Loading...
HomeMy WebLinkAbout2019-08-16 Oxoboxo Lofts - Addendum 7 - additional items  Information contained in this document is proprietary and confidential and may not be disseminated to any party other than the intended recipient without the written consent of Paul B. Bailey Architect, LLC.   ADDENDUM 7 appended  Issue Date: August 16, 2019  Oxoboxo Lofts  42 Pink Row, Uncasville, CT  General Information:    This Addendum shall become a part of the Contract and the Contractor shall be bound thereby.   Changes to the Drawings and Specifications Following the Final Construction Documents dated  10/12/2018.     This appends Addendum 7 with the missing items:  1. ComCheck.  2. Smoke detector locations.  This Addendum includes the following RFI, drawings and specs:    1. Res/ComCheck forms  2. Architectural drawing sheets:  A‐A1.11 BUILDING A – REFLECTED CEILING PLANS  B‐A1.12 BUILDING B – REFLECTED CEILING PLANS  B‐A1.13 BUILDING B – REFLECTED CEILING PLANS  B‐A1.14 BUILDING B – REFLECTED CEILING PLANS  B‐A1.15 BUILDING B – REFLECTED CEILING PLANS  B‐A1.16 BUILDING B – REFLECTED CEILING PLANS  C‐A1.11 BUILDING C – REFLECTED CEILING PLANS  D‐A1.11 BUILDING D – REFLECTED CEILING PLANS  E‐A1.11 BUILDING E – REFLECTED CEILING PLANS  G‐A1.11 BUILDING G – REFLECTED CEILING PLANS  G‐A1.12 BUILDING G – REFLECTED CEILING PLANS  HJ‐A1.11 BUILDING H – REFLECTED CEILING PLANS  HJ‐A1.12 BUILDING J – REFLECTED CEILING PLANS  HJ‐A1.13 BUILDING J – REFLECTED CEILING PLANS  K‐A1.11 BUILDING A – REFLECTED CEILING PLANS  M‐A1.11 BUILDING A – REFLECTED CEILING PLANS  M‐A1.12 BUILDING A – REFLECTED CEILING PLANS  M‐A1.13 BUILDING A – REFLECTED CEILING PLANS    END OF ADDENDUM 7 appended  P A U L B. B A I L E Y • A R C H I T E C T • LLC 1 1 0 A U D U B O N S T R E E T N E W H A V E N , C O N N E C T I C U T 0 6 5 1 0 P H: 2 0 3 7 7 6 8 8 8 8 F A X: 2 0 3 7 7 2 1 3 6 5 August 16, 2019 Vernon D. Vesey II, Building Official Town of Montville Building Department 310 Norwich-New London Turnpike Uncasville, CT 06382 Dear Vern, This letter addresses the areas of the Oxoboxo Lofts project at 42 Pink Row, Uncasville, that fail the ResCheck or ComCheck. Per IECC Section C501.6 Historic Buildings – “No provisions of this code relating to the construction, repair, alteration, restoration and movement of structures, and change of occupancy shall be mandatory for historic buildings provided a report has been submitted to the code official and signed by a registered design professional…demonstrating that compliance with that provisions would threaten, degrade or destroy the historic form, fabric or function of the building.” This letter serves as the report described above. The building envelopes of all buildings in the Oxoboxo Lofts project fail to meet IECC standards due to the fact that the Secretary of the Interior’s Standards for Rehabilitating Historic Buildings state “A property will be…given a new use that requires minimal change to its distinctive materials, features, spaces and spatial relationships.” The State Historic Preservation Office (SHPO) and the National Park Service (NPS) interpret this to mean that an interior face of an exterior wall shall have the same level of finish that it had in the original use. The original use of this property is factory, and as such the interior faces of the exterior walls never had a finished (i.e. plaster) surface – the 3-wythe brick exterior walls remained exposed brick on the interior sides. Further, the existing slab-on-grade floors are expected by the SHPO and NPS to remain, and therefore there is no opportunity to replace them & install insulation under the slab. The roofs of factory buildings traditionally did not have insulation which gave them a very thin profile, and the SHPO and NPS expect this thin profile to remain. There are a handful of original windows that remain, and the SHPO and NPS expect them to be repaired or replaced in kind – single pane wood framed windows. For the windows that have already been replaced, we are allowed to install double pane windows, but this energy savings measure by itself is not enough to overcome the above stated deficiencies. Sincerely, Susan B. Odell, AIA, CPHC® Senior Project Architect, Paul B. Bailey Architect, LLC REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building A Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Fails using prescriptive requirements for alteration projects Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling Exemption: Framing cavity filled with insulation --------------- Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 1,750 0.333 478 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 273 0.270 74 Door 1: Solid Orientation: Unspecified 43 0.500 22 Wall 2: Solid Concrete or Masonry:No Insulation Orientation: Right side 1,178 0.333 348 Window 2: Wood Frame:Double Pane with Low-E Orientation: Unspecified 84 0.270 23 Door 2: Solid Orientation: Unspecified 48 0.500 24 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 1,850 0.333 504 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 336 0.270 91 Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 206 0.0 1.042 215 Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 1 of 2 08/16/19Report date: Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 2 of 2 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 0.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.50Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 1 of 8 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 2 of 8 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 3 of 8 08/16/19Report date: Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 4 of 8 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 5 of 8 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 6 of 8 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 7 of 8 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building A Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg A ResCheck.rck Page 8 of 8 08/16/19Report date: REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building AB Connector Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Average fenestration U-factor exceeds maximum Maximum UA:86 Your UA:113 Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Flat Ceiling or Scissor Truss Exemption: Framing cavity filled with insulation --------------- Wall 1: Steel Frame, 16" o.c. Orientation: Front Exemption: Framing cavity filled with insulation --------------- Wall 3: Steel Frame, 16" o.c. Orientation: Back Exemption: Framing cavity filled with insulation --------------- Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 27 0.270 7 Door 1: Solid Orientation: Unspecified 21 0.500 11 Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 91 0.0 1.042 95 Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 1 of 9 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 2 of 9 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 3 of 9 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 4 of 9 08/16/19Report date: Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 5 of 9 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 6 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 7 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 8 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building AB Connector Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg AB Connector ResCheck.rck Page 9 of 9 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 0.