REQUEST FOR INFORMATION NO. 54
PROJECT:OXOBOXO LOFTS RFI #54
INITIATION DATE:03/02/20
FROM:Maggiore Construction Corporation DATE NEEDED:03/09/20
13 Wheeling Avenue
Woburn, MA 01801
REQUESTED BY:Gifford Perry
EMAIL: gifford@maggiorecos.com
TO:Paul B. Bailey Architect
110 Audubon Street
New Haven, CT 06510
ATTENTION:Susan Odell- email: susan@pbbarchitect.com
Frank Brachanow-Email Fbrachanow@dakotaPartners.net
Sam Kirby
SUBJECT:
REQUEST:Sketch MSK ABC-MD1.SBR2 added an exhaust fan
for the newly created cavity behind the drywall and exterior
foundation wall.
Exhaust Fan EF-3 is listed, but identified what it is, no
specification is provided
Answered By:
Company:Date:
Building C - added exhaust fan
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
D/E/F Services Group, LTD
1171 Voluntown Road
Griswold, CT 06351
Phone: (860) 376-4896
Fax: (860) 376-1213
Request for Information
RFI #: 004
To: Gifford Perry Fax: (781) 933-8044
From: Jennifer Daniels Date: 03/02/2020
Project: F29166 Pages: 2
CC: Jason Neri Return by: 03/16/2020
Urgent For Review Please Comment Please Reply Please Recycle
In regards to sketch MSK ABC-MD1.SBR2, dated 02/21/2020, located Bldg. C, Level 1.
Note on the new sketch says Exhaust fan with 4” each discharge to weather proof wall cap for
cavity space ventilation mount exhaust intake maximum 12" below top of cavity. Provide access
door as shown for service and maintenance. Coordinate with architectural. This exhaust fan is
tagged EF-3.
Can you give us more information on this exhaust fan?
(CFM, static pressure?)
WA
L2.2
L2.A
L2.B
L2.C
L2.D
L2.E
L2.F
L2.H
L2.J
L2.K
L2.M
L2.N
L2.1
L2.L
4.5
UNIT C-1(2 BEDROOM)
UNIT C-2
(2 BEDROOM)
STAIR 2
ELECTRICALMETERROOM
MAINTENANCE
ROOM
BUILDING B
BUILDING C
BUILDING A
(ABOVE)
BUILDING D
BUILDING G
T HP2
T
HP2
EF-1
EWH-1
EF-1
EF-1
EF-1
DOMESTIC HOT WATER BOILER
6" FLUE VENT AND 8" COMBUSTION AIRINTAKE
AXG
AXG
AXG
B-1
6" FLUE EXHAUST AND 8"COMBUSTION AIR INTAKE TOWALL TERMINAL KIT. SIZE,ROUTING, LOCATION ANDINSTALLATION AS PERMANUFACTURER'SRECOMMENDATIONS (TYPICAL)
8"ø 4"ø12X6" AIR TRANSFERGRILLE ASSEMBLY(AXG). PROVIDE 12"X3"TRANSFER DUCT INWALL WITH HIGHINLET GRILLE ANDLOW OUTLET GRILLE(TYPICAL FOR ALL)
C-250 B-150
C-250 B-150
8"x8"
HP2
R7-800
AXG
B-150
HP2
B-150C-250
10"x10"
C-250 10"x8"
R7-800
EUH-1
T
EUH-1
6"ø
8"ø
EXHAUST FAN WITH 4" EA DISCHARGETO WEATHER PROOF WALL CAP FORCAVITY SPACE VENTILATION. MOUNTEXHAUST INTAKE MAXIMUM 12" BELOWTOP OF CAVITY. PROVIDE ACCESS DOORAS SHOWN FOR SERVICEAND MAINTENANCE,COORDINATE WITH ARCHITECTURAL
EF-3
4"ø
4"ø
4" OA DUCT FROM WEATHERPROOFINTAKE CAP FOR CAVITY SPACEVENTILATION. MOUNT INTAKE OPENINGAT MAXIMUM 12" ABOVE BOTTOM OFCAVITY
A/D
4" EA UP IN DUCTCHASE ABOVE(TYPICAL FOR 4)
4"ø
4"ø 4"ø
10
Scale
Date
Drawn By
Checked By
Project Number
UNCASVILLE, CT
1/8" = 1'-0"
ABC-MD1.SB
MECHANICALDUCTWORK PLAN
BLDG 'B'-LEVEL SB
BLDG 'C'-LEVEL 1
Dakota
Partners, Inc.
