIDE DIAGONAL OR SOLID BRIDGING FOR ALL 2x10 OR LARGER JOISTS AT
MID SPAN IF SPAN IS GREATER THAN 10'.
ALL EXTERIOR WALLS AND PARTITIONS SHALL HAVE 2-2x10 HEADERS AT DOOR AND WINDOW OPENINGS UNLESS OTHERWISE SPECIFIED.
ALL INTERIOR WALLS AND PARTITIONS WITH THE EXCEPTION OF PLUMBING PARTITIONS, ARE TO BE 2x4 UNLESS OTHERWISE SPECIFIED.
ALL EXTERIOR DECK AND DECK RAILING TO BE PRESSURE TREATED (PT).
EXTERIOR 2X6 WALLS SHALL HAVE 5 1/2 THICK, R-21 FIBERGLASS BATTS & "ZIP" 1" R-3 SHEATHING W/ 1" (OR SIMILAR). OR SPECIFIED WALL INSULATION BASED ON 2021 IRC N1102 (TOTAL UA ALTERNATIVE [RES
CHECK]).
CEILINGS AT ATTIC SHALL HAVE GLASS FIBER BATTS WITH AN R-60 MINIMUM, OR SPECIFIED CEILING INSULATION BASED ON IRC N1102 (TOTAL UA ALTERNATIVE [RES CHECK]).
G.F.C.I. OUTLETS ARE TO BE INSTALLED IN ALL KITCHENS AND BATHROOMS PER 2021 IRC, E3901.2.1 - E3901.10
SMOKE ALARMS ARE TO BE INSTALLED IN EACH SLEEPING ROOM AND OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS.
APPROVED CARBON MONOXIDE ALARM SHALL BE INSTALLED OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS AND/OR ONE UNIT PER HABITABLE LEVEL.
ATTIC ACCESS HATCH TO HAVE R-60 BATT (MIN.) INSULATION, OR SPECIFIED CEILING INSULATION BASED ON IRC N1102 (TOTAL UA ALTERNATIVE [RES CHECK]) AND BE WEATHER STRIPPED. INSULATION
SHALL BE PROTECTED FROM COMPRESSION.
1.ALL FOUNDATION WALLS SHALL BE 8" THICK W/16"x
8" CONTINUOUS FOOTINGS. WALLS <8' TALL SHALL
HAVE ONE #4 BAR WITHIN 12 INCHES OF THE TOP OF
THE WALL STORY AND ONE #4 BAR NEAR MID-
HEIGHT OF THE WALL STORY. WALLS > 8' TALL
SHALL HAVE ONE #4 BAR WITHIN 12 INCHES OF THE
TOP OF THE WALL STORY AND ONE #4 BAR NEAR
THIRD POINTS IN THE WALL STORY.
1 PROVIDE ADEQUATE DRAIN TILING, CRUSHED
STONE AND FILTER FABRIC AROUND PERIMETER OF
FOUNDATION AT OR BELOW THE TOP OF THE
FOOTING.
2.WOOD SOLE PLATES AT ALL EXTERIOR WALLS,
WOOD SOLES OF BRACED WALL PANELS AND ALL
WOOD SILL PLATES SHALL BE ANCHORED TO THE
FOUNDATION WITH ANCHOR BOLTS SPACED A
MAXIMUM OF 4 FEET ON CENTER. BOLTS SHALL BE
AT LEAST 1/2 INCH IN DIAMETER AND SHALL EXTEND
A MINIMUM OF 7 INCHES INTO CONCRETE. A NUT
AND 3" WASHER SHALL BE TIGHTENED ON EACH
ANCHOR BOLT. THERE SHALL BE A MINIMUM OF TWO
BOLTS PER PLATE SECTION WITH ONE BOLT
LOCATED NOT MORE THAN 12 INCHES FROM EACH
END OF THE PLATE SECTION.
EXCEPTION: FOUNDATION ANCHOR STRAPS, SPACED AS
REQUIRED TO PROVIDE EQUIVALENT ANCHORAGE TO 1/2-
INCH DIAMETER ANCHOR BOLTS.
FOUNDATION NOTES 2025
MECHANICAL NOTES 2023
..THE CONTRACTOR SHALL BE RESPONSIBLE TO CALL FOR
ALL REQUIRED INSPECTIONS.
..PER THE CONDITIONS OF APPROVAL FROM ZONING, NO
FRAMING MAY TAKE PLACE UNTIL THE FOUNDATION
CERTIFICATE IS COMPLETED.
..DRYER DUCTS SHALL BE MECHANICALLY FASTENED (NOT
TAPED) WITH SCREWS PROJECTING NO LONGER THAN 1/8 INCH
INSIDE THE DUCT.
..A BLOWER DOOR TEST CONDUCTED BY A THIRD PARTY IS
REQUIRED. TEST RESULTS, SIGNED BY THE THIRD PARTY
TESTER, SHALL BE SUBMITTED TO THIS OFFICE UPON
COMPLETION OF THE TEST. THE AIR LEAKAGE RATE SHALL NOT
EXCEED 3 AIR CHANGES PER HOUR (3 ACH). THE PROPER
CONSTRUCTION METHODS TO ACHIEVE THIS RATE CAN BE
OBTAINED FROM A THIRD PARTY TESTER.
