HomeMy WebLinkAbout26 0529-1 Rev1 Submittal Action Sheet-Hanger rods response-Azt MAGGIORE CONSTRUCTION CORP.
13 Wheeling Avenue, Woburn, MA 01801 Phone 781.935.6100 FAX 781.933.8044
SUBMITTAL ACTION SHEET
Oxoboxo Lofts
40 Pink Row
Uncasville, CT
General Contractor:Architect:
Maggiore Construction Corp.Paul B Bailey Architects
13 Wheeling Ave.110 Audubon Street
Woburn, MA 01801 New Haven, CT 06510
Job No.: 1529 Job No.: 16-063
Prepared By:Maggiore Construction Corp.
Form of Submittal:
Samples Cut Sheets Schedule Shop Drawings Other
Description:Hanger rods shopdrawings
Manufacturer:Eaton
Other/Notes:Response to engineers comments
Received By MCC:12/6/2019 Received By Owner:
Reviewed:Comments:
Approved Approved as Noted
Rejected Revise and Re-submit
Compliance Equal Submitted For Approval
By: Gifford Perry - Senior Project Manager Approved By:
Date:12/6/2019 Date:
Horton Electrical Services,LLC
Canton Business Park
97 River Road
Canton, Connecticut 06019
(860)693.6388
(860)693.6517 FAXLicense # CT E-192436
Date:12/3/2019
Job:19-01-021 OXOBOXO Phase 1
Letter of Transmittal
Transmittal #:7To:Gifford Perry
Subject:Response to Engineers notes from Hangers & Supports 26 0529 Submittal
Samples
Change order
Shop drawings
Under separate cover via the following items:AttachedWE ARE SENDING YOU
Submittal
Prints Plans
Copy of letter Spec. Section
DescriptionNo.DateCopiesDocument Type
1 12/3/19 26 0529-1 Rev 1 Hangers & SupportsSubmittal
Other
PRINTS RETURNED AFTER LOAN TO USFOR BIDS DUE
For review and comment
Return ___ corrected printsReturned for corrections
Submit ___ copies for distributionApproved as noted
For approval Resubmit ___ copies for approvalApproved as submitted
THESE ARE TRANSMITTED as checked below:
Remarks:
For your use
As requested
Copy To:Gerry Campion (Horton Electrical)
Signature:From:Marilyn Horton (Horton Electrical Services, LL)
If enclosures are not as noted, kindly notify us at once. Page 1 of 1
Horton Electrical Services 97 River Road, Canton, CT 06019
HORTON ELECTRICAL SERVICES, LLC
OXOBOXO LOFTS
12/3/19 HANGERS & SUPPORTS
RESPONSE TO RETURNED SUBMITTAL DATED 11/11/19
1. Did not see hanger rod products data. If they will be used submit on them.
• Confirmed. Hanger rod information is included with this response.
Reference page 45 for general fitting and standard finish specifications.
Part No. Threads Recommended Load Wt./C Ft.(3048.0 cm)
& Size Per Inch Lbs. kN Lbs. kg
ATR 1/4”20 240 (1.07)12 (5.44)
ATR 5/16”18 400 (1.78)19 (8.62)
ATR 3/8”16 730 (3.24)29 (13.15)
ATR 1/2”13 1350 (6.00)53 (24.04)
ATR 5/8”11 2160 (9.60)89 (40.37)
ATR 3/4”10 3230 (14.37)123 (55.79)
ATR 7/8”9 4480 (19.93)170 (77.11)
ATR 1”8 5900 (26.24)225 (102.06)
ATR
All Threaded Rod
• Available in 36” (91.4 cm), 72” (182.9 cm), 120” (304.8 cm), 144” (365.7 cm)lengths
• Safety Factor of 5 on recommended load
• Standard finish: Zinc-Plated, Stainless Steel Type 304
B655 Rod Coupling
B656 Reducer Rod Coupling
• Load rating for each coupler meets
All Threaded Rod value
• Standard finish: Zinc-Plated,
Stainless Steel Type 304
BHR Series
Hot Rods for Trapeze Hangers
• 12” length of threaded rod completely assembled with rod
coupling, locking hex nuts, square washer, and channel nut.
• Standard finish: Zinc-Plated
Recommended
Part No. Size Load Length Wt./C
Lbs. kN In. mm Lbs. kg
B655-1/4 1/4”-20 240 (1.07)7/8”(22.2)1.9 (.86)
B655-5/16 5/16”-18 380 (1.69)7/8”(22.2)1.8 (.81)
B655-3/8 3/8”-16 730 (3.24)11/8”(28.6)3.6 (1.63)
B655-1/2 1/2”-13 1350 (6.00)13/4”(44.4)11.3 (5.12)
B655-5/8 5/8”-11 1810 (8.05)21/8”(54.0)17.6 (7.98)
B655-3/4 3/4”-10 2710 (12.05)21/4”(57.1)28.1 (12.74)
B655-7/8 7/8”-9 3770 (16.77)21/2”(63.5)57.2 (25.94)
B655-1 1”-8 4960 (22.06)23/4”(69.8)73.7 (33.43)
Recommended
Part No.Size Load Length Wt./C
Lbs. kN In. mm Lbs. kg
B656-3/8 x 1/4 3/8”-16 & 1/4”-20 240 (1.07)1”(25.4)3.7 (1.68)
B656-1/2 x 3/8 1/2”-13 & 3/8”-16 730 (3.24)11/4”(31.7)6.6 (2.99)
B656-5/8 x 1/2 5/8”-11 & 1/2”-13 1350 (6.00)11/4”(31.7)11.6 (5.26)
B656-3/4 x 5/8 3/4”-10 & 5/8”-11 1810 (8.05)11/2”(38.1)20.6 (9.34)
B656-7/8 x 3/4 7/8”-9 & 3/4”-10 2710 (12.05)13/4”(44.4)39.4 (17.87)
Recommended
Part No.Rod Size Load Wt./C
Lbs. kN Lbs. kg
BHR1225ZN 1/4”-20 240 (1.07)41 (18.6)
BHR1238ZN 3/8”-16 730 (3.24)63 (28.6)
BHR1250ZN 1/2”-13 1350 (6.00)98 (44.4)
BHR1262ZN 5/8”-11 1500 (6.67)148 (67.1)Channel Nuts & Hardware(BHR1225, BHR1238, and BHR1250 use combo nut washers instead of square washers and channel nuts)
Note: Based on use with 12 ga. channel.
Hardware
Strut Systems59
OXOBOXO LOFTS
42 Pink Row
Uncasville, CT
GENERAL CONTRACTOR:
Dakota Partners
1264 Main Street
Waltham, MA 02451
ELECTRICAL CONTRACTOR:
Horton Electrical Services
97 River Road
Canton, CT 06019
860‐693‐6388
Hangers & Supports
26 0529
CIVIL ENGINEER:
BSC Group
300 Winding Brook Drive
Glastonbury, CT 06033
STRUCTURAL ENGINEER:
Morrissey Engineering, LLC
58 Essex Street
Deep River, CT. 06417
ARCHITECT:
Paul B. Bailey Architect, LLC.
110 Audubon Street
New Haven, CT 06510
MECHANICAL/ELECTRICAL ENGINEER:
Aztech Engineer, Inc.
901 Wethersfield Avenue
Hartford, CT 06114