HomeMy WebLinkAbout23 0513 Submittal Action Sheet-VFD's for pumps - AZT. . . . . . . . . . . . . . . . . . . . . . . . . . . .
D/E/F Services Group, LTD
1171 Voluntown Road
Griswold, CT 06351
Phone: (860) 376-4896
Fax: (860) 376-1213
Submittal
Transmittal
TO: The Maggiore Companies
13 Wheeling Ave.
Worburn, MA 01801
Date: 9/26/2019
Project # F29166 - F29166 Oxoboxo
Submittal # 010
ATTN: Gifford Perry
RE: (ABB) VFD's for Pumps #1, #2
We are sending you the following: Attached Under Separate Cover
Via: 1st Class Mail Overnight Facsimile Pick-Up/Hand Deliver
Copies Spec No. Description
1 230513 (ABB) VFD's for Pumps #1 & 2 (HVAC)
Remarks: Please see the attached submittal for approval.
Received By: _________________________________ Date: ________________________
Signed: _______________________________
Title: _________________________________
Copy to: ___________________
Recipient’s Copy
Sign & Return
File Copy
ABB
ACH580
AC MOTOR SPEED CONTROL
SUBMITTAL FOR:
APPROVAL
PROJECT: Oxoboxo Lofts
ENGINEER: Aztech Engineer, Inc.
Hartford, CT
CONTRACTOR: D/E/F Services
Griswold, CT
SUBMITTED BY: Andrew Marques
10 Bidwell Road
South Windsor, CT 06074
860-221-3172
FLOW TECH #: 1906123800
SUBMITTAL DATE: 9/25/2019
Submittal Schedule
This schedule includes the products supplied as part of this submittal.
Schedule Motor Data1 Drive Data
Item Qty Tag HP FLA Volts Product ID HP Amps Volts
1 1 P-1 15 46.2 208
VAC ACH580-PCR-046A-2+J429 15 46.2 208
VAC
2 1 P-2 15 46.2 208 VAC ACH580-PCR-046A-2+J429 15 46.2 208 VAC
Notes: 1. AC motor data is per National Electrical Code Table 430.250 for typical motors used in most
applications. It is provided as typical data only. DC motor data is per typical industry
standards. Actual motor data may vary
Submittal Schedule Details for P-1
Item Tag / Equipment ID Product ID
1 P-1 ACH580-PCR-046A-2+J429
Item Description
Input Voltage: 208 VAC Three Phase
Rated Output Current: 46.2A
Enclosure: UL (NEMA) Type 1
Nominal Horsepower: 15 HP
Frame Size: R3
Input Disconnecting Means: Circuit Breaker
Bypass: None
Input Impedance: 5% equivalent impedance
Short Circuit Current Rating: 100 kA
Communication Protocols: Johnson Controls N2, Modbus RTU, BACnet (MS/TP) Other Options: [+J429]: Bluetooth control panel
Drive Input Fuse Ratings
Fuse Class Amps (600 V)
Class J 80
Wire Size Capacities of Power Terminals
Input Wiring Output Wiring Ground Wiring
#14…#1/0
5.2 lbf-ft
#20…#2
2.6 lbf-ft
#14…#2 #14…#10: 2.9 lbf-ft; #6…#4:
3.8 lbf-ft; #2: 4.1 lbf-ft
Dimensions and Weights
Height
in (mm)
Width
in (mm)
Depth
in (mm)
Weight
lbs (kg)
34.8
(885)
8.4
(213)
13.2
(336)
39
(17.7)
Heat Dissipation & Airflow Requirements
Power Losses Airflow
BTU/Hr Watts CFM CM/Hr
1,204 353 105 178.4
Submittal Schedule Details for P-2
Item Tag / Equipment ID Product ID
2 P-2 ACH580-PCR-046A-2+J429
Item Description
Input Voltage: 208 VAC Three Phase
Rated Output Current: 46.2A
Enclosure: UL (NEMA) Type 1 Nominal Horsepower: 15 HP Frame Size: R3
Input Disconnecting Means: Circuit Breaker
Bypass: None
Input Impedance: 5% equivalent impedance
Short Circuit Current Rating: 100 kA
Communication Protocols: Johnson Controls N2, Modbus RTU, BACnet (MS/TP)
Other Options: [+J429]: Bluetooth control panel
Drive Input Fuse Ratings
Fuse Class Amps (600 V)
Class J 80
Wire Size Capacities of Power Terminals
Input Wiring Output Wiring Ground Wiring
#14…#1/0
5.2 lbf-ft
#20…#2
2.6 lbf-ft
#14…#2
#14…#10: 2.9 lbf-ft; #6…#4:
3.8 lbf-ft; #2: 4.1 lbf-ft
Dimensions and Weights
Height
in
(mm)
Width
in
(mm)
Depth
in
(mm)
Weight
lbs
(kg)
34.8
(885)
8.4
(213)
13.2
(336)
39
(17.7)
Heat Dissipation & Airflow Requirements
Power Losses Airflow
BTU/Hr Watts CFM CM/Hr
1,204 353 105 178.4
—
PRODUCT OVERVIEW
ACH580-01/-31
The ACH580 drive sets new standards in both simplicity and reliability, and ensures
smooth, energy-efficient operation of your HVAC systems in normal and mission-critical
situations.
