May 11th, 2026
Subject: 35 Leitao Drive, Montville, CT review of engineered plans for a household subsurface
sewage disposal system, dated: May 7th, 2026.
To: Franklin Dallas
From: Donovan Moe, Environmental Health Inspector
Engineer: Jacob Faulise P.E./ Boundaries LLC. Date received: 5/7/2026
Reason for submission: Minimum perc rate faster than 1 min/inch
High maximum ground water level Shallow ledge rock Other
New construction Repair
Design specifications: MLSS: 42’ Ft. required, 50’ Ft. provided
# of Bedrooms: 3 Design perc rate: 10 Min/Inch
Septic tank: 1,000 Gallons Fill: 2’ Feet and 25’ Feet Down-Gradient
Leaching system: 50' of GST 6212 @ 10 sf/lf = 500 sf; 495 sf required
Drains: No drains noted.
Water supply: Existing well off the East corner of the house
Plan review only, not approval to construct
Approved
Approved with modifications & provisions noted (revised plan required).
Conditional approval subject to further testing as noted (additional test holes are required).
Conditional approval with modifications or provisions noted (revised plan required).
Approval denied, revise as noted (revised plan required).
Approval denied, insufficient information on plan (revised plan required).
Approval denied, further site investigation required.
Comments:
1] Prior to the start of construction, the house, well, and system are to be staked &
a benchmark set in the area of the system by a licensed surveyor.
2] After the fill is placed and compacted, it must be perc tested prior to installation of the
system.
3] Property line variance noted on plan for septic system 14’ feet from down-gradient property line.
4] No future additions to be added onto property as property does not meet B100a compliance.