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.50Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments COMcheck Software Version 4.1.1.0 Envelope Compliance Certificate Project Title: 2015 IECC Project Type:Alteration Vertical Glazing / Wall Area:12% Location:New London, Connecticut Climate Zone:5a Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Project Information Energy Code: Oxoboxo Lofts Building B Building Area Floor Area 1-Total Gross SF (Multifamily) : Residential 27908 Envelope Assemblies R-Value Post-Alteration Assembly Cavity Cont.U-Factor Proposed SHGC Max. Allowed U-Factor SHGC Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Total Gross SF], Exemption: Framing cavity filled with insulation. ------------------ Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Total Gross SF]------1.000 ---0.540 --- NORTH Exterior Wall 1: Other Mass Wall, Heat capacity 1.0, [Bldg. Use 1 - Total Gross SF], Exemption: Framing cavity not exposed. (a) ------------------ Window 1: Wood Frame:Operable, Other, Operable, Operable, [Bldg. Use 1 - Total Gross SF] ------0.270 0.180 0.450 0.531 Door 1: Wood, Swinging, [Bldg. Use 1 - Total Gross SF]------0.500 ---0.370 --- EAST Exterior Wall 2: Other Mass Wall, Heat capacity 1.0, [Bldg. Use 1 - Total Gross SF], Exemption: Framing cavity not exposed. (a) ------------------ Window 2: Wood Frame:Operable, Other, Operable, Operable, [Bldg. Use 1 - Total Gross SF] ------0.270 0.180 0.450 0.400 Door 3: Wood, Swinging, [Bldg. Use 1 - Total Gross SF]------0.500 ---0.370 --- Door 4: Wood, Swinging, [Bldg. Use 1 - Total Gross SF]------0.500 ---0.370 --- SOUTH Exterior Wall 3: Other Mass Wall, Heat capacity 1.0, [Bldg. Use 1 - Total Gross SF], Exemption: Framing cavity not exposed. (a) ------------------ Window 3: Wood Frame:Operable, Other, Operable, Operable, [Bldg. Use 1 - Total Gross SF] ------0.270 0.180 0.450 0.400 WEST Exterior Wall 4: Other Mass Wall, Heat capacity 1.0, [Bldg. Use 1 - Total Gross SF], Exemption: Framing cavity not exposed. (a) ------------------ Window 4: Wood Frame:Operable, Other, Operable, Operable,------0.270 0.180 0.450 0.400 Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 191 ofPage R-Value Post-Alteration Assembly Cavity Cont.U-Factor Proposed SHGC Max. Allowed U-Factor SHGC [Bldg. Use 1 - Total Gross SF] Door 2: Wood, Swinging, [Bldg. Use 1 - Total Gross SF]------0.500 ---0.370 --- (a)'Other' components require supporting documentation for proposed U-factors. (b)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation. (c)Slab-On-Grade proposed and budget U-factors shown in table are F-factors. Envelope FAILS Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 192 ofPage COMcheck Software Version 4.1.1.0 Interior Lighting Compliance Certificate Project Title: 2015 IECC Project Type:Alteration Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Project Information Energy Code: Oxoboxo Lofts Building B Allowed Interior Lighting Power A Area Category B Floor Area (ft2) C Allowed Watts / ft2 D Allowed Watts (B X C) 1-Total Gross SF (Multifamily)27908 0.51 14233 14233Total Allowed Watts = Proposed Interior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures Total Gross SF ( Multifamily 27908 sq.ft.) LED 1: LED A Lamp 8W:3 99 24 2376 Compact Fluorescent 1: Circline 32W: Electronic:1 34 32 1088 LED 2: LED Linear 17W:1 77 17 1309 LED 3: LED Other Fixture Unit 25W:1 16 25 400 LED 4: LED MR 2W:2 3 4 12 LED 5: LED MR 2W:2 8 4 32 LED 6: LED MR 2W:2 21 4 84 5301Total Proposed Watts = Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Interior Lighting PASSES Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 193 ofPage COMcheck Software Version 4.1.1.0 Exterior Lighting Compliance Certificate Project Title: 2015 IECC Project Type:Alteration Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Project Information Energy Code: Oxoboxo Lofts Building B 2 (Residentially zoned area)Exterior Lighting Zone Allowed Exterior Lighting Power A Area/Surface Category B Quantity C Allowed Watts / Unit D Tradable Wattage E Allowed Watts (B X C) Main entry 1 ft of door 20 Yes 20 Other door (not main entry)2 ft of door 20 Yes 40 Total Tradable Watts (a) = Total Allowed Watts = Total Allowed Supplemental Watts (b) = 60 60 600 (a) Wattage tradeoffs are only allowed between tradable areas/surfaces. (b) A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces. Proposed Exterior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixtures Main entry (1 ft of door width): Tradable Wattage LED 1: LED A Lamp 8W:2 1 16 16 Other door (not main entry) (2 ft of door width): Tradable Wattage LED 2: LED A Lamp 8W:2 2 16 32 48Total Tradable Proposed Watts = Exterior Lighting Compliance Statement Compliance Statement: The proposed exterior lighting alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Exterior Lighting PASSES Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 194 ofPage COMcheck Software Version 4.1.1.0 Mechanical Compliance Certificate Project Title: 2015 IECC Project Type:Alteration Location:New London, Connecticut Climate Zone:5a Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Project Information Energy Code: Oxoboxo Lofts Building B Mechanical Systems List Quantity System Type & Description Water Source Heat Pump Heating Mode: Capacity = 22 kBtu/h, Proposed Efficiency = 4.80 COP, Required Efficiency = 4.30 COP Cooling Mode: Capacity = 18 kBtu/h, Proposed Efficiency = 13.30 EER, Required Efficiency: 13.00 EER Fan System: None 22 HVAC System 1 (Single Zone): Gas Instantaneous Water Heater, Capacity: 100 gallons, Input Rating: 600 kBtu/h w/ Circulation Pump Proposed Efficiency: 95.10 % Et, Required Efficiency: 80.00 % Et 1 Water Heater 1: Mechanical Compliance Statement Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 195 ofPage Inspection Checklist Requirements: 2.0% were addressed directly in the COMcheck software COMcheck Software Version 4.1.1.0 Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Plan Review Complies?Comments/Assumptions C103.2 [PR1]1 Plans and/or specifications provide all information with which compliance can be determined for the building envelope and document where exceptions to the standard are