OXOBOXO
LOFTS
DA
RS
11/01/2017
16-063
A B
D E
C F
G H
J
K
L M
NORTH
SITE KEY PLAN
No.Description Date
8 Addendum 8 11/5/19
9
10 MSKABC-MD1.SBR2 02/21/20
MSK ABC-MD1.SBR2
MAX
PUMP TYPES: DS=DOUBLE SUCTION, HS=HORIZONTALMSPLIT, ES=BASE MOUNTED CENTRIFUGAL BASE SUCTION, IL=IN LINE
SCHEDULE OF PUMPS
MANUFACTURER/MODEL NUMBER RPM
NUMBER LOCATION PUMPTYPE
P1 MECHANICALROOM B&G E-1510 2.5AC
FLUID
WATER
GPM
415
HEAD(FT)
150 20 3550
HP VOLT
208
PH
3
REMARKS
SOURCE WATER PUMP, LEAD LAG
MOTOR DATA
P2 MECHANICAL
ROOM WATER 415 150
NOTES:1.PROVIDE FACTORY MOUNTED CIRCUIT TRANSFORMER FOR
STEPPING DOWN LINE VOLTAGE TO CONTROL VOTAGE
HOT WATER BOILERS-BURNERS SCHEDULE
B-1
NUMBER
MECHANICAL
LOCATION
DR1000
MODEL NUMBER REMARKS
BOILER DATA
TYPE
CONDENSING
BURNER DATA
TYPE
MODULATING
INPUT(MBH)
1,000GAS
FUEL
ROOM
SCHEDULE OF EXPANSION TANKS
SYMBOL LOCATION SYSTEM MODEL NO.GPMVOL
GAL REMARKSMANUFACTURER/TANK SYSTEMCONNECTION
AIR SEPARATOR AS1
MANUFACTURER/
MODEL NO.
AIRVENT
ET-1 MECHANICAL
ROOM AMTROL AX-60V 415
∅VOLT
(5 TO 1)CAMUS
MANUFACTURER
940
GROSS
OUTPUT
(MBH)
N/A
BOILERH.P.
H.P.
MOTOR
CONTROL
∅VOLT
SOURCE WATER 33.6 11.5 1/2"5-ADS
B&G E1510 2.5AC
ES
ES 3208
SCHEDULE OF CHEMICAL FEED SYSTEMS
MANUFACTURER MODEL NUMBER REMARKSNUMBER
CF-1 BOILER ROOM
LOCATION
SOURCE WATERSYSTEM
SERVING
VERTICAL
TANK DATA
55 GALLONS 120
ELECTRICAL DATA
TYPE CAPACITY V
POLYETHYLENE
MATERIAL
1
PH
60
HZ
1/3
HP
PROVIDE LOW LEVEL PUMP CUT-OFF, LOW LEVEL ALARM,REMOTE MONITORING CONTACTWATER TREATMENT
APPLICATION
JOHN WOOD JWGP-53-055
20 3550
P3 MECHANICALROOM WATER 160 15B&G e-80 3X3X7C IL 320811150
P4 MECHANICALROOM WATER 160 15B&G e-80 3X3X7C IL 320811150
P5 MECHANICALROOM WATER 420 40B&G e-80 5X5X7B IL 32087.5 1770
P6 MECHANICAL
ROOM WATER 420 40B&G e-80 5X5X7B IL 32087.5 1770
SOURCE WATER PUMP, LEAD LAG
BOILER PUMP
BOILER PUMP
COOLING TOWER PUMP, LEAD LAG
COOLING TOWER PUMP, LEAD LAG
COOLING HEAT REJECTION WILL BE MET BY THE ABOVE SELECTIONS.