ACH580-01, wall-mounted base drives
The ACH580-01 wall-mounted drives are available from 1 to 100 HP at 208/240 V, 1 to 350 HP at
480 V, and 2 to 250 HP at 575 V. The ACH580-01 drives are available in UL (NEMA) Type 1 and 12 configurations.
In standard installations, the drive is mounted directly onto a wall and uses the provided conduit box. Conduit
openings are provided for bottom conduit entry & exit. For mounting in a customer-supplied cabinet, the conduit
box may be removed. The drive has a 100 kA SCCR rating when paired with appropriately sized upstream fuses.
ACH580-31, ultra low harmonic wall-mounted base drives
The ACH580-31 wall-mounted drives are available from 5 to 150 HP at 480 V. The ACH580-31 are available in UL
(NEMA) Type 1 and 12 configurations. In standard installations, the drive is mounted directly onto a wall and uses
the provided conduit box. Conduit openings are provided for bottom conduit entry and exit. For mounting in a
customer-supplied cabinet, the conduit plate may be removed.
Features for HVAC
The ACH580 comes standard with an intuitive control panel used to configure, control, and monitor the drive. An
optional Bluetooth control panel allows the drive to be configured via the control panel or the DriveTune app.
A robust HVAC firmware package provides drive, motor, and application protection features. Examples of drive
protection features include undervoltage, overvoltage, overcurrent, and ground fault protection. The ACH580 also
has a variety of motor protection features including overload and stall protections.
Application specific features, such as accepting four separate start interlocks (safeties), along with broken belt
detection, are also included. The drive includes BACnet MS/TP, Modbus RTU, and Johnson N2 as standard.
Additional protocols, such as BACnet/IP and LonWorks (coming 2019), are available with optional fieldbus
adapters.
Technical specifications
Product compliance (complete list on following page)
ACH580-01/-31 CE, UL, cUL, and EAC
Supply connection
Input voltage (U1)
ACH580-xx-xxxA-2
ACH580-xx-xxxA-4
ACH580-xx-xxxA-6
Input voltage tolerance
Phase
208/240V
480V
600V
+10% / -15%
3-phase (1-phase, 240 V)
Frequency 48 to 63 Hz
Line Limitations Max ±3% of nominal phase to phase input voltage
Power Factor (cos φ) at nominal load
ACH580-01
ACH580-31
0.98
1.0
Efficiency at rated power
ACH580-01
ACH580-31
98.0%
96.5%
Power Loss Approximately 2% of rated power
Motor connection
Supported motor control Scalar and vector
Supported motor types Asynchronous motor, permanent magnet motor
(vector), SynRM (vector)
Voltage 3-phase, from 0 to supply voltage
Frequency 0 to 500 Hz
Short Term Overload Capacity Variable Torque 110% for 1 min/10min
Peak Overload Capacity
Variable Torque
1.35 for 2 second
(2 sec / 10 min)
Switching Frequency 2, 4, 8 or 12 kHz
Automatic fold back in case of overload
Acceleration/Deceleration Time 0 to 1800 s
Short Circuit Current Rating (SCCR) 100 ka with fusing
Inputs and outputs (drive)
2 analog inputs Selection of Current/Voltage input mode is user
programmable.