claimed. Complies Does Not Not Observable Not Applicable C103.2 [PR2]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the mechanical systems and equipment and document where exceptions to the standard are claimed. Load calculations per acceptable engineering standards and handbooks. Complies Does Not Not Observable Not Applicable C103.2 [PR3]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the service water heating systems and equipment and document where exceptions to the standard are claimed. Hot water system sized per manufacturer's sizing guide. Complies Does Not Not Observable Not Applicable C103.2 [PR4]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the interior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Complies Does Not Not Observable Not Applicable C103.2 [PR8]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the exterior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Complies Does Not Not Observable Not Applicable C402.4.1 [PR10]1 The vertical fenestration area <= 30 percent of the gross above-grade wall area. Complies Does Not Not Observable Not Applicable 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 196 ofPage Section # & Req.ID Plan Review Complies?Comments/Assumptions C402.4.1 [PR11]1 The skylight area <= 3 percent of the gross roof area. Complies Does Not Not Observable Not Applicable C402.4.2 [PR14]1 In enclosed spaces > 2,500 ft2 directly under a roof with ceiling heights >15 ft. and used as an office, lobby, atrium, concourse, corridor, storage, gymnasium/exercise center, convention center, automotive service, manufacturing, non- refrigerated warehouse, retail store, distribution/sorting area, transportation, or workshop, the following requirements apply: (a) the daylight zone under skylights is >= half the floor area; (b) the skylight area to daylight zone is >= 3 percent with a skylight VT >= 0.40; or a minimum skylight effective aperture >= 1 percent. Complies Does Not Not Observable Not Applicable C405.6 [PR16]1 Group R-2 dwelling units have separate electrical meters. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 197 ofPage Section # & Req.ID Footing / Foundation Inspection Complies?Comments/Assumptions C303.2 [FO4]2 Slab edge insulation installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable C303.2.1 [FO6]1 Exterior insulation protected against damage, sunlight, moisture, wind, landscaping and equipment maintenance activities. Complies Does Not Not Observable Not Applicable C402.2.5 [FO3]2 Slab edge insulation R-value.Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.2.6 [FO12]3 Radiant heating systems panels insulated to >=R-3.5 on face opposite space being heated. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. See the Envelope Assemblies table for values. C403.2.4. 5, C403.2.4. 6 [FO9]3 Snow/ice melting system sensors for future connection to controls. Freeze protection systems have automatic controls installed. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 198 ofPage Section # & Req.ID Framing / Rough-In Inspection Complies?Comments/Assumptions C303.1.3 [FR12]2 Fenestration products rated in accordance with NFRC. Complies Does Not Not Observable Not Applicable C303.1.3 [FR13]1 Fenestration products are certified as to performance labels or certificates provided. Complies Does Not Not Observable Not Applicable C402.4.3 [FR10]1 Vertical fenestration SHGC value.Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.4.3, C402.4.3. 4 [FR8]1 Vertical fenestration U-Factor.Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.4.4 [FR14]2 U-factor of opaque doors associated with the building thermal envelope meets requirements. Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.5.1 [FR16]1 The building envelope contains a continuous air barrier that is sealed in an approved manner and either constructed or tested in an approved manner. Air barrier penetrations are sealed in an approved manner. Complies Does Not Not Observable Not Applicable C402.5.2, C402.5.4 [FR18]3 Factory-built fenestration and doors are labeled as meeting air leakage requirements. Complies Does Not Not Observable Not Applicable C402.5.7 [FR17]3 Vestibules are installed on all building entrances. Doors have self-closing devices. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 199 ofPage Section # & Req.ID Plumbing Rough-In Inspection Complies?Comments/Assumptions C404.5, C404.5.1, C404.5.2 [PL6]3 Heated water supply piping conforms to pipe length and volume requirements. Refer to section details. Complies Does Not Not Observable Not Applicable C404.5, C404.5.1, C404.5.2 [PL6]3 Heated water supply piping conforms to pipe length and volume requirements. Refer to section details. Complies Does Not Not Observable Not Applicable C404.6.1, C404.6.2 [PL3]1 Automatic time switches installed to automatically switch off the recirculating hot-water system or heat trace. Complies Does Not Not Observable Not Applicable C404.6.3 [PL7]3 Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after end of heating cycle. Complies Does Not Not Observable Not Applicable C404.6.3 [PL7]3 Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after end of heating cycle. Complies Does Not Not Observable Not Applicable C404.7 [PL8]3 Water distribution system that pumps water from a heated-water supply pipe back to the heated-water source through a cold-water supply pipe is a demand recirculation water system. Pumps within this system have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F. Complies Does Not Not Observable Not Applicable C404.7 [PL8]3 Water distribution system that pumps water from a heated-water supply pipe back to the heated-water source through a cold-water supply pipe is a demand recirculation water system. Pumps within this system have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1910 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C402.2.6 [ME41]3 Thermally ineffective panel surfaces of sensible heating panels have insulation >= R-3.5. Complies Does Not Not Observable Not Applicable C402.5.5, C403.2.4. 3 [ME3]3 Stair and elevator shaft vents have motorized dampers that automatically close. Complies Does Not Not Observable Not Applicable C402.5.5, C403.2.4. 3 [ME58]3 Outdoor air and exhaust systems have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Check gravity dampers where allowed. Complies Does Not Not Observable Not Applicable C403.2.12 .1 [ME65]3 HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp. Complies Does Not Not Observable Not Applicable See the Mechanical Systems list for values. C403.2.12 .3 [ME117]2 Fans have efficiency grade (FEG) >= 67. The total efficiency of the fan at the design point of operation <= 15% of maximum total efficiency of the fan. Complies Does Not Not Observable Not Applicable C403.2.13 [ME71]2 Unenclosed spaces that are heated use only radiant heat. Complies Does Not Not Observable Not Applicable C403.2.3 [ME55]2 HVAC equipment efficiency verified.Complies Does Not Not Observable Not Applicable See the Mechanical Systems list for values. C403.2.6. 