NOTE: COOLING TOWER SELECTIONS BASED ON WATERSIDE ECONOMIZER OPERATION. MECHANICAL
VOLT PHWBDB
TEMP FAN (HIGH SPEED)
HPIN.CFM
TOTAL
(FT. HD)
PD
MAX ESPTEMP
OUTIN
GPM
CONDENSER WATER DATA AIR DATA
SCHEDULE OF COOLING TOWERS
CAP.LOCATIONMANUFACTURER/SYMBOL FAN (LOW SPEED)
HP VOLT PHTONSMODEL NUMBER REMARKS
CT-1 BAC XES15E-1212-07EN/W BLDG F ROOF 167 420 95 85 -40,230 N/A 91 73 3 208 3 3 208 3
PROVIDE COMBINATION COMBUSTION AIR INTAKEAND FLUE EXHAUST TO CONCENTRICWALL TERMINAL KIT
TYPE MODEL NUMBER
SCHEDULE OF HEAT EXCHANGERS
SYMBOL MANUFACTURER/SERVEDLOCATIONEQUIPMENT FLUID
CHILLED FLUID SIDEHEATED FLUID SIDE
GPMCAPACITY
MBH FLUID TEMP
OUTIN OUT
GPM
IN
TEMP REMARKSPD
FT
HX-1 MECHANICALROOM PLATE &FRAME CT-1 ALFA LAVAL AQ6-FG 2,100 WATER 420 83 93 WATER 420 96 86 4.82 VIBRATION ISOLATION MOUNTING
REMARKSSYMBOLSAMANUFACTURER /
MODEL NUMBER
WATER-TO-AIR HEAT PUMP SCHEDULE
AREA SERVEDLOCATION
HP1 MECHANICAL ENCLOSURE APARTMENTS WHELAN/VP-0604-B 600 -
(CFM)
OA
*1
(CFM)EFT
HEATING
CAPEATLAT
65 99 21910 68
(°F)BTUH(FWB)(FWB)HOA(Mbtuh)LFT(°F)COP
77 18120 4.8
EFT
COOLING
CAPEATLAT
76.6/64 56/55 17730 86
(°F)BTUH(DB/WB)(DB/WB)HOR(Mbtuh)LFT(°F)EER
96 22510 13.3
FLUID
4.2
(GPM)
FLUID
9.2
(FT H2O)
FLOW RATE PD ELECTRICAL
MCA
12.9
MAX CB(AMPS)
20
PH
1
V
208
HP2 APARTMENTS 800 *1 -65 99 29700 22,900 4.8 76.6/64 56/55 24000 86 96 29600 13.3 5.6 9.2 18 30 1 208
APARTMENTS J-5 & 6 1000 -35700 28400 4.8 28200 35600 7.0 19.2 30HP3
HP4
HP5
BLDG B ATTIC BLDG B CORRIDORS 1200 -47600 37300 4.8 37700 45650 8.4 21.23 35
BLDG A CRAWL SPACE 400 -18500 14800 4.8 14100 17900 3.5 10.58 15
REMARKSPHNUMBERSERVICEMANUFACTURER /
MODEL NUMBER FAN TYPE
SCHEDULE OF FANS
CFMDAMPER
TYPE DRIVEFAN
RPM(IN W.G.)