Voltage reference 0 (2) to 10 V, Rin > 200 kΩ
Current reference 0 (4) to 20 mA, Rin = 100 Ω
Potentiometer reference value 10 V ±1% max. 20 mA
2 analog outputs
AO1 is user programmable
for current or voltage.
AO2 current
Voltage reference 0 to 10 V, Rload: > 100 kΩ
Current reference 0 to 20 mA, Rload: < 500 Ω
Applicable potentiometer 1 kΩ to 10 kΩ
Internal auxiliary voltage 24 V DC ±10%, max. 250 mA
Accuracy +/- 1% full scale range at 25°C (77°F)
Output updating time 2 ms
6 digital inputs
12 to 24 V DC, 10 to 24 V AC,
Connectivity of PTC sensors supported by a single
digital input.
PNP or NPN connection
(5 DIs with NPN connection).
Programmable
Input Updating Time 2 ms
3 relay outputs
Maximum switching voltage
250 V AC/30 V DC.
Maximum continuous current 2 A rms.
Programmable, Form C
Adjustable filters on analog inputs and outputs
All control inputs isolated from ground and power
Operation
Air temperature
0 to -15 °C (32 to 5 °F).
-15 to +50 °C (5 to 122 °F):
No frost allowed.
Output derated above +40 °C (104 °F)
Installation site altitude
0 to 4000 m (13123 ft)
above sea level
Output derated above 1000 m (3281 ft)
Relative humidity
5 to 95%
No condensation allowed
Maximum relative humidity is 60% in the presence of
corrosive gasses
Atmospheric pressure 70 to 106 kPa (10.2 to 15.4 PSI)
0.7 to 1.05 atmospheres
Vibration Risk category IV Certified (IBC 2018)
Environmental protections
Chemical Gasses Class 3C2
Solid Particles Class 3S2
No conductive dust allowed
Pollution degree (IEC/EN 61800-5-1) Pollution degree 2
Product compliance
Standards and directives Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
60721-3-3: 2002
60721-3-1:1997
Quality assurance system ISO 9001 and
Environmental system ISO 14001
CE, UL, cUL, and EAC approvals
Galvanic isolation according to PELV
RoHS2 (Restriction of Hazardous Substances)
EN 61800-5-1: 2007; IEC/EN 61000-3-12;
EN61800-3: 2017 + A1: 2012 Category C2
(1st environment restricted distribution);
Safe torque off (EN 61800-5-2)
BACnet Testing Laboratory (BTL)
Seismic (IBC, OSHPD)
Plenum (ACH580-01 only)
EMC (according to EN61800-3) ACH580-01 and ACH580-31 class C2
(1st environment restricted distribution)
Storage (in Protective Shipping Package)
Air Temperature -40 to +70 °C (-40 to +158 °F)
Relative Humidity
Less than 95%
No condensation allowed
Maximum relative humidity is 60% in the presence of
corrosive gasses
Chemical Gasses Class 1C2
Solid Particles Class 1S2
Contact ABB regarding Class 1S3
Atmospheric pressure 70 to 106 kPa
0.7 to 1.05 atmospheres
Vibration (ISTA)
R1…R4
R5…R9
In accordance with ISTA 1A
In accordance with ISTA 3E
Transportation (in Protective Shipping Package)
Air Temperature -40° to 70°C (-40° to 158°F)
Relative Humidity
Less than 95%
No condensation allowed
Maximum relative humidity is 60% in the presence of
corrosive gasses
Atmospheric Pressure 60 to 106 kPa (8.7 to 15.4 PSI)
0.6 to 1.05 atmospheres
Free Fall
R1: 76 cm (30 in)
R2: 61 cm (24 in)
R3: 46 cm (18 in)
R4: 31 cm (12 in)
R5: 25 cm (10 in)
Chemical Gasses Class 2C2
Solid Particles Class 2S2
Shock/ Drop (ISTA)
R1…R4
R5…R9
In accordance with ISTA 1A
In accordance with ISTA 3E
Vibration (ISTA)
R1…R4
R5…R9
In accordance with ISTA 1A
In accordance with ISTA 3E
—
Feature overview
Communication
Protocols as standard (EIA-485): BACnet MS/TP, Modbus RTU,
Johnson Controls N2
Available as plug-in options: BACnet/IP, Modbus TCP, PROFIBUS-DP,
DeviceNet, EtherNet/IP, LonWorks (coming 2019)
Application functions
Start interlock
Delayed start
Run permissive (damper monitoring)
Override operation mode
Real-time clock (scheduling)
PID controllers for motor and process
Motor flying start
Motor preheating
Energy optimizer and calculators
Timer
2 or 3 wire start/stop
Ramp to stop
2 independent adjustable accel/decel ramp
Protection functions
Overvoltage controller
Undervoltage controller
Motor earth-leakage monitoring
Motor short-circuit protection
