Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
15910-01-0 - Building Automation Controls - AZT
. . . . . . . . . . . . . . . . . . . . . . . . . . . . D/E/F Services Group, LTD 1171 Voluntown Road Griswold, CT 06351 Phone: (860) 376-4896 Fax: (860) 376-1213 Submittal Transmittal TO: The Maggiore Companies 13 Wheeling Ave. Worburn, MA 01801 Date: 1/21/2020 Project # F29166 - F29166 Oxoboxo Submittal # 30 ATTN: Gifford Perry RE: Building Automation Controls We are sending you the following: Attached Under Separate Cover Via: 1st Class Mail Overnight Facsimile Pick-Up/Hand Deliver Copies Spec No. Description 1 M3.4 Building Automation Controls Remarks: Please see the attached submittal for approval. Received By: _________________________________ Date: ________________________ Signed: _______________________________ Title: _________________________________ Copy to: ___________________ Recipient’s Copy Sign & Return File Copy Connecticut Temperature Controls LLC An Affirmative Action / Equal Opportunity Employer 500 Corporate Row Cromwell, CT 06416 Phone: (800) 890-2022 Fax: (860) 316-5348 OXOBOXO LOFTS UNCASVILLE, CT PRODUCT DATA & CONTROL DRAWINGS AUTOMATIC TEMPERATURE CONTROLS SYSTEM Mechanical Aztech Engineers Engineer 901 Wethersfield Ave Hartford, CT 06114 Mechanical D/E/F Services Group Contractor 1171 Voluntown Road Griswold, CT 06351 Connecticut Temperature Controls LLC An Affirmative Action / Equal Opportunity Employer TABLE OF CONTENTS SECTION 1: Material Data Sheets SECTION 2: Diagrammatic Control Drawings. ECLYPSE™ Connected System Controller Overview The ECLYPSE Connected System Controller is a modular and scalable platform used to control a wide range of HVAC applications. It supports multi-protocol communications, including BACnet/IP, and is a listed BACnet Building Controller (B-BC). The ECLYPSE Connected System Controller consists of a control, automation and connectivity server, power supply, and I/O extension modules. This programmable Connected System Controller provides advanced functionality, such as customizable control logic, Web-based design and visualization interface (ENVYSION embedded), logging, alarming, and scheduling. Applications The ECLYPSE Connected System Controller is typically used as: £A controller for medium/large sized Air Handling Units (AHU), central plant, lighting, power monitoring, and other applications. £Small building server and equipment controller with embedded ENVYSION. For example, it can be used to control and serve a boiler room. Features & Benefits Connectivity The different types of connections supported by the Connected System Controller are as follows: IP wired connection Internal switch with two Ethernet ports allows the controllers to be wired in a star or daisy- chain topology. With a daisy-chain topology: £Fewer wire runs to a centralized switch are required, thereby achieving installation and cost reduction. £A laptop can be connected to the second Ethernet port for direct programming, configuration, and commissioning using EC- gfxProgram or ENVYSION. IP wireless (Wi-Fi) connection £Wi-Fi Client - Connection to the building’s existing Wi-Fi network or to another controller’s Wi-Fi Hotspot or Access Point. £Wi-Fi Access Point - extending the building’s wired IP network to your Wi-Fi Client devices. D a t a s h e e t 2 / 20 ECLYPSE™ Connected System Controller £Wi-Fi Hotspot - your own wireless area network, for wireless communication between the controllers, or with a mobile device or laptop for configuration, commissioning and servicing. Both IP wired and wireless (Wi-Fi) connection The availability of both Ethernet ports and USB ports for the Wi-Fi Adapter, allows for simultaneous wired IP and Wi-Fi communication on the same controller, which means you can choose and combine these connection methods. For example, Wi-Fi can be used between two controllers to jump a large atrium. Connect from anywhere Control technicians, facility managers, occupants, and others can easily connect to the system, on-site or off-site, using the different available tools: £ENVYSION to create and view the graphical interface £EC-gfxProgram to create custom control sequences £myDC Control to view, edit, and configure system operating parameters IP Communication £Increased speed and improved handling of numerous trend logs that enable applications, such as advanced analytics that require a large amount of data. £Experience faster response and save time when programming, configuring, creating and viewing graphics, and upgrading your system. £Control technicians can connect the ECLYPSE Wi-Fi Adapter to the Connected System Controller thereby creating a Wi-Fi Hotspot network. The control technician can then connect wirelessly to the system using a mobile device or laptop, for faster, easier system configuration, programming, commissioning, and servicing. £Hostname management allows the controller to be addressed by a nickname to facilitate network management. Open to Web Services With the RESTful API, the Connected System Controller’s data can be accessed from different applications, such as energy dashboards, analytics tools, and mobile applications. The RESTful API documentation explains the implementation protocol for this interface. HTML5 Visual Interface The ECLYPSE Connected System Controller comes embedded with both ENVYSION Studio and Viewer, and xpressENVYSION. ENVYSION – Web-based graphic design and vi- sualization interface ENVYSION is a web-based graphic design and visualization interface used to create and deliver interactive graphical user interfaces and an optimal user experience for building owners and facility managers to better manage facility data. Programmability Supports Distech Controls’ EC-gfxProgram, which makes Building Automation System (BAS) programming effortless, by allowing you to visually assemble building blocks to create a custom control sequence for any HVAC , lighting, or building automation application. Batch EC-gfxProgram Projects and Firmware Download EC-gfxProgram projects can be downloaded in batch to multiple controllers, for greater time savings. Batch firmware update can also be performed on multiple controllers. Simplified Network Commissioning The XpressNetwork Utility saves you time and expense by giving you increased control over multiple ECLYPSE controllers through device discovery and batch operations such as configuring, programming, and updating multiple ECLYPSE controllers on the network. ECLYPSE™ Connected System Controller 3 / 20 In addition, with the embedded step by step Commissioning Wizard, all configuration operations can be setup and applied in one go. Increase productivity using the xpressNetwork Companion mobile app, making it easier to identify and locate a controller on the network. Use the QR Code marked on ECLYPSE controllers to easily collect key controller data and to facilitate its network integration with xpressNetwork Utility. Scalable and Modular The Connected System Controller is sized to cost-effectively meet the requirements of any HVAC application from small to medium to large systems. The most capable Connected System Controller model can be expanded to support up to 20 input/output (I/O) modules (up to 320 I/Os) while being able to adapt to new requirements as the need arises. ECY-RS485 communication module An ECY-RS485 communication module adds two extra RS-485 trunks to support more BACnet MS/TP and Modbus RTU devices. A connecting cable is used to connect successive rows of modules within a controls’ cabinet to provide power and communication. BACnet/IP Device (pending) The Connected System Controller is BTL-listed as a BACnet Building Controller (B-BC) and is certified WSP B-BC (Europe) and AMEV AS-A & AS-B (German-speaking countries). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus. Multi-Protocol Support The Connected System Controller supports a range of communication protocols such as BACnet MS/TP, Modbus RTU, and Modbus TCP. BACnet MS/TP and Modbus RTU communications are made by connecting directly to separate RS-485 ports. The Connected System Controller integrates up to three RS-485 ports when equipped with one ECY-RS485 extension module allowing the controller to support more than one trunk or communication protocol at a time. MS/TP to IP routing Integrate full MS/TP trunks into a supervisory system like the EC-NetAX Supervisor, without the need for other hardware components such as an external BACnet MS/TP to IP router. Modbus RTU and TCP Modbus RTU and TCP communication can be used to integrate a wide variety of Modbus devices such as power and water meters, Variable Frequency Drives, air flow sensors, and more, without the need for additional hardware such as a gateway. FIPS 140-2 Level 1 Compliant FIPS 140-2 Level 1 compliance provides an enhanced level of security to protect data the controller is collecting and sharing making it suitable for use in the most sensitive environments. Weather Forecast The weather forecast is directly available from the internet to be shown on a connected ECx- Display or to be used by the controller’s code. Smart Room Control Support The Smart Room Control solution is an end-to- end system for the control of HVAC equipment, lighting, and shades/sunblinds, achieving the highest levels of comfort for occupants while cutting costs from installation time and wiring/ material requirements to energy consumption. This solution combines: £Lighting and shade/sunblind expansion modules to control lights (DALI, on/off or dimming) and shades/sunblinds (24 VDC or 100-240 VAC, up/down and angle rotation). £Multi-sensor combining motion and luminosity (Lux) sensors and equipped with an Infrared receiver that works with a convenient remote control. £Wireless (infrared) personal remote control for increased occupant comfort. £Allure™ Series Communicating Sensors for increased occupant comfort settings. Allure™ Series Communicating Sensor Support These controllers work with a wide range of sensors, such as the Allure Series Communicating Sensors that are designed to provide intelligent sensing and control devices for increased user experience and energy efficiency. £Allure EC-Smart-Vue sensors feature a backlit-display and graphical menus that provide precise environmental zone control, with any combination of the following: temperature, humidity, CO2, and motion sensor. 