HomeMy WebLinkAboutRFI 037 -Sprinkler calculation without crawl spaces ANSWEREDDistribution to:
OWNER X
ARCHITECT X
ENGINEER
13 Wheeling Ave
Woburn, MA 01801781-935-6100
REQUEST FOR INFORMATION NO. 37
PROJECT:OXOBOXO LOFTS RFI #37
INITIATION DATE:01/02/20
FROM:Maggiore Construction Corporation DATE NEEDED:01/07/20
13 Wheeling Avenue
Woburn, MA 01801
REQUESTED BY:Gifford Perry
EMAIL: gifford@maggiorecos.com
TO:Paul B. Bailey Architect
110 Audubon Street
New Haven, CT 06510
ATTENTION:Susan Odell- email: susan@pbbarchitect.com
Frank Brachanow-Email Fbrachanow@dakotaPartners.net
Sam Kirby
SUBJECT:
REQUEST: Synergy Fire needs more clarity on the underside of the raised platforms that, per the FM, are not needed.
NFPA 13 that require a 3000 SF design area penalty for buildings having unsprinklered
combustible concealed spaces which could drastically affect the overhead pipe cost and sizing for th
Please have the F.M. and engineers confirm that the 3000 sq. ft penalty is also being waived.
Unfortunately there are many pieces to this puzzle. Fire safety codes have a lot of avenues to go down and l
Also I know you sent us some new information about the bathroom walls now extending up to the roof deck a
Can you please confirm in writing that the kitchen/living room/bed room walls do not extend up to the roof de
Is it really their intention to have them open between the bed rooms and the other rooms of the apartments?
The walls and beams all have an effect on the allowable sprinkler head spacing and the acceptable head loc
so it's critical that we know exactly which walls extend up to the roof deck and which ones will not.
All the CAD files we are working with show all of the walls including closet walls sheet rocked and extending
Answered By:
Company: Date:
Sprinkler calculation without crawl spaces being sprinklered