Motor overtemperature protection
Output and input switch supervision
Motor overload protection (UL508C)
Phase-loss detection (both motor and supply)
Under load supervision (belt loss detection)
Overload supervision
Stall protection
Loss of reference
Panel loss
Ground fault
External events
Overcurrent
Current limit regulator
Transient/Surge protection (MOV and choke)
Panel functions
First start assistant
Primary settings for HVAC applications
Hand-Off-Auto operation mode
HVAC quick set-up
Includes Day, Date and Time
Operator Panel Parameter Backup (read/write)
Full Graphic and Multilingual Display for Operator Control,
Parameter Set-Up and Operating Data Display:
- Output Frequency (Hz)
- Speed (RPM)
- Motor Current
- Calculated % Motor Torque
- Calculated Motor Power (kW)
- DC Bus Voltage
- Output Voltage
- Heatsink Temperature
- Elapsed Time Meter (resettable)
- kWh (resettable)
- Input / Output Terminal Monitor
- PID Actual Value (Feedback) & Error Fault Text
- Warning Text
- Three (3) Scalable Process Variable Displays
- User-Definable Engineering Units
Motor control features
Scalar (V/Hz) and vector modes of motor control
V/Hz shapes
- Linear
- Squared
Energy optimization
IR compensation
Slip compensation
Three (3) Critical Frequency Lockout Bands
PID control
One (1) Process PID
Four (4) Integral Independent Programmable PID
Setpoint Controllers (Process and External)
External Selection between Two (2) Sets of Process
PID Controller Parameters
PID Sleep/Wake-Up
—
Control panel features
The ACH580 Assistant Control Panel features:
- Intuitive to operate
- Primary Setting menu to ease drive commissioning
- Real-time clock
- Diagnostic and maintenance functions
- Full-graphic display, including chart, graph, and meter options
- 21 editable home views
- USB interface for PC and tool connection as standard
- Parameters are alpha-numeric
- North American version supports 14 languages as standard
- Dedicated “Help” key
- 4 user sets
- Parameter are stored in control panel memory for later transfer to other drives or for backup of a particular system
- Back-up and restore parameters and/or motor data
- Automatic back-up 2 hours after parameter change
- Modified parameter display
- Creates unique short menu
- Shows parameters that differ from the default
- Bluetooth connectivity for use with mobile device (requires +J429 option)
—
PRODUCT OVERVIEW
ACH580 Packaged Drives with Disconnect
The ACH580 drive sets new standards in both simplicity and reliability, and
ensures smooth, energy-efficient operation of your HVAC systems in
normal and mission-critical situations.
The ACH580 Packaged Drive is an ACH580 Variable Frequency Drive enclosed with either an input disconnect switch and
fast acting fuses (ACH580-PDR) or an input circuit breaker (ACH580-PCR). The ACH580 Packaged Drive provides a door-
mounted input disconnect operator (padlockable in the OFF position), electronic motor overload protection, a door mounted
control panel with graphical display for local control, provisions for external control connections, and serial communications
capability.
UL (NEMA) Type 1 and 12 Packaged Drive units are available from 1 to 100 HP at 208/230V, 1 to 550 HP at 460V, and 2 to
150 HP at 575V. UL (NEMA) Type 1 and 12 units are wall mounted from 1 to 200 HP and floor mounted from 250 to 550
HP.
For outdoor applications, UL (NEMA) Type 3R Packaged Drive units are available from 1 to 100 HP at 208/230V,
1 to 350 HP at 460V and 2 to 150 HP at 575V. Construction is sheet steel with a tough powder coat paint finish for corrosion
resistance. A thermostatically controlled space heater and forced ventilated air cooling system are standard.
Features for HVAC
The ACH580 comes standard with an intuitive control panel used to configure, control, and monitor the drive. An optional
Bluetooth control panel allows the drive to be configured via the control panel or the DriveTune app.