4 / 20 ECLYPSE™ Connected System Controller £Allure EC-Smart-Comfort sensors feature colored LED indicators to provide user feedback, rotary knobs to adjust the setpoint offset and fan speed, and an occupancy override push button. This sensor can also be expanded with a combination of up to 4 add-on push button modules for lighting and shade/ sunblind control. £Allure EC-Smart-Air sensors combine precise environmental sensing in a discreet and alluring enclosure for temperature, humidity, and CO2. Mobility The controller can be remotely accessed to program, configure, or maintain the installation thus reducing costs associated with on-site visits. Through a mobile device or PC, a range of tasks can be performed using the following free-to-use tools and interfaces: £ENVYSION web-based graphic design and visualization interface £EC-gfxProgram graphical programming interface £myDC Control mobile application Hand/Off/Auto Switches and Potentiometers The front assembly of Hand/Off/Auto (HOA) equipped I/O models allow users to override the control outputs for commissioning and maintenance purposes. Universal outputs have potentiometers providing manual analog signal and output control to override voltage or current signal. High-Efficiency Design The power supply uses the latest high-efficiency switch-mode circuitry to make more power available to operate additional modules and for cooler operation. Hot-Swappable Tool-Less Design and Unique Latching Mechanism The I/O modules are hot-swappable for replacement without interrupting power and communications to other modules. The front assembly of I/O modules separate from the wiring base by pushing the two latches up to unlock a module’s front assembly and then opening and pulling the hinged gull-wing covers. The latch design locks the front assembly to the wiring base. The hinged gull-wing design protects and cover the stacked dual row I/O terminal strips. Ease of Installation The Connected System Controller modules are plug & play devices. They are equipped with HD-15 connectors that transmits power and communications to the next module for fast and easy assembly. I/O Status LEDs The status LEDs on the I/O modules allows the user to confirm the status of the inputs/outputs and facilitate commissioning and troubleshooting. Auto-Addressing The auto-addressing feature eliminates the need to manually assign an address to each I/O module therefore reducing installation and configuration time. Digital Inputs Up to 120Hz The ECY-16DI module supports pulsed signals up to 120Hz for equipment status monitoring and alarm point monitoring, commonly used in energy metering applications. ECLYPSE™ Connected System Controller 5 / 20 Color-Coded, Rising Cage Terminals Terminal blocks are uniquely identified and color-coded for clarity and to prevent wiring mistakes. The rising cage clamp terminal block connectors offer a more robust and secure wire connection, designed to withstand activity and vibrations. Robust Protection The I/O modules are protected against mis- wiring and faults to prevent damage caused by incorrect wiring or other mishaps. The power supply module contains over-voltage and over-current output protection to protect the electronics in unstable power supply conditions and against mis-wiring. Alarms, Trend Log, Schedule Support Embedded alarms, trend log and schedule support allows for fully distributed data and logic providing a more robust system. Embedded trend logs simplify system troubleshooting when compared to a centralized system. Email Notifications Service Technicians & facility managers can receive automatic email notifications for system status and alarms to ensure faster system servicing and response time. Email notification text can be customized to provide pertinent information about the issue at hand. 6 / 20 ECLYPSE™ Connected System Controller Model Selection The ECLYPSE Connected System Controller consists of a power supply, a control, automation and connectivity server, I/O extension modules, and communication modules to create a controller tailored to its application. The different models for each are shown in the tables below. Power Supply A power supply module must be added after each HD15 cable (see Accessories below). ECY-PS24 24VAC/VDC power supply module for the ECLYPSE Connected System Controller. ECY-PS100-240 100 to 240VAC power supply module for the ECLYPSE Connected System Controller. Control, Automation and Connectivity Servers Connected System Controller for medium/large sized AHU and plant applications and small building server/controller applications. Model With Embedded ENVYSION Application Maximum Number of Points Supported BACnet MS/TP to IP Routing Support – Maximum Number of BACnet MS/TP Devices Maximum Number of Modbus Devices (RTU or TCP) ECY-S1000-28 Small size equipment such as a large rooftop unit or a small AHU. 28 No1 3 ECY-S1000E-28 ECY-S1000-28-MS 28 Yes2 3 ECY-S1000E-28-MS ECY-S1000-48 Medium size equipment such as an AHU or a small size plant room 48 No1 10 ECY-S1000E-48 ECY-S1000-48-MS 48 Yes2 10 ECY-S1000E-48-MS ECY-S1000 Large size equipment such as large plant rooms and large data centers. 3204 Yes2 963 ECY-S1000E 1.Upgrade and enable the functionality of your ECLYPSE controller’s RS-485 ports with our capacity-based upgrade to ECYS1000-48MS. 2.Up to 50 BACnet MS/TP devices recommended on each RS-485 port. 3.Up to 32 Modbus RTU devices recommended on each RS-485 port. 4.The ECY-S1000 models support a maximum of 320 points OR up to a maximum of 20 IO modules. ECLYPSE™ Connected System Controller 7 / 20 I/O Modules Selection Inputs Outputs Basic Power Consumption2,WQuantityDigital Analog 18VDC Power SupplyQuantityDigital Analog HOAContactCounter120Hz Pulse Counting0 to 10VDC0 to 5VDC0 to 20mAResistanceThermistor0-277VAC / 0-30VDCForm-C, 10A24VAC Triac, 0.5 A0 or 12VDCPWMFloating0 to 10VDC10 to 20mA1ECY-8UI 8 0.94 ECY-16DI 16 0.94 ECY-6UO 6 UO1 UO2 UO3 0.94 ECY-6UO-HOA 6 UO1 UO2 UO3 0.94 ECY-8DOR 8 0.94 ECY-8DOR-HOA 8 0.94 ECY-4UI4UO 4 4 UO1 UO2 UO3 0.94 ECY-4UI4UO-HOA 4 4 UO1 UO2 UO3 0.94 ECY-8UI6UO 8 6 UO1 UO2 UO3 0.94 ECY-8UI6UO-HOA 8 6 UO1 UO2 UO3 0.94 ECY-8UI6DOT 8 6 0.94 ECY-8UI6DOT-HOA 8 6 0.94 1.0 to 10VDC is available on UO1 to UO6. 0 to 20 mA is available on UO1, UO2, and UO3; this option is individually selected through an on-board DIP switch setting. 2.External loads excluded. See the ECLYPSE Selection Tool to calculate the number of Input/Output Extension Modules that can operate with a power supply. Communication Modules Selection Communications Module Description ECY-RS485 ECLYPSE Communication module with two RS-485 ports for Modbus RTU or BACnet MS/TP. Accessories ECLYPSE HD15 Cable 6ft (1.8m) cable for Connected System Controller multiple-row panel installations. An HD15 cable must always be followed by a power supply module. For more information, refer to the Hardware Installation Guide. ECLYPSE Wi-Fi Adapter Wi-Fi Adapter for ECLYPSE Connected Controllers. 8 / 20 ECLYPSE™ Connected System Controller Product Specifications Power Supply (ECY-PS24) Power Supply Input Voltage Range 24VAC/DC; ±15%; Class 2 Power Consumption 60VA Frequency Range 50 to 60Hz Overcurrent Protection Field replaceable fuse Fuse Type 4A, fast-acting, 5 × 20mm (GMA-4A) Power Supply Output DC Voltage 18VDC regulated Rated Current Range 0 to 1.6A Rated Power 30W1 1.The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connected loads, must be less than this value. A separate transformer rated at 60VA minimum and 100VA maximum must be used for each ECY-PS24 power supply for it to operate at full capacity. Hardware Power Distribution Direction Powered modules are connected to the right Backplane Bus Pass-through connection for data and control signals Status Indicator Green LED: power status Mechanical Dimensions (H × W × D) 4.74 × 2.85 × 2.31" (120.31 × 72.38 × 58.56mm) 4.74"120.31 3.18"80.82 18.390.72 21.130.83 2.31"58.5672.38 Inches Millimeters 0.01"0.40Inter-Connection Gap: 2.61"66.190.06"1.44 0.17"4.24 2.85" 5.20"132.00 Front BackProfile Shipping weight 0.75lbs (0.34kg) Mounting DIN rail or screw mounting Enclosure Material1 FR/ABS Enclosure Rating Plastic housing, UL94-V0 flammability rating Plenum rating per UL1995 1.All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive ECLYPSE™ Connected System Controller 9 / 20 Environmental Operating Temperature 32 to 122°F (0 to 50°C) Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing Ingress Protection Rating IP20 Nema Rating 1 Standards and Regulations CE: £Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments £Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments FCC This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) UL916 Energy management equipment Power Supply (ECY-PS100-240) Power Supply Input Voltage Range 100 to 240 VAC Universal; +10%/-15% Input Current 400mA typical Frequency Range 50 to 60Hz Standby Power consumption <0.5W Overcurrent Protection Field replaceable fuse Fuse Type 2.5A, Fast-acting, high-breaking, 250VAC, 5 × 20mm (TF2.5AH250V, IEC60127-2) Power Supply Output DC Voltage 18VDC regulated Rated Current Range 0 to 2A Rated Power 40W1 1.The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connected loads, must be less than this value. Hardware Power Distribution Direction Powered modules are connected to the right Backplane Bus Pass-through connection for data and control signals Status Indicator Green LED: power status 10 / 20 ECLYPSE™ Connected System Controller Mechanical Dimensions (H × W × D) 4.74 × 4.08 × 2.31" (120.31 × 103.65 × 58.56mm) 3.18"80.82 18.390.72 21.130.83 2.31"58.56 0.06"1.44 BackProfile 103.654.08" 5.24 133.03 4.74"120.31 0.44"11.13 3.83"97.33Front 0.01"0.40Inter-Connection Gap: Inches Millimeters Shipping weight 0.71lbs (0.32kg) Mounting DIN rail or screw mounting Refer to Hardware Installation Guide for more information Enclosure Material1 FR/ABS Enclosure Rating Plastic housing, UL94-5VB flammability rating 1.All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive Environmental Operating Temperature 32 to 122°F (0 to 50°C) Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing Altitude <6562ft (2000m) Pollution Degree 2 Ingress Protection Rating IP20 (must be mounted in a protective enclosure to conform with electrical installation standards) Overvoltage Category II - 2.5 kV Electrical Protection DC output is Separated Extra-Low Voltage (SELV); SELV is implemented through reinforced insulation Standards and Regulations CE: £Electrical Safety EN 60730-1 : 2011 - Automatic electrical controls for household and similar use - Part 1: General requirements £Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments £Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments UL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment For Measurement, Control, And Laboratory Use - Part 1: ECLYPSE™ Connected System Controller 11 / 20 General Requirements - Edition 2 - Revision Date 2008/10/28 FCC This device complies with FCC rules part 15, subpart B, class B Control, Automation and Connectivity Server (ECY-S1000) Power Supply Input Voltage 18VDC Power Consumption 8.9W; external loads excluded Communications Ethernet Connection Speed 10/100 Mbps £Addressing IPv4 or Hostname BACnet Profile BACnet Building Controller (B-BC)), AMEV AS-A and AS-B (pending) BACnet Listing BTL, WSP B-BC BACnet Interconnectivity BBMD forwarding capabilities BACnet/IP to BACnet MS/TP routing BACnet Transport Layer IP & MS/TP (optional) Web Server Protocol HTML5 Web Server Application Interface REST API Supported BACnet MS/TP and Modbus RTU and TCP Connectivity: £BACnet MS/TP or Modbus RTU 1 × RS-485 serial communications ports Each RS-485 port supports one communication protocol at a time £RS-485 Wiring 1-pair + Common/shield £RS-485 EOL Resistor Built-in £RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps £RS-485 Addressing Controller’s Web Configuration Interface £Modbus TCP Devices must be on the same subnet Supported Wireless Connectivity: £Wireless Adapter Optional, USB Port Connection £Wi-Fi Communication Protocol IEEE 802.11b/g/n and 802.11s £Wi-Fi Network Types Client, Access Point, Hotspot Supported Smart Room Control Components1: Maximum number of supported devices per controller combined 12 £Allure EC-Smart-Vue Series Up to 121 £Allure EC-Smart-Comfort Series Up to 6 £Allure EC-Smart-Air Series Up to 61 £EC-Multi Sensor Up to 42 £ECx-Light-4 / ECx-Light-4D / ECx-Light-DALI Up to 22 £ECx-Blind-4 / ECx-Blind-4LV Up to 22 1.For more details about supported quantities, see the ECLYPSE Selection Tool.xlsm spreadsheet file available for download from SmartSource. 