1 [ME59]1 Demand control ventilation provided for spaces >500 ft2 and >25 people/1000 ft2 occupant density and served by systems with air side economizer, auto modulating outside air damper control, or design airflow >3,000 cfm. Complies Does Not Not Observable Not Applicable C403.2.6. 2 [ME115]3 Enclosed parking garage ventilation has automatic contaminant detection and capacity to stage or modulate fans to 50% or less of design capacity. Complies Does Not Not Observable Not Applicable C403.2.7 [ME57]1 Exhaust air energy recovery on systems meeting Table C403.2.7(1) and C403.2.7(2). Complies Does Not Not Observable Not Applicable C403.2.8 [ME116]3 Kitchen exhaust systems comply with replacement air and conditioned supply air limitations, and satisfy hood rating requirements and maximum exhaust rate criteria. Complies Does Not Not Observable Not Applicable C403.2.9 [ME60]2 HVAC ducts and plenums insulated. Where ducts or plenums are installed in or under a slab, verification may need to occur during Foundation Inspection. Complies Does Not Not Observable Not Applicable 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1911 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.2.9 [ME10]2 Ducts and plenums sealed based on static pressure and location. Complies Does Not Not Observable Not Applicable C403.2.9. 1.3 [ME11]3 Ductwork operating >3 in. water column requires air leakage testing. Complies Does Not Not Observable Not Applicable C403.4.2. 3.2.2 [ME122]3 Open- or closed circuit cooling towers have a separate heat exchanger to isolate the cooling tower from the heat pump loop, and heat loss is controlled by shutting down the circulation pump on the cooling tower loop. Complies Does Not Not Observable Not Applicable C403.4.4. 6 [ME110]3 Multiple zone VAV systems with DDC of individual zone boxes have static pressure setpoint reset controls. Complies Does Not Not Observable Not Applicable See the Mechanical Systems list for values. C408.2.2. 1 [ME53]3 Air outlets and zone terminal devices have means for air balancing. Complies Does Not Not Observable Not Applicable C403.5, C403.5.1, C403.5.2 [ME123]3 Refrigerated display cases, walk-in coolers or walk-in freezers served by remote compressors and remote condensers not located in a condensing unit, have fan-powered condensers that comply with Sections C403.5.1 and refrigeration compressor systems that comply with C403.5.2.. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1912 ofPage Section # & Req.ID Rough-In Electrical Inspection Complies?Comments/Assumptions C405.2.1 [EL15]1 Lighting controls installed to uniformly reduce the lighting load by at least 50%. Complies Does Not Not Observable Not Applicable C405.2.1 [EL18]1 Occupancy sensors installed in required spaces. Complies Does Not Not Observable Not Applicable C405.2.1, C405.2.2. 3 [EL23]2 Independent lighting controls installed per approved lighting plans and all manual controls readily accessible and visible to occupants. Complies Does Not Not Observable Not Applicable C405.2.2. 1 [EL22]2 Automatic controls to shut off all building lighting installed in all buildings. Complies Does Not Not Observable Not Applicable C405.2.3 [EL16]2 Daylight zones provided with individual controls that control the lights independent of general area lighting. Complies Does Not Not Observable Not Applicable C405.2.3, C405.2.3. 1, C405.2.3. 2 [EL20]1 Primary sidelighted areas are equipped with required lighting controls. Complies Does Not Not Observable Not Applicable C405.2.3, C405.2.3. 1, C405.2.3. 3 [EL21]1 Enclosed spaces with daylight area under skylights and rooftop monitors are equipped with required lighting controls. Complies Does Not Not Observable Not Applicable C405.2.4 [EL4]1 Separate lighting control devices for specific uses installed per approved lighting plans. Complies Does Not Not Observable Not Applicable C405.2.4 [EL8]1 Additional interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and separated from general lighting. Complies Does Not Not Observable Not Applicable C405.2.5 [EL25]null Automatic lighting controls for exterior lighting installed. Controls will be daylight controlled, set based on business operation time-of-day, or reduce connected lighting > 30%. Complies Does Not Not Observable Not Applicable C405.3 [EL6]1 Exit signs do not exceed 5 watts per face. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1913 ofPage 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1914 ofPage Section # & Req.ID Insulation Inspection Complies?Comments/Assumptions C303.1 [IN3]1 Roof insulation installed per manufacturer’s instructions. Blown or poured loose-fill insulation is installed only where the roof slope is <=3 in 12. Complies Does Not Not Observable Not Applicable C303.1 [IN10]2 Building envelope insulation is labeled with R-value or insulation certificate providing R-value and other relevant data. Complies Does Not Not Observable Not Applicable C303.2 [IN7]1 Above-grade wall insulation installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable C303.2.1 [IN14]2 Exterior insulation is protected from damage with a protective material. Verification for exposed foundation insulation may need to occur during Foundation Inspection. Complies Does Not Not Observable Not Applicable C402.2.1 [IN17]3 Insulation intended to meet the roof insulation requirements cannot be installed on top of a suspended ceiling. Mark this requirement compliant if insulation is installed accordingly. Complies Does Not Not Observable Not Applicable C402.2.3 [IN6]1 Above-grade wall insulation R-value.Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.2.5 [IN8]2 Floor insulation R-value.Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.2.6 [IN18]3 Radiant panels and associated components, designed for heat transfer from the panel surfaces to the occupants or indoor space are insulated with a minimum of R-3.5. Complies Does Not Not Observable Not Applicable C402.2.2 [IN2]1 Roof R-value. For some ceiling systems, verification may need to occur during Framing Inspection. Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.5.1. 1 [IN1]1 All sources of air leakage in the building thermal envelope are sealed, caulked, gasketed, weather stripped or wrapped with moisture vapor- permeable wrapping material to minimize air leakage. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1915 ofPage Section # & Req.ID Final Inspection Complies?Comments/Assumptions C303.3, C408.2.5. 2 [FI17]3 Furnished O&M instructions for systems and equipment to the building owner or designated representative. Complies Does Not Not Observable Not Applicable C303.3, C408.2.5. 