A robust HVAC firmware package provides drive, motor, and application protection features. Examples of drive protection
features include undervoltage, overvoltage, overcurrent, and ground fault protection. The ACH580 also has a variety of
motor protection features including overload and stall protections.
Application specific features, such as accepting four separate start interlocks (safeties), along with broken belt detection, are
also included. The drive includes BACnet MS/TP, Modbus RTU, and Johnson N2 as standard. Additional protocols, such
as BACnet/IP and LonWorks (coming 2019), are available with optional fieldbus adapters.
—
Technical specifications
Product compliance (complete list on following page)
ACH580-PxR
UL508A
Supply connection
Input voltage (U1)
ACH580-xx-xxxA-2
ACH580-xx-xxxA-4
ACH580-xx-xxxA-6
Input voltage tolerance
Phase
208/240V
480V
600V
+10% / -15%
3-phase (1-phase, 240 V)
Frequency 48 to 63 Hz
Line Limitations Max ±3% of nominal phase to phase input voltage
Power Factor (cos φ) at nominal load
ACH580-PxR
0.98
Efficiency at rated power
ACH580-PxR
98.0%
Power Loss Approximately 2% of rated power
Motor connection
Supported motor control Scalar and vector
Supported motor types Asynchronous motor, permanent magnet motor
(vector), SynRM (vector)
Voltage 3-phase, from 0 to supply voltage
Frequency 0 to 500 Hz
Short Term Overload Capacity Variable Torque 110% for 1 min/10min
Peak Overload Capacity
Variable Torque
1.35 for 2 second
(2 sec / 10 min)
Switching Frequency 2, 4, 8 or 12 kHz
Automatic fold back in case of overload
Acceleration/Deceleration Time 0 to 1800 s
Short Circuit Current Rating (SCCR)
240V 480V 600V
-PCR 100kA 100kA ≤60 Hp: 25 kA
≥75 Hp: 10 kA
-PDR 100kA 100kA 100kA
—
Technical specifications
Inputs and outputs (drive)
2 analog inputs Selection of Current/Voltage input mode is user programmable.
Voltage reference 0 (2) to 10 V, Rin > 200 kΩ
Current reference 0 (4) to 20 mA, Rin = 100 Ω
Potentiometer reference value 10 V ±1% max. 20 mA
2 analog outputs
AO1 is user programmable
for current or voltage.
AO2 current
Voltage reference 0 to 10 V, Rload: > 100 kΩ
Current reference 0 to 20 mA, Rload: < 500 Ω
Applicable potentiometer 1 kΩ to 10 kΩ
Internal auxiliary voltage 24 V DC ±10%, max. 250 mA
Accuracy +/- 1% full scale range at 25°C (77°F)
Output updating time 2 ms
6 digital inputs
12 to 24 V DC, 10 to 24 V AC,
Connectivity of PTC sensors supported by a single digital input.
PNP or NPN connection
(5 DIs with NPN connection).
Programmable
Input Updating Time 2 ms
3 relay outputs
Maximum switching voltage
250 V AC/30 V DC.
Maximum continuous current 2 A rms.
Programmable, Form C
Contact material Silver Tin Oxide (AgSnO2)
PTC, PT100 and PT1000
Any of the analog inputs, or digital input 6, are configurable for
PTC with up to 6 sensors.
Adjustable filters on analog inputs and outputs
All control inputs isolated from ground and power
Operation
Air temperature
0 to -15 °C (32 to 5 °F).
-15 to +50 °C (5 to 122 °F):
No frost allowed.