2.A controller can support a maximum of 2 Allure sensor models equipped with a CO2 sensor. Any remaining connected sensors must be without a CO2 sensor. Hardware Processor Sitara ARM processor CPU Speed 1GHz 12 / 20 ECLYPSE™ Connected System Controller Memory 4GB Non-volatile Flash (applications & storage) 512MB RAM Real Time Clock (RTC) Real Time Clock with rechargeable battery Supports SNTP network time synchronization RTC Battery 20 hours charge time, 20 days discharge time Up to 500 charge / discharge cycles Cryptographic Module FIPS 140-2 Level 1 Compliant Communications Ports: £Ethernet 2 switched RJ-45 Ethernet ports Supported Protocols BACnet/IP, Modbus TCP, NTP, and REST £USB Connections 2 × USB 2.0 Ports 1 × Micro-USB 2.0 Ports £RS-485 Serial Communications Screw terminals Supported Protocols BACnet MS/TP or Modbus RTU £Subnet RJ-45 Status Indicators Green LED: Power status, Subnet TX, RS-485 TX, and Ethernet Traffic Orange LED: Controller status, Subnet RX, RS-485 RX, and Ethernet Speed Mechanical Dimensions (H × W × D) 4.74 × 3.57 × 2.31" (120.31 × 90.67 × 58.56mm) 3.18"80.82 18.540.73 21.080.83 3.33"84.47 0.4"1.092.31"58.563.57"90.67 Inches Millimeters Inter-Connection Gap: 0.01"0.40 5.13"130.29 0.06"1.44 4.74"120.31 0.39"9.98 Front BackProfile Shipping weight 0.85lbs (0.39kg) Mounting DIN rail or screw mounting Enclosure Material FR/ABS Enclosure Rating1 Plastic housing, UL94-V0 flammability rating Plenum rating per UL1995 1.All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive Environmental Operating Temperature 32 to 122°F (0 to 50°C) Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing ECLYPSE™ Connected System Controller 13 / 20 Ingress Protection Rating IP20 Nema Rating 1 Standards and Regulations CE: £Emission EN61000-6-3: 2007+A1:2011; Generic standards for residential, commercial and light-industrial environments £Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments FCC This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) UL916 Energy management equipment I/O Modules Power Supply Input Voltage 18VDC Power Consumption Calculate power supply requirements with the ECLYPSE Selection Tool Hardware Status Indicator Green LEDs: inputs and outputs For ECY-8UI, ECY-16DI, ECY-6UO, ECY-6UO-HOA, ECY-4UI4UO, ECY-4UI4UO- HOA, ECY-8UI6UO, ECY-8UI6UO-HOA, ECY-8UI6DOT, & ECY-8UI6DOT-HOA Models: Mechanical Dimensions (H × W × D) 4.74 × 3.20 × 2.31" (120.31 × 81.17 × 58.56mm) 2.95"74.99 4.74"120.31 3.20"81.17 2.31"58.56 3.18"80.82 18.540.73 21.080.83 Inches Millimeters Inter-Connection Gap: 0.01"0.40 Front BackProfile0.06"1.44 4.80"121.75 Shipping weight 0.85lbs (0.39kg) Mounting DIN rail or screw mounting Hot-swappable Yes Enclosure Material FR/ABS Enclosure Rating1 Plastic housing, UL94-V0 flammability rating; Plenum rating per UL1995 14 / 20 ECLYPSE™ Connected System Controller 1.All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive Environmental Operating Temperature 32 to 122°F (0 to 50°C) Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing Ingress Protection Rating IP20 Nema Rating 1 Standards and Regulations CE: £Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments £Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments FCC This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) UL916 Energy management equipment I/O Modules - Universal Inputs (UI) General Input Type Universal; software configurable Current Input Option Selection DIP switch Input Resolution 16-bit analog to digital converter Power Supply Output 18VDC; 20mA maximum per 0 to 20 mA input Contact Type Dry contact Counter Type Dry contact Maximum Frequency 1Hz maximum, Minimum Duty Cycle 500milliseconds On / 500milliseconds Off 0 to 10VDC Range 0 to 10VDC (40kΩ input impedance) 0 to 5VDC Range 0 to 5VDC (high input impedance) 0 to 20mA Range 0 to 20mA 249Ω DIP-switch configurable internal resistor Resistance/Thermistor Range 0 to 350 KΩ ECLYPSE™ Connected System Controller 15 / 20 Supported Thermistor Types Any that operate in this range Pre-configured Temperature Sensor Types: £Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF; 25ºC) £Platinum Pt1000 (1KΩ @ 32ºF; 0ºC) £Nickel RTD Ni1000 (1KΩ @ 32ºF; 0ºC) RTD Ni1000 (1KΩ @ 69.8ºF; 21ºC) I/O Modules - Digital Inputs (DI) General Input Type Dry contact or Open-Collector Low Threshold < 2.5V High Threshold > 3.0V Pulse/Counter Pulse Input S0 output compatible Maximum Frequency 120Hz Minimum Duty Cycle 4.167milliseconds On / 4.167milliseconds Off I/O Modules - Universal Outputs (UO) General Output Type Universal; software configurable Output Resolution 10-bit digital to analog Converter Output Protection Built-in snubbing diode to protect against back-EMF, for example when used with a 12VDC relay Load Resistance Minimum 200Ω for 0 to 10VDC and 0 to 12VDC outputs Maximum 500Ω for 0 to 20mA output Auto-reset Fuse 60mA @ 140ºF; 60ºC 0 or 12VDC (On/Off) Range 0 or 12VDC PWM Range Adjustable period from 2 to 65seconds Floating Minimum Pulse On/Off Time 500milliseconds Drive Time Period Adjustable 0 to 10VDC Range 0 to 10VDC linear 0 to 20mA Range 0 to 20mA Current Source 20mA maximum per 0 to 20 mA output Ports UO1, UO2, and UO3 only DIP switch 16 / 20 ECLYPSE™ Connected System Controller HOA Hand-Off-Auto switch When equipped Supervision allows control logic to read the current HOA switch and potentiometer settings Threshold Configurable Potentiometer Voltage Range 0 to 12VDC I/O Modules - Digital Output (DOT) General Output Type 24VAC Triac; software configurable Maximum Current 0.5A continuous 1A @ 15% duty cycle for a 10 minute period Power Source External power supply 0 or 24VAC (On/Off) Range 0 or 24VAC PWM Range Adjustable period from 2 to 65seconds Floating Minimum Pulse On/Off Time 500milliseconds Drive Time Period Adjustable HOA Hand-Off-Auto switch When equipped Supervision allows control logic to read the current HOA switch setting I/O Modules - Digital Output (DOR) For ECY-8DOR & ECY-8DOR-HOA Models: General Output Type Relay contact Relay Type Form C Power Source Dry contact (external power supply) Operating Voltage 0 to 277VAC or 0-30VDC ±10%, see HIG for mounting specifications Maximum Current £Resistive Load 10A £Inductive Load 6A £Motor Load 3A Protection Outputs must be protected with max 10 A external circuit breaker Digital Range On/Off ECLYPSE™ Connected System Controller 17 / 20 HOA Hand-Off-Auto switch When equipped Supervision allows control logic to read the current HOA switch setting Mechanical Dimensions (H × W × D) 4.74 × 5.15 × 2.31" (120.31 × 130.07 × 58.56mm) 4.74"120.31 2.31"58.56 Front Profile O6O3O1O4 O7 O8O5O2 MAN AUTO OFF Inter-Connection Gap: 0.01"0.40 5.15"130.07 4.94"125.32 Back 3.18"80.82 18.540.73 21.080.83 Inches Millimeters0.06"1.44 4.8"121.75 Shipping weight 0.75lbs (0.34kg) Mounting DIN rail or screw mounting Hot-swappable Yes (once high voltages have been removed) Enclosure Material FR/ABS Enclosure Rating1 Plastic housing, UL94-5VB flammability rating 1.All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive Environmental Operating Temperature 32 to 122°F (0 to 50°C) Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing Altitude <6562ft (2000m) Pollution Degree 2 Ingress Protection Rating IP20 (must be mounted in a protective enclosure to conform with electrical installation standards) Overvoltage Category II - 2.5 kV Standards and Regulations CE: £Electrical Safety EN 60730-1 : 2011 - Automatic electrical controls for household and similar use - Part 1: General requirements £Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments £Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments UL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment For Measurement, Control, And Laboratory Use - Part 1: 18 / 20 ECLYPSE™ Connected System Controller General Requirements - Edition 2 - Revision Date 2008/10/28 FCC This device complies with FCC rules part 15, subpart B, class B Communications Module ECY-RS485 Communications Module Supported Quantity 1 × ECY-RS485 per ECY-S1000 Power Supply Input Voltage 18VDC Power Consumption 1.5 W Communications Supported BACnet MS/TP or Modbus RTU Connectivity: £BACnet MS/TP or Modbus RTU 2 × RS-485 serial communications ports Each RS-485 port supports one communication protocol at a time £RS-485 Wiring 1-pair + Common/shield £Connection Type Screw terminals £RS-485 EOL Resistor Built-in £RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps £RS-485 Addressing Controller’s Web Configuration Interface Status Indicators Green LED: TX Orange LED: RX Mechanical Dimensions (H × W × D) 4.74 × 3.16 × 2.31" (120.31 × 80.19 × 58.56mm) 2.95 [74.99] 4.74 [120.31] 3.20 [81.17]2.31 [58.56] 3.18 [80.82] 0.73 [18.54] 0.83 [21.08] Inter-Connection Gap: 0.01 [0.40] Front BackProfile0.06 [1.44] 5.30 [134.65] Inches [Millimeters] 0.51 [12.90] RX2 TX2RX1TX1 Shipping weight 0.55lbs (0.25 kg) Mounting DIN rail or screw mounting Enclosure Material FR/ABS Enclosure Rating1 Plastic housing, UL94-V0 flammability rating ECLYPSE™ Connected System Controller 19 / 20 Plenum rating per UL1995 1.All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive Environmental Operating Temperature 32 to 122°F (0 to 50°C) Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing Ingress Protection Rating IP20 Nema Rating 1 Standards and Regulations CE: £Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments £Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments FCC This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) UL916 Energy management equipment Applications ⎕HVAC ⎕Clean rooms ⎕Museums / Archives ⎕Hospitals and Pharmaceuticals Features & Benefits ⎕Economical ⎕Ease of installation ⎕Highly stable humidity sensor ⎕Proven long stability and performance ⎕Field selectable analog signals Overview The HS-O Series are relative humidity trans-mitters for outside air. They use a highly accu- rate and reliable Thermoset Polymer based ca-pacitance humidity sensor and state-of-theart digital linearization and temperature compen-sated circuitry to monitor humidity levels. A 60 micron HDPE filter protects the sensor from contaminants. Excellent long term stability and quick response time combined with temperature compensation make the HS-O Series the ide- al choice for the HVAC market. All models are available with RH accuracies of 2%, 3% or 5%. Datasheet HS-O Series Outside Air Humidity Transmitters Accessories HS-FCAL Factory Calibration Certificate HS-NIST NIST Calibration Certificate Note: Calibration certificates must be purchased at the time of purchasing the relative sensors. HS-O Series2/4 Model Selection HS-O2PSX 2% accuracy outside air relative humidity transmitter, 24 Vac/dc and jumper selectable outputs HS-O2PST 2% accuracy outside air relative humidity transmitter, 24 Vac/dc and jumper selectable outputs, 10kΩ, type 2, NTC thermistor. HS-O3PSX 3% accuracy outside air relative humidity transmitter, 24 Vac/dc and jumper selectable outputs HS-O3PST 3% accuracy outside air relative humidity transmitter, 24 Vac/dc and jumper selectable outputs, 10kΩ, type 2, NTC thermistor. HS-O5PSX 5% accuracy outside air relative humidity transmitter, 24 Vac/dc and jumper selectable outputs HS-O5PST 5% accuracy outside air relative humidity transmitter, 24 Vac/dc and jumper selectable outputs, 10kΩ, type 2, NTC thermistor. 3/4HS-O Series Product Specifications Environmental Operating temperature: ——————————————————————————————-40 °C to 85 °C (-40 °F to 185 °F) Storage temperature: ————————————————————————————————-40 °C to 85 °C (-40 °F to 185 °F) Ambient humidity: ————————————————————————————————————————0 to 95% Non-condensing Humidity Sensor/Probe Sensor Type: ———————————————————————————————————Thermoset Polymer based Capacitive Sensor Accuracy: ———————————————————————————————————±2, 3, or 5% RH (5% to 95% RH) Output Signal ——————————————————————————————4-20 mA current loop, 0-5 Vdc, or 0-10 Vdc Range —————————————————————————————————————————————————————————0 to 100%RH Response Time ———————————————————————————————————————————————15 seconds typical Temperature Dependence ——————————————————————————————————————————±0.05% RH/ °C Hysteresis —————————————————————————————————————————————————±1.5% RH maximum Repeatability ——————————————————————————————————————————————————±0.5% RH typical Linearity —————————————————————————————————————————————————————±0.5% RH typical Enclosure Material ——————————————————————————————————Grey ABS; Type: UL94-5VB IP65(NEMA 4X) Shipping Weight ————————————————————————————————————————————————0.70 lbs (0.32 kg) Temperature Sensor Option Type1: ———————————————————————————————————————————10,000Ω, Type 2, NTC Thermistor Accuracy —————————————————————————————————————————————————————————————±0.2 C Electrical Dissipation Factor: ——————————————————————————————————————————2.2 mW/K (Thermistor)Max Power @ 25°C (77°F): —————————————————————————————————————75 mW (Thermistor)Thermal Time Constant: ———————————————————————————————————Less than 10 s (Thermistor)Power Supply ———————————————————————————————————————————18 to 30 Vdc, 15 to 26 VacConsumption ———————————————————————————————————————————————————22 mA Maximum Output Drive at 24 Vdc ——————————————————————————————————550 Ω Max for Current Output10 kΩ Min for Voltage OutputInternal Adjustments —————————————————————————————Clearly marked ZERO and SPAN potsProtection Circuitry —————————————————————————Reverse voltage protected and output limitedInput Voltage Effect ————————————————————————————Negligible over specified operating rangeTermination —————————————————————————————————————Screw terminal block (14 20 22 AWG) Agency Approval Material2 ———————————————————————————————————————————————————————————UL94-VB 1. Temperature sensor type stated is standard. Other temperature sensor types are available. 