3 [FI8]3 Furnished O&M manuals for HVAC systems within 90 days of system acceptance. Complies Does Not Not Observable Not Applicable C402.5.3 [FI51]3 Where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening are located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms are sealed and insulated. Complies Does Not Not Observable Not Applicable C402.5.6 [FI37]1 Weatherseals installed on all loading dock cargo doors. Complies Does Not Not Observable Not Applicable C402.5.8 [FI26]3 Recessed luminaires in thermal envelope to limit infiltration and be IC rated and labeled. Seal between interior finish and luminaire housing. Complies Does Not Not Observable Not Applicable C403.2.2 [FI27]3 HVAC systems and equipment capacity does not exceed calculated loads. Complies Does Not Not Observable Not Applicable C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable C403.2.4. 1.1 [FI42]3 Heat pump controls prevent supplemental electric resistance heat from coming on when not needed. Complies Does Not Not Observable Not Applicable C403.2.4. 1.2 [FI38]3 Thermostatic controls have a 5 °F deadband. Complies Does Not Not Observable Not Applicable C403.2.4. 1.3 [FI20]3 Temperature controls have setpoint overlap restrictions. Complies Does Not Not Observable Not Applicable C403.2.4. 2 [FI39]3 Each zone equipped with setback controls using automatic time clock or programmable control system. Complies Does Not Not Observable Not Applicable 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1916 ofPage Section # & Req.ID Final Inspection Complies?Comments/Assumptions C403.2.4. 2.1, C403.2.4. 2.2 [FI40]3 Automatic Controls: Setback to 55°F (heat) and 85°F (cool); 7-day clock, 2- hour occupant override, 10-hour backup Complies Does Not Not Observable Not Applicable C404.3 [FI11]3 Heat traps installed on supply and discharge piping of non-circulating systems. Complies Does Not Not Observable Not Applicable C404.4 [FI25]2 All piping insulated in accordance with section details and Table C403.2.10. Complies Does Not Not Observable Not Applicable C404.6.1 [FI12]3 Controls are installed that limit the operation of a recirculation pump installed to maintain temperature of a storage tank. System return pipe is a dedicated return pipe or a cold water supply pipe. Complies Does Not Not Observable Not Applicable C405.4.1 [FI18]1 Interior installed lamp and fixture lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts. Complies Does Not Not Observable Not Applicable See the Interior Lighting fixture schedule for values. C405.5.1 [FI19]1 Exterior lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts. Complies Does Not Not Observable Not Applicable See the Exterior Lighting fixture schedule for values. C408.2.1 [FI28]1 Commissioning plan developed by registered design professional or approved agency. Complies Does Not Not Observable Not Applicable C408.2.3. 1 [FI31]1 HVAC equipment has been tested to ensure proper operation. Complies Does Not Not Observable Not Applicable C408.2.3. 2 [FI10]1 HVAC control systems have been tested to ensure proper operation, calibration and adjustment of controls. Complies Does Not Not Observable Not Applicable C408.2.4 [FI29]1 Preliminary commissioning report completed and certified by registered design professional or approved agency. Complies Does Not Not Observable Not Applicable C408.2.5. 1 [FI7]3 Furnished HVAC as-built drawings submitted within 90 days of system acceptance. Complies Does Not Not Observable Not Applicable C408.2.5. 1 [FI16]3 Furnished as-built drawings for electric power systems within 90 days of system acceptance. Complies Does Not Not Observable Not Applicable 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1917 ofPage Section # & Req.ID Final Inspection Complies?Comments/Assumptions C408.2.5. 3 [FI43]1 An air and/or hydronic system balancing report is provided for HVAC systems. Complies Does Not Not Observable Not Applicable C408.2.5. 4 [FI30]1 Final commissioning report due to building owner within 90 days of receipt of certificate of occupancy. Complies Does Not Not Observable Not Applicable C408.3 [FI33]1 Lighting systems have been tested to ensure proper calibration, adjustment, programming, and operation. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1918 ofPage Project Title: Data filename: Oxoboxo Lofts Building B F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg B ComCheck.cck 08/16/19Report date: 1919 ofPage REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building C Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Average fenestration U-factor exceeds maximum Maximum UA:548 Your UA:1176 Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 1,887 0.0 24.0 0.039 74 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 720 0.333 182 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 105 0.270 28 Door 1: Solid Orientation: Unspecified 40 0.500 20 Door 3: Solid Orientation: Unspecified 28 0.500 14 Wall 2: Solid Concrete or Masonry:No Insulation Orientation: Left side 816 0.333 261 Window 2: Wood Frame:Double Pane with Low-E Orientation: Left side 33 0.270 9 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 1,200 0.333 288 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 282 0.270 76 Door 4: Solid Orientation: Unspecified 27 0.500 14 Door 5: Solid Orientation: Unspecified 27 0.500 14 Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 188 0.0 1.042 196 Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 1 of10 08/16/19Report date: Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 5 of10 08/16/19Report date: Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building C Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg C ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.50Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building D Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Fails using prescriptive requirements for alteration projects Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 1,887 0.0 24.0 0.039 74 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 1,360 0.333 355 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 294 0.270 79 Wall 2: Solid Concrete or Masonry:Interior Insulation Orientation: Left side 630 0.0 6.0 0.111 58 Window 2: Wood Frame:Double Pane with Low-E Orientation: Left side 63 0.270 17 Door 6: Solid Orientation: Unspecified 48 0.500 24 Wall 3: Solid Concrete or Masonry:Interior Insulation Orientation: Back 1,632 0.0 6.0 0.111 143 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 276 0.270 75 Door 4: Solid Orientation: Unspecified 40 0.500 20 Door 5: Solid Orientation: Unspecified 27 0.500 14 Wall 4: Solid Concrete or Masonry:Interior Insulation Orientation: Unspecified 630 0.0 6.0 0.111 68 Door 7: Solid Orientation: Unspecified 21 0.500 11 Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 196 0.0 1.042 204 Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 1 of10 08/16/19Report date: Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 5 of10 08/16/19Report date: Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building D Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg D ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 6.