HomeMy WebLinkAbout005 - Fire Hydrant - NETSUBMITTAL
COVER SHEET
PROJECT:
SUBMITTAL NO.:
GENERIC NAME:
TRANSMITTAL INFORMATION
FROM:
CONTRACTOR:
TO:
ENGINEER’S ACTION (See Stamp)
Submitted for review and approval
Resubmitted for review and approval
Substitution involved - Substitution request attached
SUBMITTAL REVIEW
This review is only for general conformance with the design concept of the Project and general compliance with the information given in the Contract Documents. Corrections or comments made on the submittal during this review do not relieve contractor from compliance with the requirements of the plans and specifications. Approval of a specific item shall not be deemed approval of an assembly of which the item is a component. Contractor is responsible for the dimensions to be confirmed and correlated at the job-site; information that pertains solely to the fabrication process of the means, methods, techniques, sequences, and procedures of construction; coordination of his or her work with that of all other trades; and performing all work in a safe and satisfactory manner.
BSC Companies, Inc.
Reviewed By:
No Exceptions Taken
Approved as Noted
Revise & Resubmit
RejectedFurnish as Corrected
No action required
Not subject to review
See attached comments ( page(s))
Remarks:
CC:
SUBMITTAL DATE:
DATE RECEIVED:
MAGGIORE CONSTRUCTION CORP.
13 Wheeling Avenue, Woburn, MA 01801 Phone 781.935.6100 FAX 781.933.8044
SUBMITTAL ACTION SHEET
Oxoboxo Lofts
40 Pink Row
Uncasville, CT
General Contractor:Architect:
Maggiore Construction Corp.Paul B Bailey Architects
13 Wheeling Ave.110 Audubon Street
Woburn, MA 01801 New Haven, CT 06510
Job No.: 1529 Job No.: 16-063
Prepared By:Maggiore Construction Corp.
Form of Submittal:
Samples Cut Sheets Schedule Shop Drawings Other
Description:Fire Hydrant, pipe and fittings
Mechanical Joints
Megalug
Field Lok 350 Red Gasket
Marking Tape
Tyton Joint Ductile Pipe
Gate Valves by Mueller
Valve Bvox
Manufacturer:Mueller, Tyler Union Products,Ebava Iron,
Omega Marking Co., Tyton,
Other/Notes:ADS is being submited as an alternate to RCP.
Received By MCC:12/30/2019 Received By Owner:
Reviewed:Comments:
Approved Approved as Noted
Rejected Revise and Re-submit
Compliance Equal Submitted For Approval
By: Gifford Perry - Senior Project Manager Approved By:
Date:12/31/2019 Date:
9.6
Rev. 4-14 Shaded area indicates changes
MUELLER® SUPER CENTURION®
FIRE HYDRANT
❏ Super Centurion 250™ catalog numbers
- UL 246, FM 1510 ANSI/AWWA C502 250 psi rated
A421 4-1/2" main valve opening 3-way (2 hose nozzle / 1 pumper nozzle)
A423 5-1/4" main valve opening 3-way (2 hose nozzle / 1 pumper nozzle)
A454 5-1/4" main valve opening 3-way (3 hose nozzle) *
A455 5-1/4" main valve opening 4-way (4 hose nozzle) *
A458 5-1/4" main valve opening 4-way (3 hose nozzle / 1 pumper nozzle) *
A459 5-1/4" main valve opening 4-way (2 hose nozzle / 1 pumper nozzle)** * Hose Gate Valves required on FM Approved Models
** A459 is UL Listed and ANSI/AWWA C502
❏ Super Centurion 350™ catalog number
- UL 246, FM 1510 ANSI/AWWA C502 350 psi rated
A423 5-1/4" main valve opening 3-way (2 hose nozzle / 1 pumper nozzle)
❏ Super Centurion 200™ catalog numbers
- UL 246, FM 1510 ANSI/AWWA C502 200 psi rated
A-433 4-1/2" main valve opening 2-way (2 hose nozzle) A-435 5-1/4" main valve opening 2-way (2 hose nozzle)
- ANSI/AWWA C502 200 psi rated A-420 4-1/2" main valve opening 2-way (2 hose nozzle) A-424 4-1/2" main valve opening 1-way (1 pumper nozzle) A-422 5-1/4" main valve opening 2-way (2 hose nozzle) A-425 5-1/4" main valve opening 2-way (2 hose nozzle) A-423 5-1/4" main valve opening 3-way (2 hose nozzle / 2 pumper nozzle)
❏ 10 year limited warranty on material and workmanship
❏ Meets all applicable parts of ANSI/AWWA C502 Standard
❏ Post type dry barrel design
❏ Dry top design with O-ring sealed oil reservoir
❏ Traffic feature with stainless steel safety stem coupling
❏ Compression-type main valve closes with pressure for positive seal; it is made of rubber and is conveniently reversible providing a spare for long service life
❏ Operating nut available in wide variety of shapes and sizes-open left or right
❏ Field replaceable hose and pumper nozzles
❏ Hose and pumper nozzles have large radius, full flow openings for low friction loss
❏ Contoured shoe is designed for full flow
❏ Dual bronze drain valves provide effective barrel drainage
❏ 350 psig (2400 kPa/24 barg) maximum working pressure, 700 psig (4800 kPa/48 barg) static test pressure; 250 psig (1725 kPa/17 barg) maximum working pressure, 500 psig (3450 kPa/35 barg) static test pressure; 200 psig (1400 kPa/14 barg) maximum working pressure, 400 psig (2800 kPa/28 barg) static test pressure
Dimensions Non-rotating bolt design: cast-in pads eliminate need
for anti-rotation bolts.
Front view detail of Mechanical joint (Standard only)
Vertical Flange
ASME B16.1 Class 125
PN 10/16 Drilling
Mechanical joint standard and D-150