2. All materials and manufacturing processes comply with the RoHS directive 05DI-DSHSOSX-124/4 Specifications subject to change without notice. Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. All other trademarks are property of their respective owner. ©, Distech Controls Inc., 2015 to 2016. All rights reserved. 4/4 Dimensions Overview Enclosed, self-powered, split core current sen-sors (voltage and current output) and switches (fixed and adjustable trip points). Refer to CS-RIBA Series track mount relays to combine with “Snap-On” model relays. Features & Benefits ⎕Pre Packaged for Convenience ⎕Adjustable or Fixed Thresholds ⎕Split Core Models ⎕Miniature Size Datasheet Applications ⎕General Load Status ⎕Motor Status Model Selection Product Number Sensor Output Switching Voltage Range Maximum Switching Current Sensor Contact Termination Range Type Threshold LED 1 LED 2 CS-RIBXGF SS Switch SPST 30 Vac/dc .4 Amps Wire Leads .35-150A Split Fixed, .35Amp CS-RIBXGFL SS Switch SPST 30 Vac/dc .4 Amps Wire Leads .75-150A Split Fixed, .75Amp Over Trip Point CS-RIBXGTF SS Switch SPST 30 Vac/dc .4 Amps Terminals .35-150A Split Fixed, .35Amp CS-RIBXGTFL SS Switch SPST 30 Vac/dc .4 Amps Terminals .75-150A Split Fixed, .75Amp Over Trip Point CS-RIBXGA SS Switch SPST 30 Vac/dc .4 Amps Wire Leads .75-150A Split Adjustable Over Trip Point Under Trip Point CS-RIBXGTA SS Switch SPST 30 Vac/dc .4 Amps Terminals .75-150A Split Adjustable Over Trip Point Under Trip Point CS-RIBXGA-SCAL SS Switch SPST 30 Vac/dc .4 Amps Wire Leads 3-150A Split Adjustable See -SCAL LED Table Below CS-RIBXGTA-SCAL SS Switch SPST 30 Vac/dc .4 Amps Terminals 3-150A Split Adjustable See -SCAL LED Table Below CS-RIBXG Series Solid Core AC Transducers 2/2 CS-RIBXG Series_DS_11_EN Specifications subject to change without notice. Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. All other trademarks are property of their respective owner. ©, Distech Controls Inc., 2015. All rights reserved. Specifications Operating Temperature ————————————————————————————————————————————— -30 to 140° F Humidity Range ——————————————————————————————————————————5 to 95% (noncondensing) Max Sense Voltage ————————————————————————————————————————————————————600 Vac Sensor Output: ⎕ Current below threshold ————————————————————————————————————————————————Open ⎕ Current above threshold ———————————————————————————————————————————————Closed ⎕ Contact Type ————————————————————————————————————————————————————Solid State ⎕ Contact Rating —————————————————————————————————————————30 Vac/dc, .4 Amp Max. ⎕ When current sensor status is off (open), leakage ———————————————————<30 uA @ 30Vac/dc ⎕ When current sensor status is on (closed), voltage drop: ———————————< 0.3 Vac/dc @ .01 Amp < 1.6 Vac/dc @ 0.4 Amp Approvals ———————————UL Listed, UL916, UL864, C-UL, California State Fire Marshal, CE, RoHS Mounting/Installation ————————————————————————————————Removable mounting tab provided The wire clamp locks against the load wire, securing the unit in place -SCAL LED Table Self-Calibrating AC Sensors (Models with -SCAL Suffix): The SCAL unit begins the 30 second self-calibration process the first time current is applied in the operating range. The threshold is permanently set. Subsequent calibrations may be performed by moving SW1 to the position opposite of its current position with or without current applied (hands can be safely away from live voltage). Once current begins flowing, or if it already is, the calibration pro-cess will begin. At the end of the 30 seconds, amperage will be read and set as the threshold. SW2 in the ON position provides a 15% (+/-3%) differential, in the OFF position it provides a 25% (+/-3%) dif-ferential. SW2 can be selected at anytime and does not affect the threshold setting. Current in-range closes the status contacts. Current above or below range opens the status contacts. For example, with a current of 10 amps set as the threshold and a 15% differential, status contacts will be closed between 8.5 amps and 11.5 amps and open outside of this range. A small amount of hysteresis is provided to prevent dithering near the differential limits. Status Description LED Off No Current Two Winks Current Below Range Three Winks Current In Range Four Winks Current Above Range Continuous Winks Calibration in Progress Dimensions Overview Enclosed Single, double and triple power sup-plies Features & Benefits ⎕5 or 3 isolated 100 VA outputs ⎕On/Off circuit breaker switch for each output ⎕UL Listed Class 3 ⎕Fully enclosed – perfect for central location Datasheet Applications ⎕Power Control PW-PSH (40/75/100 VA AC Power Supply) Series AC Power Supply Model Selection Model # Trans- former Input Power UL 120 Vac Outlets Aux Out- put Wire Main Breaker on Input Power Secondary Configuration Weight PW-PSH40A 40 VA 120 Vac • 1 1 External Terminal Strip 4.00 lbs. PW-PSH40AN 40 VA 120 Vac • 1 External Terminal Strip 4.00 lbs. PW-PSH40ANW 40 VA 120 Vac • 1 Internal Wires 4.00 lbs. PW-PSH40AW 40 VA 120 Vac • 1 1 Internal Wires 4.00 lbs. PW-PSH40AB10 40 VA 120 Vac • 1 1 1 10 Amp Switch / Breaker External Terminal Strip 4.00 lbs. PW-PSH40ANB10 40 VA 120 Vac • 1 1 10 Amp Switch / Breaker External Terminal Strip 4.00 lbs. PW-PSH40ANWB10 40 VA 120 Vac • 1 1 10 Amp Switch / Breaker Internal Wires 4.00 lbs. PW-PSH40AWB10 40 VA 120 Vac • 1 1 1 10 Amp Switch / Breaker Internal Wires 4.00 lbs. PW-PSH75A 75 VA Multi- Tap • 2 1 External Terminal Strip 4.50 lbs. PW-PSH75AN 75 VA Multi- Tap • 2 External Terminal Strip 4.50 lbs. PW-PSH75ANW 75 VA Multi- Tap • 2 Internal Wires 4.50 lbs. PW-PSH75AW 75 VA Multi- Tap • 2 1 Internal Wires 4.50 lbs. PW-PSH75AB10 75 VA Multi- Tap • 2 1 1 10 Amp Switch / Breaker External Terminal Strip 4.50 lbs. PW-PSH75ANB10 75 VA Multi- Tap • 2 1 10 Amp Switch / Breaker External Terminal Strip 4.50 lbs. PW-PSH75ANWB10 75 VA Multi- Tap • 2 1 10 Amp Switch / Breaker Internal Wires 4.50 lbs. PW-PSH75AWB10 75 VA Multi- Tap • 2 1 1 10 Amp Switch / Breaker Internal Wires 4.50 lbs. PW-PSH100A 100 VA 120 Vac • 2 1 External Terminal Strip 4.60 lbs. PW-PSH100AN 100 VA 120 Vac • 2 External Terminal Strip 4.60 lbs. PW-PSH100ANW 100 VA 120 Vac • 2 Internal Wires 4.60 lbs. PWPSH100AW 100 VA 120 Vac • 2 1 Internal Wires 4.60 lbs. PW-PSH100AB10 100 VA 120 Vac • 2 1 1 10 Amp Switch / Breaker External Terminal Strip 4.60 lbs PW-PSH (40/75/100 VA AC Power Supply) Series2/4 3/4PW-PSH (40/75/100 VA AC Power Supply) Series Product Specifications Number of Transformers ———————————————————————————————————————————————————One Transformer Type ——————————————————————————————————————————————————Split-Bobbin Over Current Protection ————————————————————————————————————————————Circuit Breaker Frequency ——————————————————————————————————————————————————————————50/60 Hz 24 Vac ON/OFF ——————————————————————————————————————————On / Off Switch & Breaker Main Breaker ON/OFF: ⎕ ——————————————————————————Switch / Breaker (10 Amp) available according to Parts table ⎕ —————————————————————————Kills power to entire unit: Outlets, Aux. Output, & Transformer ⎕ Total Combined Output ———————————————————————————————————————————————————9A Switched Outlets** ———————————Main Breaker ON/OFF switches outlets ON/OFF (factory default) ———————————————————An internal jumper setting can make the outlets hot - see diagrams below Dimensions —————————————————————————————————————————H 4.500˝ x W 5.438˝ x D 4.500˝ PW-PSH40A Series Model # Trans-former Input Power UL 120 Vac Outlets Aux Out-put Wire Main Breaker on Input Power Secondary Configuration Weight PW-PSH100ANB10 100 VA 120 Vac • 2 1 10 Amp Switch / Breaker External Terminal Strip 4.60 lbs PW-PSH100ANWB10 100 VA 120 Vac • 2 1 10 Amp Switch / Breaker Internal Wires 4.60 lbs PW-PSH100AWB10 100 VA 120 Vac • 2 1 1 10 Amp Switch / Breaker Internal Wires 4.60 lbs 4/4 PW-PSH-40-75-100 Series_DS_11_EN Specifications subject to change without notice. Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. All other trademarks are property of their respective owner. ©, Distech Controls Inc., 2015. All rights reserved. PW-PSH75A Series PW-PSH100A Series Overview Kit Consisting of Enclosed Power Control Center Model PW-PSH2RB10 (10 Amp Switch / Circuit Breaker, Two (2) 120 VAC Outlets, Terminals, 120 VAC Input) with a 600 VA UPS. (No Status Contacts) Features & Benefits ⎕Pre Packaged for Convenience ⎕UL Class 2 C-UL CE RoHS ⎕UPS Included ⎕UPS Interface Board ⎕Made in USA ⎕Back up time: 2.5 min. Datasheet Applications ⎕UPS Interface ⎕Hardwire line voltage to UPS while hardwir-ing the UPS to final load PW-PSH600-UPS Uninterruptible Power Supply Kit (No Status Contact) 2/2 PW-PSH600-UPS_DS_10_EN Specifications subject to change without notice. Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. All other trademarks are property of their respective owner. ©, Distech Controls Inc., 2015. All rights reserved. Product Specifications Shipping Weight —————————————————————————————————————————————————————— 22.3 lbs. Product Weight ——————————————————————————————————————————————————————— 17.3 lbs. UPS UPS ———————————————————————————————————————————————————————————————— 600VA Backup Time ——————————————————————————————————————————2.5 Min. @ Full 600 VA Load 10.2 Min. @ 1/2 Load Input ———————————————————————————————————————————————————————— 120 Vac, 12 Amp Output ——————————————————————————————————————————————————————120 Vac, 4.6 Amp Frequency —————————————————————————————————————————————————————————— 50/60 Hz Temperature Rating of UPS ——————————————————————————————————————————— 32 to 104° F UPS Transfer Time ——————————————————————————————————————————————————————— 6ms Approvals ————————————————————————————————————————————————————UL Listed, UL1778 Weight ——————————————————————————————————————————————————————————————8.4lbs. PW-PSH2RB10 Operating Temperature ——————————————————————————————————————————————-30 to 140° F Humidity Range ——————————————————————————————————————————5 to 95% (noncondensing) Main Breaker ON/OFF —————————————————————————————————————Switch / Breaker (10 Amp) Approvals ———————————————————————————————————————UL Listed, UL916, C-UL, CE, RoHS Dimensions ————————————————————12.000˝ x 14.000˝ x 6.000˝Metal Housing with Screw Cover On/Of Switch, Breaker & Indicator Light Computer OutletTo UPS UPS Output HotNeut.GNDLine Input GNDHotNeut.RESET OFF UPS To Protected Device From UPS To UPS 120 Vac Line Input }} Overview Enclosed 10 Amp Relay with 24 VAC/DC Coil Datasheet RE-RIB (Enclosed Pilot Relay) Series Enclosed Pilot Relays 2/4 RE-RIB (Enclosed Pilot Relay) Series Model Selection Model #UL1 Coil Voltage Coil Current Relays Contacts Dimensions Nipple Override Switch Gold FlashAC/DC AC Form Rating NO / NC RE-RIBU1C •10-302 120 Type 1 1 SPDT Type 1 NO 1.70˝ x 2.80˝ x 1.50˝.50˝ NPT • RE-RIBH1C •10-302 208-277 Type 1 1 SPDT Type 1 NO 1.70˝ x 2.80˝ x 1.50˝.50˝ NPT • RE-RIBL1C-DC •10-304 Type 3 1 SPDT Type 1 NO 1.70˝ x 2.80˝ x 1.50˝.50˝ NPT • RE-RIB2421C •245 120-277 Type 4 1 SPDT Type 5 NO 1.70˝ x 2.80˝ x 1.50˝.50˝ NPT RE-RIBU2C •10-302 120 Type 1 2 2 SPDT Type 1 NO 2.30˝ x 3.20˝ x 1.80˝.75˝ NPT • RE-RIBH2C •10-302 208-277 Type 1 2 2 SPDT Type 1 NO 2.30˝ x 3.20˝ x 1.80˝.75˝ NPT • RE-RIBL3C •10-302 Type 1 3 3 SPST Type 1 NO 4.00˝ x 4.00˝ x 1.80˝ .50˝ NPT • RE-RIBL3C-NC •10-302 Type 1 3 3 SPST Type 1 NC 4.00˝ x 4.00˝ x 1.80˝ .50˝ NPT • RE-RIBL4C •10-302 Type 1 4 3 SPST, 1 SPDT Type 1 NO 4.00˝ x 4.00˝ x 1.80˝ .50˝ NPT • RE-RIBL4C-NC •10-302 Type 1 4 3 SPST, 1 SPDT Type 1 NC 4.00˝ x 4.00˝ x 1.80˝ .50˝ NPT • RE-RIBU1S •10-302 120 Type 1 1 SPST Type 2 NO 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 1 • RE-RIBU1S-NC •10-302 120 Type 1 1 SPST Type 2 NC 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 1 • RE-RIBH1S •10-302 208-277 Type 1 1 SPST Type 2 NO 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 1 • RE-RIBH1S-NC •10-302 208-277 Type 1 1 SPST Type 2 NC 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 1 • RE-RIBU1SM-250 •10-302 120 Type 2 1 SPST Type 3 NO 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 1+monitor6 • RE-RIBU1SM-250 -NC •10-302 120 Type 2 1 SPST Type 3 NC 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 1+monitor6 • RE-RIBH1SM-250 •10-302 208-277 Type 2 1 SPST Type 3 NO 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 1+monitor6 • RE-RIBH1SM-250-NC •10-302 208-277 Type 2 1 SPST Type 3 NC 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 1+monitor6 • RE-RIBU2SC •10-302 120 Type 1 2 1 SPST, 1 SPDT Type 2 NO 2.30˝ x 3.20˝ x 1.80˝.75˝ NPT 1 • RE-RIBU2SC-NC •10-302 120 Type 1 2 1 SPST, 1 SPDT Type 2 NC 2.30˝ x 3.20˝ x 1.80˝.75˝ NPT 1 • RE-RIBU2S2 •10-302 120 Type 1 2 2 SPST Type 2 NO 4.00˝ x 4.00˝ x 1.80˝ .50˝ NPT 2 • RE-RIBU2S2-NC •10-302 120 Type 1 2 2 SPST Type 2 NC 4.00˝ x 4.00˝ x 1.80˝ .50˝ NPT 2 • RE-RIB2401D •243 120 Type 5 1 DPDT Type 4 NO 1.70˝ x 2.80˝ x 1.50˝.50˝ NPT RE-RIB2402D •243 208-277 Type 5 1 DPDT Type 4 NO 1.70˝ x 2.80˝ x 1.50˝.50˝ NPT RE-RIBU1SC •10-302 120 Type 1 1 SPDT Type 2 NO 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 27 • RE-RIBH1SC •10-302 208-277 Type 1 1 SPDT Type 2 NO 2.30˝ x 3.20˝ x 1.80˝.50˝ NPT 27 • 1. UL Listed : UL916 Energy Management, UL864 Fire ; USA & Canada 2. Coil Drop Out Voltage = 2.1 Vac / 2.8 Vdc, Coil Pull In Voltage = 9 Vac / 10 Vdc 3. Coil Drop Out Voltage = 3 Vac / 3.8 Vdc, Coil Pull In Voltage = 18 Vac / 20 Vdc 4. DC Only, Coil Drop Out Voltage = 2.8 Vdc, Coil Pull In Voltage = 10 Vdc 5. Coil Drop Out Voltage = 3 Vac / 3.8 Vdc, Coil Pull In Voltage = 20 Vac / 20 Vdc 6. Second pole of override switch can be connected to digital-in of controller to report position of override switch. Rating of second pole is 250 Vac max and 5 Amp max. 7. SPDT with override requires 2 switches 3/4RE-RIB (Enclosed Pilot Relay) Series Product Specifications Relay Coil —————————————————————————————————————————————————Continuous Duty Coil Expected Relay Life ——————————————————————————————10 million cycles minimum mechanical Operating Temperature ————————————————————————————————————————————— -30 to 140° F Humidity Range ——————————————————————————————————————————5 to 95% (noncondensing) Relay Status —————————————————————————————————————————————————LED On = Activated Wires ————————————————————————————————————————————————————————16˝, 600V Rated Approvals ———————————UL Listed, UL916, UL864, C-UL, California State Fire Marshal, CE, RoHS Housing Rating ———————————————————————————————UL Accepted for Use in Plenum, NEMA 1 AC Coil Frequency —————————————————————————————————————————————————————50/60Hz Operate Time: ⎕All Models ——————————————————————————————————————————————————————————20ms ⎕Except RE-RIB2401D & RE-RIB2402D ——————————————————————————————————————8ms Coil Current Type 1 Relay Coil(s): ⎕ ——————————————————————————————————————————————————————————33 mA @ 10 Vac ⎕ ——————————————————————————————————————————————————————————13 mA @ 10 Vdc ⎕ ——————————————————————————————————————————————————————————35 mA @ 12 Vac ⎕ ——————————————————————————————————————————————————————————15 mA @ 12 Vdc ⎕ ——————————————————————————————————————————————————————————46 mA @ 24 Vac ⎕ ——————————————————————————————————————————————————————————18 mA @ 24 Vdc ⎕ ——————————————————————————————————————————————————————————55 mA @ 30 Vac ⎕ ——————————————————————————————————————————————————————————20 mA @ 30 Vdc ⎕For Models with a 120 Vac Coil ——————————————————————————————————28 mA @ 120 Vac ⎕For Models with a 208-277 Vac Coil———————————————————————————39 mA @ 208-277 Vac Type 2 Relay Coil(s): ⎕ ——————————————————————————————————————————————————————————55 mA @ 30 Vac ⎕ ——————————————————————————————————————————————————————————20 mA @ 30 Vdc ⎕For Models with a 120 Vac Coil ——————————————————————————————————28 mA @ 120 Vac ⎕For Models with a 208-277 Vac Coil———————————————————————————39 mA @ 208-277 Vac Type 3 Relay Coil(s): ⎕ ——————————————————————————————————————————————————————————13 mA @ 10 Vdc ⎕ ——————————————————————————————————————————————————————————15 mA @ 12 Vdc ⎕ ——————————————————————————————————————————————————————————18 mA @ 24 Vdc ⎕ ——————————————————————————————————————————————————————————20 mA @ 30 Vdc Type 4 Relay Coil(s): ⎕ ——————————————————————————————————————————————————————————66 mA @ 24 Vac ⎕ ——————————————————————————————————————————————————————————38 mA @ 24 Vdc ⎕ —————————————————————————————————————————————————————40 mA @ 120-277 Vac Type 5 Relay Coil(s): ⎕ ——————————————————————————————————————————————————————————24 mA @ 18 Vac ⎕ ——————————————————————————————————————————————————————————20 mA @ 20 Vdc ⎕ ——————————————————————————————————————————————————————————32 mA @ 24 Vac ⎕ ——————————————————————————————————————————————————————————24 mA @ 24 Vdc ⎕ ——————————————————————————————————————————————————————————40 mA @ 30 Vac ⎕ ——————————————————————————————————————————————————————————36 mA @ 30 Vdc ⎕For Models with a 120 Vac Coil ——————————————————————————————————31 mA @ 120 Vac ⎕For Models with a 208-277 Vac Coil———————————————————————————36 mA @ 208-277 Vac 4/4 RE-RIB Enclosed Pilot Series_DS_10_EN Specifications subject to change without notice. ECLYPSE, Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. All other trademarks are property of their respective owner. ©, Distech Controls Inc., 2014. All rights reserved. Contact Ratings Type 1 Contact(s): ⎕ —————————————————————————————————————————————————10 Amp Resistive @ 277 Vac ⎕ ——————————————————————————————————————————————————10 Amp Resistive @ 28 Vdc ⎕ —————————————————————————————————————————————480 VA Pilot Duty @ 240-277 Vac ⎕ ——————————————————————————————————————————————————480 VA Ballast1 @ 277 Vac ⎕ ———————————————————————————————————————————600 Watt Tungsten @ 120 Vac (N/O) ⎕ ———————————————————————————————————————————240 Watt Tungsten @ 120 Vac (N/C) ⎕ —————————————————————————————————————————————————1/3 HP @ 120-240 Vac (N/O) ⎕ —————————————————————————————————————————————————1/6 HP @ 120-240 Vac (N/C) ⎕ ————————————————————————————————————————————————————1/4 HP @ 277 Vac (N/O) ⎕ ————————————————————————————————————————————————————1/8 HP @ 277 Vac (N/C) Type 2 Contact(s): ⎕ —————————————————————————————————————————————————10 Amp Resistive @ 277 Vac ⎕ ————————————————————————————————————————————————480 VA Pilot Duty @ 277 Vac ⎕ ——————————————————————————————————————————————————480 VA Ballast1 @ 277 Vac ⎕ ———————————————————————————————————————————600 Watt Tungsten @ 120 Vac (N/O) ⎕ ———————————————————————————————————————————240 Watt Tungsten @ 120 Vac (N/C) ⎕ —————————————————————————————————————————————————1/3 HP @ 120-240 Vac (N/O) ⎕ —————————————————————————————————————————————————1/6 HP @ 120-240 Vac (N/C) ⎕ ————————————————————————————————————————————————————1/4 HP @ 277 Vac (N/O) ⎕ ————————————————————————————————————————————————————1/8 HP @ 277 Vac (N/C) Type 3 Contact(s): ⎕ —————————————————————————————————————————————10 Amp Resistive @ 120/250 Vac ⎕ —————————————————————————————————————————————345 VA Pilot Duty @ 120/240 Vac ⎕ ——————————————————————————————————————————————211 VA Pilot Duty @ 120/240 Vac ⎕ —————————————————————————————————————————————————1/3 HP @ 120-240 Vac (N/O) ⎕ —————————————————————————————————————————————————1/6 HP @ 120-240 Vac (N/C) Type 4 Contact(s): ⎕ ——————————————————————————————————————————————————10 Amp Resistive @ 30 Vdc ⎕ ——————————————————————————————————————————————10 Amp General Use @ 277 Vac ⎕ —————————————————————————————————————————————————1/2 HP @ 120/240 Vac (N/O) ⎕ —————————————————————————————————————————————————1/3 HP @ 120/240 Vac (N/C) ⎕B300 Pilot Duty ——————————————————————————————120 Vac 30A Make 3A Break (360 VA) ⎕B300 Pilot Duty ————————————————————————————240 Vac 15 A Make 1.5A Break (360 VA) ⎕B300 Pilot Duty ———————————————————————————208 Vac 17.3A Make 1.73A Break (360 VA) ⎕B300 Pilot Duty —————————————————————————————277 Vac 13A Make 1.3A Break (360 VA) ⎕B300 Pilot Duty —————————————————————————24 Vac 30A Make 5A Break (120VA) 5A Max Type 5 Contact(s): ⎕ ——————————————————————————————————————————————10 Amp General Use @ 277 Vac ⎕ —————————————————————————————————————————————10 Amp Resistive @ 30 Vdc (N/O) ⎕ ——————————————————————————————————————————————7 Amp Resistive @ 30 Vdc (N/C) ⎕ —————————————————————————————————————————————————————————1/2 HP @ 125 Vac ⎕ ——————————————————————————————————————————————————————————1 HP @ 250 Vac ⎕ —————————————————————————————————————————————————————————1/4 HP @ 277 Vac ⎕ ———————————————————————————————————————————————————————————C300 Pilot Duty 1. Not rated for Electronic Ballast Applications ⎕Used for measuring temperature on: supply and return ducts, supply and return hot water pipes of heating systems, domestic hot water tanks and piping, and supply and return lines in chillers ⎕Incorporated in chillers to monitor tempera-ture gradients ⎕Used in heat exchangers and air handling units to provide temperature sensing for con- trol of heating / cooling coils Features & Benefits ⎕Economical ⎕Ease of installation ⎕Sensors are hermetically sealed ⎕Proven long stability and performance ⎕Probes made of corrosion-resistant 304 stainless steel ⎕Accurate temperature monitoring for in-creased comfort Overview TS-D2X Series all-purpose temperature sen-sors provide precision temperature sensing for ducts. When combined with a TS-TW series S/S thermowell, they can be used to measure liquid temperature in pipes. The TS-D2X single-point temperature sensor uses a precision sensor en-capsulated in a 6.00 mm (0.236”) OD, a 304-se-ries stainless steel probe, and it is available in various lengths. All probes provide excellent heat transfer, fast response and resistance to mois-ture penetration. Datasheet TS-D2X Sensor Series Duct & Immersion Temperature Sensors, Nema 4X 2/4 TS-D2X Sensor Series Model Selection Accessories Thermal Joint Compound TS-JC2 Thermal Joint Compound, 2 oz (60ml) Jar TS-JC5 Thermal Joint Compound, 5 oz (150ml) Tube TS-JC8 Thermal Joint Compound, 8 oz Jar (240ml) Thermowells TS-TWN30402 50mm (2”) 304 SS well, NPT TS-TWN30404 100mm (4”) 304 SS well, NPT TS-TWN30406 150mm (6”) 304 SS well, NPT TS-TWN30408 200mm (8”) 304 SS well, NPT TS-TWN31602 50mm (2”) 316 SS well, NPT TS-TWN31604 100mm (4”) 316 SS well, NPT TS-TWN31606 150mm (6”) 316 SS well, NPT TS-TWN31608 200mm (8”) 316 SS well, NPT TS-D XX 002 Mounting Style D = Duct / Immesion Enclosure XX = No enclosure2X = Plastic enclosure, Nema 4X Probe Length 002 = 2" (50mm)004 = 4" (100mm)006 = 6" (150mm)008 = 8" (200mm)012 = 12" (300mm)018 = 18" (450mm) 3/4TS-D2X Sensor Series Product Specifications Environmental Operating Temperature ————————————————————————————————— -20ºC to 105ºC; -4ºF to 221ºF Storage Temperature ——————————————————————————————————-20ºC to 105ºC; -4ºF to 221ºF Relative Humidity ————————————————————————————————————————0 to 95% Non-condensing Bracket Material ——————————————————————————————————————————————————————ABS - UL94-5VB Color ————————————————————————————————————————————————————————————————Black Shipping Weight ————————————————————————————————————————————————0.20lbs (0.091kg) Probe Dimension —————————————————————————————————————————6.35 mm (0.25”) Diameter Electrical Dissipation Factor ———————————————————————————————————————————2.2mW/K (Thermistor) Max Power @ 25°C (77°F) ——————————————————————————————————————75mW (Thermistor) Thermal Time Constant ———————————————————————————————————Less than 10s (Thermistor) Wire Material (TS-DXX Series) ————————————————————————————————————Plenum rated FT-6 Wire Length (TS-DXX Series) —————————————————————————————————————————3.05 m (10’) Temperature Sensor with Enclosure Sensor Type1 ——————————————————————————————————————————10kΩ NTC thermistor, Type 2Accuracy ——————————————————————————————————————————————————————±0.2°C; ±0.36°FProbe Sensing Range —————————————————————————————————————-20 to 105°C (-4 to 221°F)Probe Material ——————————————————————————————————————————304 Series Stainless SteelProbe Dimension ———————————————————————————————————————6.00 mm (0.236”) DiameterEnclosure Type —————————————————————————— Material; Grey ABS; UL94-V0, IP65 (NEMA 4X) Shipping Weight ————————————————————————————————————————————— 0.60 lbs (0.2727 kg) Agency Approvals Material2 ————————————————————————————————————————————————————————————UL94-V0 1. Temperature sensor type stated is standard. Other temperature sensor types are available. 