Output derated above +40 °C (104 °F)
Installation site altitude
0 to 1000 m (3281 ft)
above sea level
Output derated above 1000 m (3281 ft)
Relative humidity
5 to 95%
No condensation allowed
Maximum relative humidity is 60% in the presence of corrosive gasses
Atmospheric pressure 70 to 106 kPa (10.2 to 15.4 PSI)
0.7 to 1.05 atmospheres
Siesmic Risk category IV Certified (IBC 2018)
—
Feature overview
Communication
Protocols as standard (EIA-485): BACnet MS/TP, Modbus
RTU, Johnson Controls N2
Available as plug-in options: BACnet/IP, Modbus TCP,
PROFIBUS-DP, DeviceNet, EtherNet/IP
Application functions
Start interlock
Delayed start
Run permissive (damper monitoring)
Override operation mode
Real-time clock (scheduling)
PID controllers for motor and process
Motor flying start
Motor preheating
Energy optimizer and calculators
Timer 2 or 3 wire start/stop
Ramp to stop
2 independent adjustable accel/decel ramp
Protection functions
Overvoltage controller
Undervoltage controller
Motor earth-leakage monitoring
Motor short-circuit protection
Motor overtemperature protection
Output and input switch supervision
Motor overload protection (UL508C)
Phase-loss detection (both motor and supply)
Under load supervision (belt loss detection)
Overload supervision
Stall protection
Loss of reference
Panel loss
Ground fault
External events
Overcurrent
Current limit regulator
Transient/Surge protection (MOV and choke)
Panel functions
First start assistant
Primary settings for HVAC applications
Hand-Off-Auto operation mode HVAC quick set-up
Includes Day, Date and Time
Operator Panel Parameter Backup (read/write)
Full Graphic and Multilingual Display for Operator Control,
Parameter Set-Up and Operating Data Display:
- Output Frequency (Hz)
- Speed (RPM)
- Motor Current
- Calculated % Motor Torque
- Calculated Motor Power (kW)
- DC Bus Voltage
- Output Voltage
- Heatsink Temperature
- Elapsed Time Meter (resettable)
- kWh (resettable)
- Input / Output Terminal Monitor
- PID Actual Value (Feedback) & Error Fault Text
- Warning Text
- Three (3) Scalable Process Variable Displays
- User-Definable Engineering Units
Motor control features
Scalar (V/Hz) and vector modes of motor control V/Hz shapes
- Linear
- Squared
Energy optimization
IR compensation
Slip compensation
Three (3) Critical Frequency Lockout Bands
PID control
One (1) Process PID
Four (4) Integral Independent Programmable PID
Setpoint Controllers (Process and External)
External Selection between Two (2) Sets of Process
PID Controller Parameters PID Sleep/Wake-Up
—
Control panel features
The ACH580 Assistant Control Panel features:
- Intuitive to operate
- Primary Setting menu to ease drive commissioning
- Real-time clock
- Diagnostic and maintenance functions
- Full-graphic display, including chart, graph, and meter options
- 21 editable home views
- USB interface for PC and tool connection as standard
- Parameters are alpha-numeric
- North American version supports 14 languages as standard
- Dedicated “Help” key
- 4 user sets
- Parameter are stored in control panel memory for later transfer to other drives or for backup of a particular
system
- Back-up and restore parameters and/or motor data
- Automatic back-up 2 hours after parameter change
- Modified parameter display
- Creates unique short menu
- Shows parameters that differ from the default
- Bluetooth connectivity for use with mobile device (requires +J429 option)
51250837
16
—
Cable connections
The following illustrations show the ACH580 Packaged Drive cable connection points for the various enclosure styles.
The illustrations indicate the location of input and output power connections as well as equipment and motor
grounding connection points.
ACH580-PCR and PDR packages are configured for wiring access from the bottom only on vertical wall mount units
and from the top only on UL (NEMA) Type 1 and 12 standard wall mount units. UL (NEMA) Type 3R enclosures are
configured for bottom access. At least three separate metallic conduits are required, one for input power, one for
output power to the motor and one for control signals.
51250837
17
—
Cable connections
51250837
18
—
Control connections
51250837
19
—
Cable connections
51250837
20
—
Control connections
51250837
21
Item
1
Part Number
ACH580-PCR-046A-2+J429
Customer Designation
P-1
{3AXD50000313792_1.png}
51250837
22
Item 1 Part Number ACH580-PCR-046A-2+J429 Customer Designation P-1
{3AXD50000312191.png}
51250837
23
Item 1 Part Number ACH580-PCR-046A-2+J429 Customer Designation P-1
{3AXD50000222636.png}
51250837
24
Item 2 Part Number ACH580-PCR-046A-2+J429 Customer Designation P-2
{3AXD50000313792_1.png}
51250837
25
Item 2 Part Number ACH580-PCR-046A-2+J429 Customer Designation P-2
{3AXD50000312191.png}
51250837
26
Item 2 Part Number ACH580-PCR-046A-2+J429 Customer Designation P-2
{3AXD50000222636.png}