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.50Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building E Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Average fenestration U-factor exceeds maximum Maximum UA:620 Your UA:1161 Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 1,950 0.0 24.0 0.039 76 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 1,430 0.333 437 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 88 0.270 24 Door 8: Solid Orientation: Unspecified 30 0.500 15 Wall 2: Solid Concrete or Masonry:Interior Insulation Orientation: Left side 690 0.0 6.0 0.111 66 Window 2: Wood Frame:Double Pane with Low-E Orientation: Left side 33 0.270 9 Door 6: Glass Orientation: Unspecified 63 0.350 22 Wall 3: Solid Concrete or Masonry:Interior Insulation Orientation: Back 1,690 0.0 6.0 0.111 172 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 116 0.270 31 Door 5: Solid Orientation: Unspecified 27 0.500 14 Wall 4: Solid Concrete or Masonry:Interior Insulation Orientation: Right side 690 0.0 6.0 0.111 70 Window 4: Wood Frame:Double Pane with Low-E Orientation: Unspecified 17 0.270 5 Door 7: Solid Orientation: Right side 44 0.500 22 Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 1 of10 08/16/19Report date: Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 190 0.0 1.042 198 Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 5 of10 08/16/19Report date: Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building E Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg E ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 6.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.35Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building F Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Average fenestration U-factor exceeds maximum Maximum UA:691 Your UA:1941 Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 2,000 0.0 24.0 0.039 78 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 960 0.333 261 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 92 0.270 25 Window 5: Wood Frame:Single Pane Orientation: Unspecified 63 0.800 50 Door 8: Solid Orientation: Unspecified 21 0.500 11 Wall 2: Solid Concrete or Masonry:No Insulation Orientation: Left side 1,039 0.333 289 Window 2: Wood Frame:Single Pane Orientation: Left side 49 0.800 39 Door 6: Glass Orientation: Unspecified 121 0.350 42 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 1,690 0.333 546 Window 1: Wood Frame:Single Pane Orientation: Unspecified 49 0.800 39 Wall 4: Solid Concrete or Masonry:No Insulation Orientation: Right side 1,039 0.333 320 Window 4: Wood Frame:Single Pane Orientation: Unspecified 49 0.800 39 Door 7: Solid Orientation: Right side 28 0.500 14 Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 1 of10 08/16/19Report date: Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 180 0.0 1.042 188 Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 5 of10 08/16/19Report date: Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building F Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg F ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.35Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building G Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Fails using prescriptive requirements for alteration projects Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 6,439 0.0 24.0 0.039 251 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 2,171 0.333 506 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 595 0.270 161 Door 8: Glass Orientation: Unspecified 56 0.350 20 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 2,800 0.333 684 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 746 0.270 201 Wall 4: Solid Concrete or Masonry:No Insulation Orientation: Right side 633 0.333 155 Window 4: Wood Frame:Double Pane with Low-E Orientation: Unspecified 168 0.270 45 Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 370 0.0 1.042 386 Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 1 of10 08/16/19Report date: Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 5 of10 08/16/19Report date: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building G Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg G ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.35Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building H Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Fails using prescriptive requirements for alteration projects Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 4,280 0.0 24.0 0.039 167 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 875 0.333 212 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 168 0.270 45 Door 8: Glass Orientation: Unspecified 70 0.350 25 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 840 0.333 205 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 224 0.270 60 Wall 4: Solid Concrete or Masonry:No Insulation Orientation: Right side 136 0.333 45 Wall 5: Solid Concrete or Masonry:No Insulation Orientation: Left side 176 0.333 40 Window 4: Wood Frame:Double Pane with Low-E Orientation: Unspecified 56 0.270 15 Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 285 0.0 1.042 297 Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 1 of10 08/16/19Report date: Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 5 of10 08/16/19Report date: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building H Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg H ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.35Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building J Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 0 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Fails using prescriptive requirements for alteration projects Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 8,000 0.0 24.0 0.039 312 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 2,560 0.333 488 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 1,026 0.270 277 Door 8: Glass Orientation: Unspecified 70 0.350 25 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 3,520 0.333 905 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 802 0.270 217 Wall 4: Solid Concrete or Masonry:No Insulation Orientation: Right side 128 0.333 43 Wall 5: Solid Concrete or Masonry:No Insulation Orientation: Left side 950 0.333 242 Window 4: Wood Frame:Double Pane with Low-E Orientation: Unspecified 224 0.270 60 Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 420 