2. All materials and manufacturing processes comply with the RoHS directive. 4/4 TS-D2X Sensor Series_DS_10_EN Specifications subject to change without notice. ECLYPSE, Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. All other trademarks are property of their respective owner. ©, Distech Controls Inc., 2018. All rights reserved. 82.5 mm 3.25 “ 69.8 mm 2.75 “ 76.2 mm 3.00 “ 52.0 mm 2.05 “ Various Probe Lengths See Ordering Chart 0.5” NPT 6.0mm 0.236“ Foam Gasket 304 Series S/S Probe Dimensions Bracket Applications ⎕Industrial OEM Equipment ⎕Hydraulic Systems ⎕Compressor Control ⎕HVAC/R Equipment ⎕Industrial Engines Features & Benefits ⎕High Overpressure Option Available on Se- lect Ranges ⎕Operates Over a Wide Temperature Band ⎕Compatible w/ a Variety of Gases & Liquids ⎕Operates on Low Cost Unregulated DC Pow- er ⎕Suitable For High Shock & Vibration Appli- cations ⎕No Seals or O-Rings to Cause Leakage ⎕No Brazed Joints Susceptible to Corro- sion Problems ⎕CE & RoHS Compliant Overview The PS-2091 Liquid Static Pressure Sensor Se-ries is designed for high performance, reliabili-ty and versatility at an affordable price. It offers exceptional ±0.25% FS accuracy with pressure ranges from 1 PSI up to 10,000 PSI to meet a multitude of demanding applications. The PS-2091 Series features all stainless steel wetted materials and offers many pressure and electri-cal connections to satisfy challenging installation requirements. The PS-2091 Series features a patented overpressure stop to protect the sensor against unexpected spikes or in high pulsation applications. Datasheet PS-2091 Series Liquid Static Pressure Sensors PS-LSP Series2/6 Model Selection PS-001P G 2M 11 02 Pressure Range 001P = 0 to 1 psi 0012 = 0 to 2 psi 005P = 0 to 5 psi 010P = 0 to 10 psi 025P = 0 to 25 psi 050P = 0 to 50 psi 100P = 0 to 100 psi 200P = 0 to 200 psi 250P = 0 to 250 psi 500P = 0 to 500 psi 10CP = 0 to 1,000 psi 15CP = 0 to 1,500 psi 20CP = 0 to 2,000 psi 30CP = 0 to 3,000 psi 50CP = 0 to 5,000 psi 10KP = 0 to 10,000 psi Z01P = 0 to -14.7 psi Pressure Type G = GaugeC = Compound Pressure Fitting 2M = 1/4” NPT Male Output 11 = 4-20mA Electrical Termination 02 = 2 ft. cable 3/6PS-LSP Series Standard Option Full Scale Range (PSI) Proof Pressure (PSI) Burst Pressure (PSI) High Proof Pressure (PSI) High Burst Pressure (PSI) 1 2 250 N/A N/A 2 4 250 N/A N/A 5 10 250 N/A N/A 10 20 500 N/A N/A 25 50 500 N/A N/A 50 100 750 800 5,000 100 200 1,000 1,000 5,000 200 400 2,000 1,500 5,000 250 500 2,000 2,000 8,000 500 1,000 3,000 2,500 10,000 1,000 2,000 5,000 4,000 10,000 1,500 2,500 6,000 5,000 12,000 2,000 3,000 6,500 N/A N/A 3,000 4,500 7,500 N/A N/A 5,000 7,500 10,000 N/A N/A 10,000 12,500 20,000 N/A N/A -14.7 (Vacuum)10 15 N/A N/A Proof Pressure PS-LSP Series4/6 Product Specifications Performance Data Accuracy RSS1 (at constant temp) ———————————————————————————————————————±0.25% FS Non-Linearity, BFSL —————————————————————————————————————————————————±0.22% FS Hysteresis ——————————————————————————————————————————————————————————0.10% FS Non-Repeatability ————————————————————————————————————————————————————0.05% FS Thermal Effects Compensated Range °F (°C) ———————————————————————————————————-4 to +176 (-20 to +80) Zero Shift %FS/100°F (%FS/50°C) ———————————————————————————————————————±2.0 (±1.8) Span Shift %FS/100°F (%FS/50°C) ———————————————————————————————————————±1.5 (±1.3) Warm-up Shift ————————————————————————————————————————————————————0.1% FS Total Response Time ———————————————————————————————————————————————————5 milliseconds Long Term Stability ——————————————————————————————————————————————— 0.5% FS/1 YR Pressure Media —————————————————————————————Liquids and gases compatible with 17-4 PH Stainless Steel.2 Physical Description Case ————————————————————————————————————————————————————Stainless Steel & ValoxWetted Material ————————————————————————————————————————————17-4 PH Stainless SteelElectrical Connection ———————————————————————————————————————2 ft. multiconductor cablePressure Fitting5 ————————————————————————————————————————————1/4” -18 NPT external,17-4 PH Stainless SteelVent ——————————————————————————————————————————————————————————Through cableWeight (approx.) ————————————————————————————————————————————2.3 ounces (65 grams) Environmental Data Operating3 Temperature °F (°C) ———————————————————————————————-40 to + 185 (-40 to +85)Storage Temperature °F (°C) —————————————————————————————————-40 to + 185 (-40 to +85)Shock3 ————————————————————————————————————————————————————————200g operatingAcceleration ———————————————————————————————————————————————————10 g Maximum5Shock3 ————————————————————————————————————————————————————————200g OperatingVibration4 ——————————————————————————————————————————————————————————————20gEnvironmental Protection —————————————————————————————————————————Weather Resistant Electrical Data (Voltage) Circuit —————————————————————————————————————————————————3-Wire (COM, OUT, EXC)Excitation ————————————————————————————————————————————————————————9 to 30 VDCOutput6 ———————————————————————————————————————————————————————0.5 to 5.5 VDC7Output Impedance —————————————————————————————————————————————————————10 ohms 5/6PS-LSP Series Electrical Data (Current) Circuit ———————————————————————————————————————————————————————————————2-Wire Output8 ———————————————————————————————————————————————————————————4 to 20mA9 External Load ————————————————————————————————————————————————————0 to 800 ohms Minimum supply voltage (VDC) —————————————————9+ 0.02 x (Resistance of receiver plus line) Maximum supply voltage (VDC) ———————————————30+ 0.004 x (Resistance of receiver plus line) Notes: 1. RSS of Non-Linearity, Hysteresis, and Non-Repeatability. 2. Note: Hydrogen not recommended for use with 17-4 PH Stainless Steel. 3. Mil-Std. 202, Method 213B, Cond. C 4. Mil-Std. 202, Method 204, Cond. C 5. See ordering information for other fittings available (minimum quantities apply). 6. Calibrated into a 50K ohm load, operable into a 5000 ohm load or greater. 7. Zero output factory set to within ±50mV. Span (Full Scale) output factory set to within ±50mV. 8. Calibrated at factory with a 24 VDC loop supply voltage and a 250 ohm load. 9. Zero output factory set to within ±0.16mA. Span (Full Scale) output factory set to within ±0.16mA. 10. Specifications subject to change without notice. Product Specifications (cont’d) PS-2091 Series_DS_10_EN6/6 Specifications subject to change without notice. Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. All other trademarks are property of their respective owner. ©, Distech Controls Inc., 2015 to 2017. All rights reserved. Dimensions MADE INUSA Family owned and made in the USA since 1985 901 Tryens Road Aston, PA 19301 Phone: 877-373-2700 Web: sensaphone.com TECH SPECS All specifi cations subject to change without notice Product Name Part Number 4-20mA Type Vibration Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .FGD-0303 Magnetic Mount for Vibration Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .FGD-0303-MOUNT 24VDC Power Supply for 4-20mA Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .FGD-0070 Name 4-20mA Type Vibration Sensor with 5m Cable Operating Voltage 18-32 DC Input/Output Circuit 1 x analog 4-20mA Measuring Range (mm/s)0 - 25 RMS Frequency Range (Hz)10 - 1,000 Ambient Temperature -25° to 80°C Environmental Rating IP 67 / IP 68 / IP 69K Monitor the overall vibration of equipment The electronic vibration sensor monitors the overall vibration condition of machines and equipment according to DIN ISO 10816. The sensor measures vibration velocity on a non-rotating component surface. The characteristic value is provided as a current signal (4-20 mA) for connection to the Sensaphone. The Sensaphone triggers an alarm when an out of limit value is exceeded. Requires a 24VDC power supply (FGD-0070) 4-20mA Vibration Sensor4-20mASeries Shown with optional magnetic mount 397Power SuppliesPROCESS CONTROLDWYER INSTRUMENTS, INC. | dwyer-inst.com LOW COST DC POWER SUPPLYRegulated 0.5 A, 1 A Fuse ProtectionThe Model BPS-005 Low Cost DC Power Supply is a regulated .5 A power supply that accepts 24 VAC input and provides an adjustable 1.5 to 29 VDC output. Output voltage adjustments are made using the on-board potentiometer while measuring the output with a multimeter. A compact snap track design allows the power supply to be surface mounted within a panel. FEATURES/BENEFITS• Snap track design allowing for easy panel installation• Regulated 0.5 Amp SPECIFICATIONSInput: 24 VAC/VDC 50/60 Hz.Output: 24 VDC (full wave rectified and regulated) adjustable 1.5 to 29 VDC, 0.5 A max.Maximum Current Output: 0.5 A.Over-Current Protection: 1 A fuse.Operating Temperature: 32 to 130°F (0 to 55°C).Humidity Limits: 95% (non-condensing).Weight: 0.4 lb.Agency Approvals: Meets the technical requirements of EU Directive 2011/65/EU (RoHS II).LOW COST DC POWER SUPPLYRegulated 1.5 A, 3 A Fuse ProtectionDIN RAIL MOUNT DC POWER SUPPLY Regulated 1 A, 24 VDC Output SNAPTRACK4-1/16[103.12]2-19/64[58.17]1-15/16[49.02]11/16[17.27] 2.362[60.00].524[13.30]1.437[36.50] .118 [3.00] 3.543[90.00]SIZED FOR35MM DINRAIL MOUNT 2-13/32[61.19]3[76.20]2-1/16[52.28]19/32[14.97]SNAPTRACKThe Model BPS-015 Low Cost DS Power Supply is used to convert 24 VAC to a regulated DC power source for transmitters with 4 to 20 mA outputs. The output voltage can be field adjusted from 1.5 V to 27 V using a potentiometer. The 3 A fuse protects the power supply from over-current conditions. The snap-on bracket can be quickly surface mounted to any flat surface.FEATURES/BENEFITS• Snap track design allowing for easy panel installation• Regulated 1.5 Amp The Model SCD-PS DIN Rail Mount DC Power Supply is a compact and economical solution for providing DC power to any Dwyer pressure, humidity, temperature, level or air velocity transmitters. Input voltage can range from 100 to 240 VAC, 50/60 Hz without any jumpers or dip switch selections. A plastic cover slides over the terminals in order to prevent shock from accidental touching of high voltage wires. FEATURES/BENEFITS• DIN rail mount• Universal supply voltage input SPECIFICATIONSInput: 24 VAC/VDC 50/60 Hz.Output: 24 VDC (full wave rectified and regulated) adjustable 1.5 to 27 VDC.Maximum Current Output: 1.5 A (de-rated to 400 mA for non-isolated circuits).Temperature Limits: 32 to 130°F (0 to 55°C).Humidity Limits: 95% (non-condensing).Weight: 0.4 lb. SPECIFICATIONS AC Input: 100 to 240 VAC, 50/60 Hz. DC Output: 24 VDC (±3% VDC). Maximum Current Output: 1 A. Noise: Under 100 mVp-p typical at full load. Temperature Limits: 32 to 131°F (0 to 55°C). Weight: 5.6 oz (158 g). Agency Approvals: CE, cULus. MODEL BPS-005®MODEL BPS-015MODEL SCD-PS APPLICATIONS • BAS• HVACAPPLICATIONS • BAS• HVAC APPLICATIONS • BAS• HVAC MODEL CHARTModelDescriptionBPS-005 Low cost DC power supplyMODEL CHARTModelDescriptionBPS-015 