EXT. S.P.MOTOR DATA
VOLTHP/W RPMCONTROLAREA SERVEDLOCATION
EF-1 DWELLING UNITS KITCHENS AND BATHROOMS GREENHECK/SP-B110 EXHAUST CE WALL SWITCH 100 0.375 950 DIRECT 80W 950 120 1 COORDINATE LOCATION AND INSTALLATION WITH ARCHITECTS RCP
120 3 24 1
PROVIDE WITH STARTER, DISCONNECT SWITCH,
VIBRATION ISOLATION MOUNTING
68 77
68 77
68 77
68 77
68 77
68 77
86 96
86 96
86 96
86 96
86 96
13.3
13.3
13.3
13.3
13.3
9.2
9.2
5.2
9.2
9.4
1 208
1 208
1 208
1 208
1 208
HP6 APT K-2 LAV APARTMENT K-2
HP7 BLDG E MECH ROOM BLDG E OFFICE & FITNESS
HP9 BLDG F
HP8 BLDG H MECH ROOM BLDG G,H,J,K,M CORRIDOR
600 21910
800 26600
1000 200 35700
65 99
65 99
65 99
65 99
65 99
65 99 68 77
4.8
4.8
4.8
76.6/64 56/55
76.6/64 56/55
76.6/64 56/55
76.6/64 56/55
76.6/64 56/55
76.6/64 56/55
18120
22900
28400
17730
23300
28200
22510
29400
35600
4.2
5.6
7.0
12.9 20
18 30
19.2 30 1 208
*1
*1
*1
*1
*1
86 96 13.3 9.2
MECHANICAL ENCLOSURE
MECHANICAL ENCLOSURE
WHELAN/VP-0804-B
WHELAN/VP-1004-B
WHELAN/CASH-036AB
WHELAN/CASH-012AB
WHELAN/CASH-018AB
WHELAN/CASH-024AB
WHELAN/CASH-030AB
BLDG A CORRIDORS
NOTES:1. *1= OUTSIDE (VENTILATION) AIR PROVIDED BY OPERABLE WINDOWS UNLESS OTHERWISE NOTED. WHERE HARD DUCT OA CONNECTIONS ARE SHOWN COORDINATE INSTALLATION WITH MANUFACTURER (TYPICAL)
2. CONTRACTOR SHALL COORDINATE ALL HEAT PUMP MOUNTING HEIGHTS, SUPPLY & RETURN PLENUMS, ENCLOSURES, DUCT TAKEOFFS AND ELEVATIONS, DIFFUSER AND GRILLE MOUNTING AND LOCATIONS, ETC. WITH ARCHITECTURAL, STRUCTURAL AND ALL WORK OF OTHER TRADES PRIOR TO INSTALLATION (TYPICAL)
3. PROVIDE CONDENSATE PUMPS FOR ALL HEAT PUMP UNITS AS REQUIRED. VERIFY LOCATIONS, QUANTITIES, PIPE ROUTING, INDIRECT DRAIN CONNECTIONS, ETC. WITH UNIT LAYOUTS AND MANUFACTURER RECOMMENDATIONS PRIOR TO ORDERING AND INSTALLATION (TYPICAL)
1000 200 357006599 68 77 4.8 76.6/64 56/5528400 28200 35600 7.0 19.2 30 1 208869613.3 9.2WHELAN/CASH-030ABBLDG F
CF-2 BOILER ROOM COOLING TOWERLOOP VERTICAL 55 GALLONS 120POLYETHYLENE 1 60 1/3 PROVIDE LOW LEVEL PUMP CUT-OFF, LOW LEVEL ALARM,REMOTE MONITORING CONTACTWATER TREATMENTJOHN WOOD JWGP-53-055
VOLUME
(GALLONS)
ACCEPTANCE
FAN TYPES: CRCE=CENTRIFUGAL ROOF CURB MOUNTED EXHAUSTER
PRCE=PROPELLER ROOF CURB MOUNTED EXHAUSTER
PRCS=PROPELLER ROOF CURB MOUNTED SUPPLY FAN
CFC=CENTRIFUGAL FORWARD CURVED
CE=CEILING MOUNTED EXHAUSTER
CRCU=CENTRIFUGAL ROOF CURB UPBLAST
CAF=CENTRIFUGAL AIR FOIL CBI=CENTRIFUGAL BACKWARD INCLINED VA=VANE AXIAL
EF-2 BUILDING H METER ROOM GREENHECK/SP-B110 EXHAUST CE REVERSE-ACTING THERMOSTAT GRAVITYBACK DRAFT
GRAVITYBACK DRAFT
9501000.375 DIRECT 80W 950 120 1
EF-3 BLDG C-LEVEL ONE WATERPROOF CAVITY GREENHECK/CSP-A110 EXHAUST INLINE CONTINUOUS OPERATION -100 0.250 950 DIRECT 51W 950 120 1 CONNECT TO CIRCUIT FED FROM PANEL ON EMERGENCY GENERATOR, PROVIDE VIBRATION MOUNTING ANDACCESS DOOR FOR SERVICE
Scale
Date
Drawn By
Checked By
Project Number
UNCASVILLE, CT
1/8" = 1'-0"
M2.1
MECHANICALSCHEDULES
Dakota
Partners, Inc.
OXOBOXO
LOFTS
Checker
Author
11/01/2017
16-063
No.Description Date
8 Addendum 8 11/5/19
9 02/14/20MSK M2.1R1
MSK M2.1R1
9