0.0 1.042 438 Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 1 of10 08/16/19Report date: Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 5 of10 08/16/19Report date: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building J Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg J ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.35Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building K Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 90 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Fails using prescriptive requirements for alteration projects Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 3,880 0.0 24.0 0.039 151 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 1,596 0.333 359 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 518 0.270 140 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 1,596 0.333 359 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 518 0.270 140 Wall 5: Solid Concrete or Masonry:No Insulation Orientation: Left side 209 0.333 70 Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 265 0.0 1.042 276 Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 1 of 9 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 2 of 9 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 3 of 9 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 4 of 9 08/16/19Report date: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 5 of 9 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 6 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 7 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 8 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building K Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg K ResCheck.rck Page 9 of 9 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building L Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 180 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Fails using prescriptive requirements for alteration projects Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 999 0.0 24.0 0.039 39 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 405 0.333 108 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 32 0.270 9 Door 1: Solid Orientation: Unspecified 48 0.500 24 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 405 0.333 118 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 52 0.270 14 Wall 5: Solid Concrete or Masonry:No Insulation Orientation: Left side 555 0.333 185 Wall 6: Solid Concrete or Masonry:No Insulation Orientation: Right side 555 0.333 153 Window 4: Wood Frame:Double Pane with Low-E Orientation: Unspecified 96 0.270 26 Floor 1: All-Wood Joist/Truss:Over Unconditioned Space 128 0.0 0.0 0.249 32 Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 1 of10 08/16/19Report date: Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 92.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Complies?Comments/Assumptions 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 5 of10 08/16/19Report date: Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.6 [IN1]1 Floor insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2, 402.2.7 [IN2]1 Floor insulation installed per manufacturer’s instructions and in substantial contact with the underside of the subfloor, or floor framing cavity insulation is in contact with the top side of sheathing, or continuous insulation is installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Complies Does Not Not Observable Not Applicable 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building L Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg L ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window 0.50Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building M Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 90 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Invalid U-Factor(s) Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 11,440 0.0 24.0 0.039 446 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 832 0.333 179 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 224 0.270 60 Door 1: Solid Orientation: Unspecified 70 0.000 0 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 832 0.333 202 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 224 0.270 60 Wall 5: Solid Concrete or Masonry:No Insulation Orientation: Left side 3,520 0.333 645 Window 5: Wood Frame:Double Pane with Low-E Orientation: Unspecified 1,064 0.270 287 Window 6: Wood Frame:Single Pane Orientation: Unspecified 518 0.800 414 Wall 6: Solid Concrete or Masonry:No Insulation Orientation: Right side 2,848 0.333 551 Window 4: Wood Frame:Double Pane with Low-E Orientation: Unspecified 896 0.270 242 Window 4 copy 1: Wood Frame:Single Pane Orientation: Unspecified 228 0.800 182 Door 2: Solid Orientation: Unspecified 70 0.500 35 Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 1 of10 08/16/19Report date: Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0' 544 0.0 1.042 567 Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 2 of10 08/16/19Report date: Inspection Checklist Requirements: 94.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 3 of10 08/16/19Report date: Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.2 [FO1]1 Slab edge insulation R-value.R-_____ Unheated Heated R-_____ Unheated Heated Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.2 [FO3]1 Slab edge insulation depth/length. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 4 of10 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 5 of10 08/16/19Report date: Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 6 of10 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 7 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 8 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 9 of10 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg M ResCheck.rck Page 10 of10 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments REScheck Software Version 4.6.5 Compliance Certificate Project Oxoboxo Lofts Building M Energy Code:2015 IECC Location:New London, Connecticut Construction Type:Multi-family Project Type:Alteration Orientation:Bldg. faces 90 deg. from North Climate Zone:5 (5951 HDD) Permit Date: Construction Site: 42 Pink Row Uncasville, CT 06382 Owner/Agent: Dakota Partners 1264 Main Street Waltham, MA 02451 Designer/Contractor: Paul B. Bailey Architect LLC 110 Audubon Street New Haven, CT 06510 203-776-8888 Permit Number: Compliance: Fails using prescriptive requirements for alteration projects Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Ceiling 1: Cathedral Ceiling 837 0.0 24.0 0.039 33 Wall 1: Solid Concrete or Masonry:No Insulation Orientation: Front 1,316 0.333 382 Window 3: Wood Frame:Double Pane with Low-E Orientation: Unspecified 168 0.270 45 Wall 3: Solid Concrete or Masonry:No Insulation Orientation: Back 1,316 0.333 382 Window 1: Wood Frame:Double Pane with Low-E Orientation: Unspecified 168 0.270 45 Floor 1: All-Wood Joist/Truss:Over Outside Air 204 0.0 0.0 0.249 51 Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 1 of 9 08/16/19Report date: Inspection Checklist Requirements: 92.0% were addressed directly in the REScheck software REScheck Software Version 4.6.5 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable Requirement will be met. 