Power supply MODEL CHART Model Description SCD-PS DIN Rail DC Power Supply Features & Benefits ⎕Enclosure is formed and spot welded from 12 or 14 gauge steel. ⎕Removable 12 or 14 gauge inner panel is mounted in the rear of the enclosure on col-lar studs. ⎕Removable door is mounted on slip hinges. ⎕Door is fastened with a slotted quarter turn latch; doors 30” and higher are provided with two latches. ⎕A bonding stud is provided on the door and a grounding stud is provided in the box. ⎕Mounting holes are provided in the rear of the enclosure. Piano hinge on 12 gauge units. ⎕Enclosure and door are finished in ANSI 61 gray powder coating. ⎕Inner panel is finished in white powder coat- ing. Applications ⎕Designed for indoor use to house controls, instruments and components not requiring oil-tight or dust-tight protection. Datasheet Standards ⎕UL-50 Type 1 ⎕CSA Type 1 ⎕Complies with: ⎕ NEMA Type 1 ⎕IEC 60529, IP20 PP-N1A Series Medium, NEMA 1, Wallmount Enclosures Accessories PP-AP Series Perforated Panels for PP-N1A Series Enclosures PP-1427LKN1 Lock kit Other accessory options are available. PP-N1A Series2/4 Part No.Dimensions Panel Size Panel Gauge No. of Studs A B C D E PP-N1A16127 16.00 12.00 7.00 13.00 10.50 14.00 4.00 PP-N1A16167 16.00 16.00 7.00 13.00 14.50 14.00 4.00 PP-N1A16207 16.00 20.00 7.00 13.00 18.50 14.00 4.00 PP-N1A20167 20.00 16.00 7.00 17.00 14.50 14.00 4.00 PP-N1A20207 20.00 20.00 7.00 17.00 18.50 14.00 4.00 PP-N1A24167 24.00 16.00 7.00 21.00 14.50 14.00 4.00 PP-N1A24207 24.00 20.00 7.00 21.00 18.50 14.00 4.00 PP-N1A24247 24.00 24.00 7.00 21.00 22.50 12.00 4.00 PP-N1A30207 30.00 20.00 7.00 26.00 18.50 12.00 6.00 PP-N1A30247 30.00 24.00 7.00 26.00 22.50 12.00 6.00 PP-N1A36247 36.00 24.00 7.00 32.00 22.50 12.00 6.00 PP-N1A36307 36.00 30.00 7.00 32.00 28.50 12.00 8.00 PP-N1A16129 16.00 12.00 9.00 13.00 10.50 14.00 4.00 PP-N1A20169 20.00 16.00 9.00 17.00 14.50 14.00 4.00 PP-N1A20209 20.00 20.00 9.00 17.00 18.50 14.00 4.00 PP-N1A20249 20.00 24.00 9.00 17.00 22.50 14.00 4.00 PP-N1A24209 24.00 20.00 9.00 21.00 18.50 14.00 4.00 PP-N1A24249 24.00 24.00 9.00 21.00 22.50 12.00 4.00 PP-N1A30209 30.00 20.00 9.00 26.00 18.50 12.00 6.00 PP-N1A30249 30.00 24.00 9.00 26.00 22.50 12.00 6.00 PP-N1A30309 30.00 30.00 9.00 26.00 28.50 12.00 8.00 PP-N1A36249 36.00 24.00 9.00 32.00 22.50 12.00 6.00 PP-N1A36309 36.00 30.00 9.00 32.00 28.50 12.00 8.00 PP-N1A42249 42.00 24.00 9.00 38.00 22.50 12.00 6.00 PP-N1A242012 24.00 20.00 12.00 21.00 18.50 14.00 4.00 PP-N1A242412 24.00 24.00 12.00 21.00 22.50 12.00 4.00 PP-N1A302412 30.00 24.00 12.00 26.00 22.50 12.00 6.00 PP-N1A363012 36.00 30.00 12.00 32.00 28.50 12.00 8.00 PP-N1A423012¹42.00 30.00 12.00 38.00 28.50 12.00 8.00 PP-N1A423612¹42.00 36.00 12.00 38.00 34.50 12.00 8.00 PP-N1A483612¹48.00 36.00 12.00 44.00 34.50 12.00 8.00 Notes: 1. 12 gauge construction Model Selection 3/4PP-N1A Series Part No.DimensionsPanel SizePanel GaugeNo. of Studs ABCDE PP-N1A1612716.0012.007.0013.0010.5014.004.00 PP-N1A1616716.0016.007.0013.0014.5014.004.00 PP-N1A1620716.0020.007.0013.0018.5014.004.00 PP-N1A2016720.0016.007.0017.0014.5014.004.00 PP-N1A2020720.0020.007.0017.0018.5014.004.00 PP-N1A2416724.0016.007.0021.0014.5014.004.00 PP-N1A2420724.0020.007.0021.0018.5014.004.00 PP-N1A2424724.0024.007.0021.0022.5012.004.00 PP-N1A3020730.0020.007.0026.0018.5012.006.00 PP-N1A3024730.0024.007.0026.0022.5012.006.00 PP-N1A3624736.0024.007.0032.0022.5012.006.00 PP-N1A3630736.0030.007.0032.0028.5012.008.00 PP-N1A1612916.0012.009.0013.0010.5014.004.00 PP-N1A2016920.0016.009.0017.0014.5014.004.00 PP-N1A2020920.0020.009.0017.0018.5014.004.00 PP-N1A2024920.0024.009.0017.0022.5014.004.00 PP-N1A2420924.0020.009.0021.0018.5014.004.00 PP-N1A2424924.0024.009.0021.0022.5012.004.00 PP-N1A3020930.0020.009.0026.0018.5012.006.00 PP-N1A3024930.0024.009.0026.0022.5012.006.00 PP-N1A3030930.0030.009.0026.0028.5012.008.00 PP-N1A3624936.0024.009.0032.0022.5012.006.00 PP-N1A3630936.0030.009.0032.0028.5012.008.00 PP-N1A4224942.0024.009.0038.0022.5012.006.00 PP-N1A24201224.0020.0012.0021.0018.5014.004.00 PP-N1A24241224.0024.0012.0021.0022.5012.004.00 PP-N1A30241230.0024.0012.0026.0022.5012.006.00 PP-N1A36301236.0030.0012.0032.0028.5012.008.00 PP-N1A423012¹42.0030.0012.0038.0028.5012.008.00 PP-N1A423612¹42.0036.0012.0038.0034.5012.008.00 PP-N1A483612¹48.0036.0012.0044.0034.5012.008.00 Notes: 1. 12 gauge construction Part No.Mounting Dimensions Panel Clearance Ship Wt. lbs G H J Q P F K O PP-N1A16127 13.88 7.00 2.50 1.06 0.31 6.04 1.50 -25 PP-N1A16167 13.88 11.00 2.50 1.06 0.31 6.04 1.50 -30 PP-N1A16207 13.88 15.00 2.50 1.06 0.31 6.04 1.50 -36 PP-N1A20167 17.88 11.00 2.50 1.06 0.31 6.04 1.50 -37 PP-N1A20207 17.88 15.00 2.50 1.06 0.31 6.04 1.50 -43 PP-N1A24167 21.88 11.00 2.50 1.06 0.31 6.04 1.50 -43 PP-N1A24207 21.88 15.00 2.50 1.06 0.31 6.04 1.50 -51 PP-N1A24247 21.88 19.00 2.50 1.06 0.31 6.01 1.50 -67 PP-N1A30207 27.50 12.75 3.63 1.25 0.44 6.01 2.00 6.16 67 PP-N1A30247 27.50 16.75 3.63 1.25 0.44 6.01 2.00 6.16 80 PP-N1A36247 33.50 16.75 3.63 1.25 0.44 6.01 2.00 7.16 94 PP-N1A36307 33.50 22.75 3.63 1.25 0.44 6.01 2.00 7.16 114 PP-N1A16129 13.88 7.00 2.50 1.06 0.31 8.04 1.50 -27 PP-N1A20169 17.88 11.00 2.50 1.06 0.31 8.04 1.50 -31 PP-N1A20209 17.88 15.00 2.50 1.06 0.31 8.04 1.50 -47 PP-N1A20249 17.88 19.00 2.50 1.06 0.31 8.04 1.50 -55 PP-N1A24209 21.88 15.00 2.50 1.06 0.31 8.04 1.50 -55 PP-N1A24249 21.88 19.00 2.50 1.06 0.31 8.01 1.50 -125 PP-N1A30209 27.50 12.75 3.63 1.25 0.44 8.01 2.00 6.16 72 PP-N1A30249 27.50 16.75 3.63 1.25 0.44 8.01 2.00 6.16 85 PP-N1A30309 27.50 22.75 3.63 1.25 0.44 8.01 2.00 6.16 102 PP-N1A36249 33.50 16.75 3.63 1.25 0.44 8.01 2.00 7.16 107 PP-N1A36309 33.50 22.75 3.63 1.25 0.44 8.01 2.00 7.16 120 PP-N1A42249 39.50 16.75 3.63 1.25 0.44 8.01 2.00 8.16 111 PP-N1A242012 21.88 15.00 2.50 1.06 0.31 11.04 1.50 -61 PP-N1A242412 21.88 19.00 2.50 1.06 0.31 11.01 1.50 -132 PP-N1A302412 27.50 16.75 3.63 1.25 0.44 11.01 2.00 6.16 94 PP-N1A363012 33.50 22.75 3.63 1.25 0.44 11.01 2.00 7.16 129 PP-N1A423012¹39.50 22.75 3.63 1.25 0.44 11.01 2.00 8.16 144 PP-N1A423612¹39.50 28.75 3.63 1.25 0.44 11.01 2.00 8.16 169 PP-N1A483612¹45.50 28.75 3.63 1.25 0.44 11.01 2.00 9.16 197 Notes: 1. 12 gauge construction Model Selection 4/4 PP-N1A Series_DS_10_EN Specifications subject to change without notice. Distech Controls, and the Distech Controls logo are trademarks of Distech Controls Inc. All other trademarks are property of their respective owner. ©, Distech Controls Inc., 2015. All rights reserved. Dimensions OXOBOXO LOFTS42 Pink Row Uncasville, CT As Prepared By500 Corporate Row.Cromwell, CT 06416Phone Number (800) 890‐2022Fax Number (860) 316‐5348 Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYTable Of ContentsREVMDC19‐000150SCALENoneSHEET2 OF 14Table Of Contents1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac Power1 Title Page2Table Of Contents3 Summary of Material4Notes Page5Riser6 Boiler/CTower/HX/Pumps Control7 Pumps P‐3, 4, 5 & 6 Control8 Boiler/CTower/HX/Pumps Controllers9 Controls Enclosure10 Domestic HW Boilers11 WSHP T'Stat Wiring12 Symbol Legend13 VFD and Grounding14 Wire Specification Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYSummary of MaterialREVMDC19‐000150SCALENoneSHEET3 OF 14Summary of Material1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac PowerLabel Description Manufacturer PN Quantity24DC 24AC-24DC P/S 1.5Amp Alps BPS-015 1VIB Vibration Sensor, Requires Base Alps FGD-0303 1VIB-M Vibration Sensor Mount Alps FGD-0303-Mount 18UI6DOT 8UI-6DOT Module Distech CDIY-8UI6DOT-00 28UI6UO 8UI-6UO Module Distech CDIY-8UI6UO-00 1CS1 Current Switch 0.5-150a Split-Core Distech CS-RIBXGTA 4DTI4 Duct Temp/Immersion Sensor 4" 10k T2 Distech TS-D2X004 7GWP1 Pressure Guage, 4-20mA Distech PS-2LSP0100PP5D 2IW4 Immersion Well 4" Distech TS-WS304004 7OAH1 OSA Temp/Humidity Distech HS-O3PST 1PERF5 Enclosure 24"x24" Perf Panel Distech PP-AP2424PP 1PS24 24v Source P/S, 18vdc Output Distech CDIT-PS24-00 1RN1 Relay Nippled SPDT 10-30VAC/DC/120vac Coil Distech RE-RIBU1C 8S1048 Connected System Controller Distech CDIY-S1048ENVY-00 1UPS Uniterruptible Power Supply Distech PSH600-UPS 1XF-5 Transformer/AC Power Supply 100VA 120 Primary 24vac Sec Distech PSH100A 1PNL5 Nema 1 Enclosure 24"x24" Distech PP-N1A24247 1Parts this Page Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYNotes PageREVMDC19‐000150SCALENoneSHEET4 OF 14Notes Page1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac Power Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYRiserREVMDC19‐000150SCALENoneSHEET5 OF 14Riser1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac PowerBACnet MS/TPECY‐S1000HostDeviceSubNetEOLTo Bldg NetworkEnclosure to be Located in Boiler RoomLochinvarBoiler 1&2EOLUPSECY‐PS2424V COM24VAC/DC24VAC 120VACLochinvarBldg “B” DHW Boiler 1LochinvarBldg “HK” DHW Boiler1Label Description Manufacturer PN QuantityUPS Uniterruptible Power Supply Functional Devices PSH600-UPS 1Parts this Page Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYBoiler/CTower/HX/Pumps ControlREVMDC19‐000150SCALENoneSHEET6 OF 14Boiler/CTower/HX/Pumps Control1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac Power+‐2310111213682021AmpsVFDEnableSpeed0‐10v InAlarm+‐P‐1 (VFD By Others)+‐2310111213682021AmpsVFDEnableSpeed0‐10v InAlarm+‐P‐2 (VFD By Others)RN1RN11OSA TempUI‐012OSA HumidityUI‐02+24vacOAH1OSATempTo Boiler #1Term 31/32Provided by Manuf+‐2310111213682021AmpsVFDEnableSpeed0‐10v InAlarm+‐CT Fan (VFD By Others)RN1Vibration Sensor+ ‐24vdcP/S+ ‐Input PointBrown Wire +White Wire (4‐20mA)5P‐1 VFD AmpsUI‐056P‐2 VFD AmpsUI‐067P‐1 VFD AlarmUI‐078P‐2 VFD AlarmUI‐0832CT Fan VFD AmpsUI‐30434CT Fan VFD AlarmUI‐30635Sand Filter AlrmUI‐30710P‐1 VFD S/SUO‐0211P‐2 VFD S/SUO‐0323CT Fan VFD S/SUO‐20238P‐1 VFD SpeedUO‐30239P‐2 VFD SpeedUO‐30340CT Fan VFD SpeedUO‐3049Boiler Sys S/SUO‐01SWRMount In 2" Lines @ Corridor 206 Per HP1.03DTI4IW438A 39B7 83334From PriorBacnet DeviceBlkWhtShldTo Next Bacnet Device38A 39B1819ABLochinvarLochinvarSWSProvided by ManufTo Boiler #1Term 27/28P‐3P‐4HX‐1DTI4IW4P‐1P‐2DTI4IW4P‐5P‐6RedBlk+24dcv‐24dcv4‐20mA SignalGWP1RedBlk+24dcv‐24dcv4‐20mA SignalGWP1DTI4IW4CT Located On RoofS‐1 Remote Sump in Boiler Room31 32To Provided OSA Temp SensorDTI4IW4B‐1B‐2RN1VIBVIB‐MDTI4IW4DTI4IW43SWS Sup PressureUI‐034SWS Ret PressureUI‐0415SWS Sup TempUI‐20116SWS Ret TempUI‐20219Boiler Sup TempUI‐20520Boiler Ret TempUI‐20629CHW Sup TempUI‐30130CHW Ret TempUI‐30237Boiler SetPtUO‐30133CT Sump TempUI‐30531CT Vibration SenUI‐30324DCPipe Pressure Gauge TransmitterLabel Description Manufacturer PN Quantity24DC 24AC-24DC P/S 1.5Amp Alps BPS-015 1VIB Vibration Sensor, Requires Base Alps FGD-0303 1VIB-M Vibration Sensor Mount Alps FGD-0303-Mount 1DTI4 Duct Temp/Immersion Sensor 4" 10k T2 Distech TS-D2X004 7GWP1 Pressure Guage, 4-20mA Distech PS-2LSP0100PP5D 2IW4 Immersion Well 4" Distech TS-WS304004 7OAH1 OSA Temp/Humidity Distech HS-O3PST 1RN1 Relay Nippled SPDT 10-30VAC/DC/120vac Coil Distech RE-RIBU1C 4Parts this PageSand Filter Control Panel Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYPumps P‐3, 4, 5 & 6 ControlREVMDC19‐000150SCALENoneSHEET7 OF 14Pumps P‐3, 4, 5 & 6 Control1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac Power18P‐4 StatusUI‐20417P‐3 StatusUI‐20320P‐5 StatusUI‐20721P‐6 StatusUI‐208P‐6 MHOAMFan MotorLNRN1CS1P‐4 MHOAMFan MotorLNRN1CS1P‐5 MHOAMFan MotorLNRN1CS1P‐3 MHOAMFan MotorLNRN1CS112P‐3 S/SUO‐0413P‐4 S/SUO‐0514P‐5 S/SUO‐0622P‐6 S/SUO‐201Label Description Manufacturer PN QuantityCS1 Current Switch 0.5-150a Split-Core Distech CS-RIBXGTA 4RN1 Relay Nippled SPDT 10-30VAC/DC/120vac Coil Distech RE-RIBU1C 4Parts this Page Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYBoiler/CTower/HX/Pumps ControllersREVMDC19‐000150SCALENoneSHEET8 OF 14Boiler/CTower/HX/Pumps Controllers1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac PowerECY‐S1000From Prior Bacnet MS/TP DeviceTo Next Bacnet MS/TP DeviceBlkWhtShldHostDeviceSubNetS1048PS2424VAC 120VACECY‐PS2424V COM24VAC/DCUI1COMCOMUI2UI3UI418VDCUI5COMCOMUI6UI7UI818VDC1OSA TempUI‐01LOWER TBUPPER TB2OSA HumidityUI‐023SWS Sup PressureUI‐034SWS Ret PressureUI‐045P‐1 VFD AmpsUI‐056P‐2 VFD AmpsUI‐067P‐1 VFD AlarmUI‐078P‐2 VFD AlarmUI‐088UI6DOTC1DO1 DO2 DO3 DO4 DO5 DO6DIGITAL OUTPUTSC2 C3C4C5 C68UI6DOTUI1COMCOMUI2UI3UI418VDCUI5COMCOMUI6UI7UI818VDC22P‐6 S/SDO‐20123CT Fan VFD S/SDO‐20224Spare Signal PointDO‐20326Spare Signal PointDO‐20427Spare Signal PointDO‐20528Spare Signal PointDO‐20615SWS Sup TempUI‐20101LOWER TBUPPER TB16SWS Ret TempUI‐20217P‐3 StatusUI‐20318P‐4 StatusUI‐20419Boiler Sup TempUI‐20520Boiler Ret TempUI‐20620P‐5 StatusUI‐20721P‐6 StatusUI‐2088UI6DOTC1DO1DO2DO3DO4DO5DO6DIGITAL OUTPUTSC2 C3C4C5 C68UI6DOT Locate Enclosure in Boiler Room3.1 WATER SOURCE HEAT PUMPS (WSHP) A. Water Source heat pumps shall be controlled by the associated apartment’s programmable thermostat. B. Upon a call for heating or cooling in the space (apartment) the WSHP’s source water valves shall open and the WSHP’s SA fan shall start and the WSHP’s compressor (refrigeration system) shall operate to maintain associated space temperature. The WSHP’s reversing valve shall switch from heating to cooling operation depending on the call form the thermostat. C. There shall be a field adjustable dead band between heating and cooling. D. When there is no call for heating and cooling the WSHP’s fan and refrigeration system shall shut down and its associated source water valve shall close. (NOTE: Mounting and wiring of WSHP thermostat by CTC). 