REQUEST FOR INFORMATION NO. 52
PROJECT:OXOBOXO LOFTS RFI #52
INITIATION DATE:02/28/20
FROM:Maggiore Construction Corporation DATE NEEDED:03/03/20
13 Wheeling Avenue
Woburn, MA 01801
REQUESTED BY:Gifford Perry
EMAIL: gifford@maggiorecos.com
TO:Paul B. Bailey Architect
110 Audubon Street
New Haven, CT 06510
ATTENTION:Susan Odell- email: susan@pbbarchitect.com
Frank Brachanow-Email Fbrachanow@dakotaPartners.net
Sam Kirby
SUBJECT:
REQUEST:Per the building inspector he says outlets are required by behind
the entry door.
Please advise if this is required by code.
Answer: Drawings were sent to the Building Official to show Foyers and Corridors in all units, which
have different outlet requirements than living spaces. Foyers under 60 s.f. do not need outlets. Foyers
larger than 60 s.f. need 1 outlet every 3 feet of linear wall, excluding openings.
Corridors less than 10 feet in length do not need outlets. Corridors greater than 10 feet in length are
required to have 1 outlet.
The drawings sent to the Building Official included Bldgs A, B, C, D, E, G, H, J and K residential units
Buildings L and F were not sent because they do not have residential units.
Bldg M was not sent because the requested outlets have already been installed.
As a result of the study of foyers & corridors, 1 outlet was found to be needed in the corridor of Unit A-1.
See attached.
Answered By:
Company: Date:5/20/2020
Building Inspector wants more outlets
Susan Odell
Paul B. Bailey Architect