..A WHOLE HOUSE MECHANICAL VENTILATION SYSTEM
SHALL BE PROVIDED THAT MEETS THE REQUIREMENTS OF
SECTION M1505 OF THE 2021 IRC OR THE INTERNATIONAL
MECHANICAL CODE.
..A PERMANENT CERTIFICATE SHALL BE COMPLETED AND
POSTED ON OR IN THE ELECTRICAL DISTRIBUTION PANEL
BY THE BUILDER. THE CERTIFICATE SHALL NOT COVER OR
OBSTRUCT THE VISIBILITY OF THE CIRCUIT DIRECTORY
LABEL, SERVICE DISCONNECT LABEL OR OTHER REQUIRED
LABELS. THE CERTIFICATE SHALL LIST THE PREDOMINANT
R-VALUES OF INSULATION INSTALLED IN OR ON THE
CEILING/ROOF, WALLS, FOUNDATION (SLAB, FOUNDATION
WALLS, CRAWL SPACE WALLS AND/OR FLOOR) AND DUCTS
OUTSIDE OF CONDITIONED SPACED. THE CERTIFICATE
SHALL INCLUDE THE RESULTS OF THE BLOWER DOOR TEST
AND DUCT TIGHTNESS TEST. THE CERTIFICATE SHALL ALSO
LIST THE TYPES AND EFFICIENCIES OF HEATING, COOLING
AND SERVICE WATER HEATING EQUIPMENT.
..DUCT SEALING AND DUCT TIGHTNESS TESTING IS
REQUIRED IN ACCORDANCE WITH SECTION N1103.3.6
LEAKAGE SHALL BE LESS THAN OR EQUAL TO 8 C.F.M. PER
100 SQUARE FEET OF CONDITIONED FLOOR AREA.
..PRIOR TO A CERTIFICATE OF OCCUPANCY BEING ISSUED,
THE CONTRACTOR SHALL PROVIDE THE BUILDING DEPARTMENT
WITH AN AFFIDAVIT/STATEMENT INDICATING WHO THE CONCRETE
SUPPLIER AND INSTALLER WAS FOR THIS PROJECT ALONG WITH
ALL THEIR CONTACT INFORMATION AND ADDRESSES.
BRACED WALL PANEL-TO-FOUNDATION HOLDOWN
SOLUTIONS FOR 800 LB. CAPACITY REQUIREMENTPORTAL FRAME DETAIL
Wall Schedule2D Symbol Wall Type
8" Concrete Stem Wall
Exterior-2x6
Interior-2x6
Interior-2x4
Deck Railing/Fence
THESE DRAWINGS ARE THE PROPRIETARY WORK PRODUCT AND PROPERTY OF Cornerstone Designs, llc. ,DEVELOPED FOR THE EXCLUSIVE USE OF Cornerstone Designs, llc.. USE OF THESE DRAWINGS AND CONCEPTSCONTAINED THEREIN WITHOUT THE WRITTEN PERMISSION OF Cornerstone Designs, llc. IS PROHIBITED AND MAY SUBJECT YOU TO A CLAIM FOR DAMAGES FROM $100,000.3 1/2" DIA. CONCRETE FILLEDLALLY COLUMN (TYP.)
2'-6" x 2'-6" x 1'-0" CONCRETEFTG. (TYP.)
3-1 3/4" x 9 1/4" 2.0E Microllam® LVL-FLUSH
2'8'-6"2'-4"8'-6"25'-8"27'9'47'
8"
1'-4"8"8"8"11'-8"11'-4"24'
9' V.I.F.1'10'2'-11 1/2"6'-7 1/4" V.I.F.47'1'-4"11'-9"1'-6"11'-9"1'-4"Unexcavated
MASONRY OPENINGMASONRY OPENING
STEP FOUNDATIONWALL & FOOTINGPER SITE
CONDITIONS - V.I.F.
STEP FOUNDATIONWALL & FOOTINGPER SITECONDITIONS - V.I.F.PITCH SLAB 2" TOWARDSDOORS - GARAGE PORTIONP.T. 6x6 SUPPORT POST(TYP.) ON 12" PIER OR 10"
PIER W/BF20 "BIGFOOT
SYSTEMS" FOOTING TO 42"BELOW GRADE (TYP.)PROVIDE 4-# 4 REBARS VERT.
SEE DETAILS 3 & 4, SHEET
A-1 FOR CONNECTOR
INFORMATION - TYP. ALL
POST TO PIER AND POST TO
BEAM CONNECTIONS.
CONT. 18" WIDE x 8" THICK CONC. FTG BELOW FRAMED BEARING WALL ABOVE.