3.2 SOURCE WATER SYSTEM TEMPERING AND DISTRIBUTION SYSETM A. Source water shall be continuously available and operating. Main source water pumps P‐1 & P‐2 shall operate continuously. B. System shall operate to maintain source water temperature of a field adjustable set point, initially set at 65 °F (adj) with dead band between water heating and water cooling. C. If the source water temperature falls below the set point (and dead band) then the water heating shall initiate. 1. One boiler pump (P‐3 or P‐4) shall sequence on and once flow is confirmed the associated boiler shall sequence on. 2. Boilers gas burner shall modulate to maintain water temperature. 3. If first initiated boiler cannot maintain water temperature set point then second boiler shall sequence on through its manufacture controls. 4. Boilers shall be set up as lead lag that changes between boilers to equalize run time. D. If source water rises above set point (and dead band) then source water shall return (SWR) into the heat exchanger (HX‐1) to cool it. 1. Condenser water pumps (P‐5 and P‐6) shall operate to maintain HX‐1 discharge temperature. 2. The cooling tower (CT‐1) shall be enabled during the cooling season. CT‐1 fan shall ramp up and down to maintain water temperature in sump‐1. 3. If the vibration sensor value exceeds the operational limits of the cooling tower, shut down fan. E. Source water pumps P‐1 and P‐2 shall operate continuously. The pumps VFD shall ramp the pump up and down to satisfy SWS and SWR pressure differential as sensed by the SWS and SWR piping pressure sensors. F. Dual pumps for the same piping feeds (P‐1/P‐2 and P‐5/P‐6) shall be lead lag, with the lag pump operating only if the lead pump fails to operate. Lead/lag status shall switch between pumps periodically to equalize run time. Label Description Manufacturer PN Quantity4UI4UO 4UI-4UO Module Distech CDIY-4UI4UO-00 18UI6DOT 8UI-6DOT Module Distech CDIY-8UI6DOT-00 2PS24 24v Source P/S, 18vdc Output Distech CDIT-PS24-00 1S1048 Connected System Controller Distech CDIY-S1048ENVY-00 1Parts this PageUI1COMCOMUI2UI3UI418VDCUI5COMCOMUI6UI7UI818VDC37Boiler SetPtUO‐30138P‐1 VFD SpeedUO‐30239P‐2 VFD SpeedUO‐30340CT Fan VFD SpeedUO‐30441Spare Signal PointUO‐30542Spare Signal PointUO‐30629CHW Sup TempUI‐301LOWER TBUPPER TB30CHW Ret TempUI‐30231CT Vibration SenUI‐30332CT Fan VFD AmpsUI‐30433CT Sump TempUI‐30534CT Fan VFD AlarmUI‐30635Sand Filter AlrmUI‐30736Spare Signal PointUI‐3088UI6UOUO1UO2UO5UO3UO4UO6COMCOMCOMCOMCOMCOM9Boiler Sys S/SDO‐0110P‐1 VFD S/SDO‐0211P‐2 VFD S/SDO‐0312P‐3 S/SDO‐0413P‐4 S/SDO‐0514P‐5 S/SDO‐06DO1DO2DO5DO3DO4DO6C1C2C5C3C4C6+24vac‐24vacDO1DO2DO5DO3DO4DO6C1C2C5C3C4C6+24vac‐24vac Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYControls EnclosureREVMDC19‐000150SCALENoneSHEET9 OF 14Controls Enclosure1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac PowerPNL51"x 1 ½"1 ½”x3"1 ½”x3"XF5CHXF‐5Distech 24x24PERF51 ½”x3"1 ½”x3"1 ½”x3"1”x3" Locate Enclosure in Boiler RoomLabel Description Manufacturer PN QuantityPERF5 Enclosure 24"x24" Perf Panel Distech PP-AP2424PP 1PNL5 Nema 1 Enclosure 24"x24" PP-N1A24247 SCE24N2406NK-B 1XF-5 Transformer/AC Power Supply 100VA 120 Primary 24vac Sec Functional Devices PSH100A 1Parts this Page Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYDomestic HW BoilersREVMDC19‐000150SCALENoneSHEET10 OF 14Domestic HW Boilers1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac PowerLochinvarP‐1P‐2HW Recirculation120°F Tempered Water SupplyDomestic HW Storage TanksB‐1Domestic Hot Water BoilersBuilding HK & B(Typical of 2)Storage Tank Temp Sensor(Provided w/ Boiler)P‐1Boiler/DHW Circ PumpP‐2Recirculation PumpCN41617B‐1From PriorBacnet DeviceBlkWhtShldTo Next Bacnet DeviceValve by OthersWiring Only(No DDC) Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYWSHP T'Stat WiringREVMDC19‐000150SCALENoneSHEET11 OF 14WSHP T'Stat Wiring1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac PowerY O G R CY O G R CWSHP T’Stat InterfaceT’Stat Provided by Manuf. Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYSymbol LegendREVMDC19‐000150SCALENoneSHEET12 OF 14Symbol Legend1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac PowerCommon Abbreviations:AC - Air Conditioning EVAP - Evaporator SA - Supply AirACU - Air Conditioning Unit F - Fahrenheit SF - Supply FanAHU - Air Handling Unit FCU - Fan Coil Unit SP - Static PressureAI - Analog Input HOA - Hand / Off / Auto TEMP - TemperatureAO - Analog Output HP - Heat Pump UH - Unit HeaterAUTO - Automatic HRU - Heat Recovery Unit UV - Unit VentilatorAUX - Auxiliary HTEX - Heat Exchanger VAV - Variable Air VolumeC - Common HW - Hot Water VVTU - Variable Volume Terminal UnitCHW - Chilled Water HWP - Hot Water Pump W/ - withCHWP - Chilled Water Pump HWR - Hot Water Return W/O - withoutCHWR - Chilled Water Return HWS - Hot Water Supply WSHP - Water-Source Heat PumpCHWS - Chilled Water Supply MAX - MaximumCOND - Condenser MIN - MinimumCW - Condenser Water MISC - MiscellaneousCWP - Condenser Water Pump NC - Normally ClosedCWR - Condenser Water Return NO - Normally OpenCWS - Condenser Water Supply OA - Outdoor AirDA - Discharge Air PIU - Powered Induction UnitDI - Digital Input RA - Return AirDO - Digital Output RF - Return FanEA - Exhaust Air RH - Relative HumidityEF - Exhaust Fan RTU - Roof-top UnitSFSupply FanEFExhaust FanRFReturn FanFan w/ Inlet Vane ControlPump or T T Room Temperature Sensor or H H Room Humidity SensorFreezeStatSmoke DetectorFSFlow Sensor2 ‐ Way Valve3 ‐ Way ValveSTMSteam Heating CoilCHWChilled Water Cooling CoilHWHot Water Heating CoilGASGas HeatingElectric Heating CoilDXDX Cooling CoilDuct Temperature SensorAveraging Duct Temperature SensorDuct Humidity SensorImmersion Temperature Sensor w/ WellPSPressure SensorFilterAir Flow StationDamperABC##Part Label Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYVFD and GroundingREVMDC19‐000150SCALENoneSHEET13 OF 14VFD and Grounding1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac Power24VAC 120VACWarning: Failure to properly connect Ground may damage controller. Ensure the Common 24VAC is Grounded.Common24VACRequired Single Transformer GroundingGeneral Notes:1. Refer to Distech Technical Documentation for specifications on Modules and wiring.2. Relays as required due to different operating voltages, power sources, or loads.3. Wiring is for reference only. This project may not include all that is represented.1. Alternate Wiring - 2 Conductor Cable - Tie Shield Wire to AGND: X1-31, No ground wire used. 2. Set switch J2 to OFF. BUS termination is an active network: Pull Up & Pull Down (BIAS) resistors are on board the ACH550 Drive! 3. Tie shield wires together at Drive AGND - Do Not terminate at SCR! Integration Device Provided by othersVFD by OthersBACnet LAN – MS/TPEthernet to MS/TP RouterBACnet LAN - Ethernet BACnet WorkstationVariable Speed Drive Installation Notes:Drive terminals 28…32 are for RS485 communications. Use Belden 9842 or equivalent. Belden 9842 is a dual twisted, shielded pair cable with a wave impedance of 120 Ω. Use one of these twisted shielded pairs for the RS485 link. Use this pair to connect all A (-) terminals together and all B (+) terminals together.Use one of the wires in the other pair for the logical ground (terminal 31), leaving one wire unused.Do not directly ground the RS485 network at any point. Ground all devices on the network using their corresponding earthing terminals.As always, the grounding wires should not form any closed loops, and all the devices should be earthed to a common ground.Connect the RS485 link in a daisy-chained bus, without dropout lines. 2627282930Each Ckt supplies 100VA1Sw/Breaker 12Sw/Breaker 23Sw/Breaker 14Sw/Breaker 25Sw/Breaker 2480277240120CommonCkt1 24VAC 100 VA to devicesCkt2 24VAC 100 VA to devicesCkt3 24VAC 100 VA to devicesCkt4 24VAC 100 VA to devicesCkt5 24VAC 100 VA to devicesRequired Multi Transformer Grounding Phone (800) 890‐2022Fax (860) 316‐5348Oxoboxo LoftsUncasville CTConnecticut Temperature Controls500 Corporate RowCromwell, CT 06416SIZEDRAWN BYWire SpecificationREVMDC19‐000150SCALENoneSHEET14 OF 14Wire Specification1/21/2020Page NameJob NumberRed Conductor = 24VacGreen Conductor = FeedbackWhite Color Conductor = SignalBlack Conductor = Com/NegTypical Conductor Signal WiringTypical Wiring Rules2. Yellow Cable = Analog Output3. Green Cable = Digital Input1. Blue Cable = Analog Input5. Purple 22awg = LonWorks Com6. Purple 24awg = Bacnet Com4. Orange Cable = Digital Output7. White Cable = 24 Vac PowerThe shield of the data bus must be connected to the electrical system ground at only one point‐ usually at one end of the bus as shownAdd a 120 Ohm resistor as shown hereLabel To and From on cableEclypse Connected System ControllersMaximum Wiring Distance for all I/O Points is 200 ftTypical BACnet System Communications Layout ‐ For Reference OnlyTypical Eclypse System Module For Reference OnlyTypical LONworks System Communications Layout ‐ For Reference OnlyCablePart Number Cable Type Manufacturer Typical Application1 0023240 18‐02 Shielded/Plenum Windy City Digital Output 2 wire (Orange)2 0023430 18‐04 Shielded/Plenum Windy City Analog Output 4 wire (Yellow)3 0023260 18‐02 Shielded/Plenum Windy City Digital Input 2 wire (Green)4 002369 18‐02 Unshielded/Plenum Windy City Analog Input 2 wire (Blue)5 002349 18‐04 Shielded/Plenum Windy City Analog Input 4 wire (Blue)6 105550 22‐1P Unshielded/Plenum Windy City Lonworks Comm (Purple)7 042005 24‐1P Shielded/Plenum Windy City BACNet MSTP Comm (Purple)8 5556150 24‐4P Unshielded/Plenum C5E Windy City Ethernet C5E (Purple)9 5566050 23‐4P Unshielded/Plenum C6 Windy City Ethernet C6 (Purple)10 002360 18‐02 Unshielded/Plenum Windy City 24VAC Power (White)11 001360 16‐02 Unshielded/Plenum Windy City 24VAC Power (White)12 007960 14‐02 Unshielded/NON‐Plenum Windy City 24VAC Power (White)13 441260BR 12‐02 Unshielded/NON‐Plenum Windy City 24VAC Power (White)ConnecticutTemperature Controls Cable Specification and AbbreviationsWindy City Wire ‐ Contact Marty Eck (800) 379‐119122 ga 20 ga 18 ga 16 ga 14 ga 12 ga 10 ga16.46 10.35 7.95 4.99 3.13 1.98 1.24AVA0.11 2.5 552 878 1144 1822 2895 4591 73310.21 5 289 460 599 954 1517 2405 38400.42 10 145 230 302 481 764 1212 19350.83 20 73 116 151 240 382 606 9681.25 30 49 77 101 160 255 404 6451.67 40 36 58 75 120 191 303 4842.08 50 29 46 60 96 153 242 3872.5 60 24 39 50 80 127 202 3232.92 70 21 33 43 69 109 173 2763.33 80 18 29 38 60 96 152 2423.75 90 16 26 34 53 85 135 2154 961524315080126202AWGohms/kFtMaximum One Way Distance to Load in Ft