4" CONCRETE FLOOR
SLAB W/ W.W.M. ANDVAPOR BARRIER OVER8" MINIMUM CRUSHEDSTONE
Foundation 5036 CASE EGRESS30682668 20683046-2
80708070
2668
2668 2668
UP
2x10 or 9.5" LVL Flr. Jsts. @ 16" o.c.2x10 or 9.5" LVL Flr. Jsts. @ 16" o.c.2x10 or 9.5" LVL Flr. Jsts. @ 16" o.c.2x10 or 9.5" LVL Flr. Jsts. @ 16" o.c.SD/CO
AC/DC
INTERCONNECTED
SMOKE & CARBON
MONOXIDE
DETECTOR/ALARM
EF
EXHAUST
FAN/LIGHT
5/8" TYPE "X" GYP.
BOARD AT COMMON
WALLS AND ALL
CEILINGS - TYP.
20 Min. Self-Closing Solid
Core Door
HEATSENSOR HS P.T. 2X10 Deck Jsts. @ 16" o.c.SD AC/DC
INTERCONNECT
20 Min. Self-
Closing Solid
Core Door
3 x 9 1/4 Beam
2-1 3/4" x 9 1/2" LVL Beam
P.T. 2-2x10 BEAM 4x4 Post4x4 Post4x4 Post
10'-10"5'-9"7'-2"8'-5"8'-7"
22'-10"7'-2"17'
47'13'-5"4'-2 3/4"9'-4 1/4"9'1'27'10'24'-2"22'-10"
3'-2 1/2"3 1/2"3'-2 1/2"9'-10"3'-7"9'-7"4'6'-9"5'-9"10'-9"4'9'-1 1/2"3 1/2"
23'-8 1/2"27'9'-2" V.I.F.1'10'1'3'-3"6'-5 1/2" V.I.F.1'1'652 sq ft
Living
Area
Lndry.
Closet
Family
Bedroom
Garage
P.T. 2x10 LEDGER BOARD
BOLTED TO WALL W/ 1/2"
BOLTS @ 2'-0" O.C.
STAGGERED -TYP.CANT.CANT.STAIRS
DISTANCE TO STAIRSPROVIDE R-21
KRAFT FACED F.G.BATT INSULATION INCOMMON GARAGEWALL.
3 1/2" DIA.CONCRETE FILLEDLALLY COLUMN(TYP.)
BEARING WALL
3 1/2" DIA.CONCRETE FILLEDLALLY COLUMN
(TYP.)Storage1st Floor
DN
306826682668 2068266840682668
2668246826682668
2030 SAFETY 6068
30493049
UP
DN
PORCHPRE-ENGINEERED TRUSSED ROOF -TO BE DESIGNED BY OTHERSPRE-ENGINEERED TRUSSED ROOF -TO BE DESIGNED BY OTHERS30"x30" MIN. ATTICACCESS,WEATHER STRIPAND INSULATE TOR-38 MIN.
SD/CO
AC/DC
INTERCONNECTED
SMOKE & CARBON
MONOXIDE
DETECTOR/ALARM
EF
EXHAUST
FAN/LIGHT
EF
EXHAUST
FAN/LIGHT
Exact kitchen cabinetdesign and layout tobe completed bykitchen designer.
SD AC/DC
INTERCONNECT
SD AC/DC
INTERCONNECT
SD AC/DC
INTERCONNECT
8'-6"8'-6"4'-6"6'-1 1/2"5'-6"5'-10"2'-8"3'-2"5'-5 3/4"5'-4 1/4"3'-10 1/2"5'5'-9 1/2"
6'-2"4'-2"
10'-4"2'-4"10'-7 1/2"6'-8 1/2"17'
47'14'14'28'1'1'5'9'-4 1/2"5'-9 1/2"5 1/2"5'-3"5'-6 1/2"2'-7"13'
20'-7 1/2"10'-9 1/2"15'-7"
47'11'3'3'4'-6"2'-7 1/2"11'-4 1/2"1245 sq ft
Living
Area
Landing
Living
Kitchen
Bedroom
Master Bdrm
Master Bath
Bedroom ClosetClosetBath
Closet
Dining
Closet PRE-ENGINEERED SCISSORTRUSSED ROOF - TO BEDESIGNED BY OTHERSPRE-ENGINEERED SCISSORTRUSSED ROOF - TO BEDESIGNED BY OTHERS1/2 WALL
RAILINGTUB/SHOWER
TUB/SHOWER
Linen ISLAND3030
3049 EGRESS 3049 EGRESS
3049 EGRESS
3049 EGRESS2nd Floor
Wall Schedule2D Symbol Wall Type
8" Concrete Stem Wall
Exterior-2x6
Interior-2x6
Interior-2x4
Deck Railing/Fence
Lisa Kobar
PO Box 1
Yantic
CT 06389
860-287-1025
Lisa@CSDplans.com
1/4"=1'-0"
SHEET:
SCALE:
DRAWINGS
PROVIDED BY:DESCRIPTIONCornerstone
Designs
DATE:DATENO.PROJECT DESCRIPTION:SHEET TITLE:A-2
10/24/2025Heller DevelopmentPRELIMINARY ONLYP R E LIM IN A R Y