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 2 of 9 08/16/19Report date: Section # & Req.ID Foundation Inspection Complies?Comments/Assumptions 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 3 of 9 08/16/19Report date: Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 08520 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07275 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable Exception: Ducts located completely inside the building envelope. 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 4 of 9 08/16/19Report date: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 5 of 9 08/16/19Report date: Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable Requirement will be met. 402.1.1, 402.2.6 [IN1]1 Floor insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2, 402.2.7 [IN2]1 Floor insulation installed per manufacturer’s instructions and in substantial contact with the underside of the subfloor, or floor framing cavity insulation is in contact with the top side of sheathing, or continuous insulation is installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Complies Does Not Not Observable Not Applicable 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 6 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable Requirement will be met. Location on plans/spec: Section 07210 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable Requirement will be met. 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable Requirement will be met. 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable Exception: All ducts and air handlers are located within conditioned space. 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 7 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable Requirement will be met. 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable Exception: Requirement is not applicable. 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable Requirement will be met. 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 8 of 9 08/16/19Report date: Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Oxoboxo Lofts Building M Data filename: F:\Proj 2016\PR 16-063 Uncasville\Documents\ComCheck\Bldg JM Connector ResCheck.rck Page 9 of 9 08/16/19Report date: 2015 IECC Energy Efficiency Certificate Insulation Rating R-Value 0.00Above-Grade Wall 0.00Below-Grade Wall 0.00Floor 24.00Ceiling / Roof _______Ductwork (unconditioned spaces): Glass & Door Rating SHGCU-Factor 0.27Window Door Heating & Cooling Equipment Efficiency _______Heating System:_________________________ _______Cooling System:_________________________ _______Water Heater:___________________________ Name:Date: Comments ACBEB B B B B B BB ECBEXITEXITEXITEXITEXITSDSDSDSDSDSDSDSDSDSDSDBATHROOMBATHROOMBATHROOMBEDROOMCL -7'-6"BEDROOMLIVINGKITCHENCL -7'-6"CL -7'-6"BEDROOMBEDROOMBEDROOMKITCHENKITCHENLIVINGLIVINGCORRIDOREQ EQEQEQ1/32/3EQ7' - 0"EQB B 4' - 10"EQEQ1/32/3BECBBB B1/32/3EQEQ2/31/3EQEQ5' - 6" 3' - 11 5/8"EQEQEQEQEQ EQEQ EQAAAEQEQEQ 10' - 0" 10' - 0" 10' - 0" EQEQEQ3' - 7 1/2"B BBB EQ EQ EQ4' - 10"3' - 6"EQ EQEQ EQEQ EQ4' - 10"B B BEQ EQEQ EQBB5' - 0 3/8"3' - 6" 6' - 6 3/4" 3' - 5 7/8"1/34' - 5" 4' - 5"AAAAEQ EQ4' - 7"EQ EQEQ EQEQ EQEQ 'A' EQ 'A'EQ 'B' EQ 'B'EQ EQ5' - 8 7/8"5' - 8 3/4"3' - 3"999EQEQBCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. DBBB B EEC CABB BBB DECDB B BB EXITEXITEXITEXIT SDSDSDSDSDSDSDSDSDBATHROOMBATHROOMBEDROOMBEDROOMBEDROOMBEDROOMBATHROOMKITCHENKITCHENKITCHENCORRIDORLIVINGLIVINGLIVINGCL -10' 0"CL -10' 0"6' - 6"EQEQEQEQ2/31/3EQEQ3' - 0"10' - 0"EQEQEQEQ1/32/3EQEQEQEQ2/31/32/31/3EQ 2"EQEQEQAAAAAAA4' - 7 3/8"10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"EQEQ EQEQ BEQ BEQ AEQ AEQEQEQ EQEQ EQEQ EQEQEQEQ EQEQ B6' - 0"EQ BEQ EQEQ EQEQEQEQ EQAAAAEQ EQEQ EQEQ EQEQ EQEQ 'B'EQ 'B'EQ EQEQ EQEQ 'A' EQ 'A'A.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.3' - 0"3' - 0"3' - 0"EQ EQ999REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedA-A1.11BUILDING AREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"A-A1.111BLDG A - LEVEL 11/4" = 1'-0"A-A1.112BLDG A - LEVEL 2ABDECFGHJKLMNORTHSITE KEY PLANABNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/199 Permit ReviewComments8/5/19 B-A2.27B-A6.356BBBBBBB ACCCE EXITSDSDSDSDBATHROOM1/32/3EQEQEQEQEQEQEQEQ6' - 4 5/8"6' - 4 5/8"8' - 0"3' - 6"4' - 0 1/4"4' - 0"EQEQEQEQBEDROOMBEDROOMKITCHENAAAEQ EQEQ EQEQ AEQ AEQ EQEQ BEQ BEQEQEQ EQEQEQEQ EQA.F.F.GWB on Mtl Stud7' - 6"EQEQ9B-A2.28B-A6.323BBBBAAAACCCCEXITEXITEXITEXITBSDSDSDSDSDBBSDBATHROOMEQEQ1/32/32/31/3EQEQEQEQ1/32/3EQEQEQEQEQEQEQEQEQEQEQEQ7' - 11 1/8"EQEQEQBEDROOMBEDROOMKITCHENEQ EQEQ EQEQ EQEQEQ EQEQEQ EQ2' - 4" 3' - 0" 1' - 6"EA.F.F.GWB on Mtl Stud7' - 6"7B-A5.67B-A5.6MIN.3' - 6"9BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedB-A1.12BUILDING BLEVEL B -REFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.121BLDG B - LEVEL B, RCP (PART A)1/4" = 1'-0"B-A1.122BLDG B - LEVEL B, RCP (PART B)MATCH LINEMATCH LINEABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 B-A2.27B-A6.398ACEBBBBBBBBBBCCCCB EEXITSDSDSDSDSDSDBATHROOMBATHROOM3' - 6"EQEQ2/31/39' - 0 1/8"EQEQ2/31/3EQEQEQEQ2/31/36' - 5 3/4"6' - 5 3/4"EQ5' - 11 3/4"EQ5' - 0"6' - 0"4' - 0"4' - 11 3/8"8' - 8 1/8"6' - 6 1/8"1/32/3KITCHENBEDROOMBEDROOMBEDROOMKITCHENCH: 7'-0"AAEQ EQEQEQEQEQ EQEQEQEQ EQEQEQEQ EQ1' - 6"3' - 4"2' - 7"A20' - 0"EQ EQA.F.F.GWB on Mtl Stud8' - 0"9EQ EQ9AECBBB BEC BBBCEB BAEXITEXITEXITSDSDSDSDSDSDSDSDSDBATHROOMBATHROOMBATHROOMEQEQEQEQEQEQ2/31/3EQEQ1/32/3EQEQ2/31/31/32/31/32/35' - 0"EQEQ5' - 6"EQEQEQEQ2/31/3EQEQ1/32/3KITCHENBEDROOMKITCHENKITCHENBEDROOMBEQEQEQ EQBEQ EQEQEQAA15' - 0"2' - 2 7/8" EQEQEQEQEQEQ EQEQ EQEQ EQA.F.F.GWB on Mtl Stud8' - 0"A.F.F.GWB on Mtl Stud7' - 0"9A.F.F.GWB on Mtl Stud8' - 0"9BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedB-A1.13BUILDING BLEVEL ONE -REFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.131BLDG B - LEVEL ONE, RCP (PART A)1/4" = 1'-0"B-A1.132BLDG B - LEVEL ONE, RCP (PART B)MATCH LINEMATCH LINEABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 AACEBBBBBBBBBBCCCEXITSDSDSDSDSDSDEQEQEQ9' - 0"EQ1/32/3EQEQEQEQ2/31/3EQ7' - 0"EQ6' - 5 3/4"4' - 5 5/8"6' - 0"9' - 2 1/2"EQ9' - 0"EQ1/32/3EQ EQEQ EQEQEQEQEQEQEQ5' - 0"EQBEDROOMBEDROOMBEDROOMKITCHENBATHROOMA.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud8' - 0"BATHROOM9EQ EQ9AEBCBC AABBB BEC BBBCEB BBEXITSDSDSDSDSDSDSDSDC1BATHROOMBATHROOMBATHROOMEQ14' - 0"EQEQEQ1/32/3EQEQBEDROOMKITCHENEQEQ1/32/3BEDROOMBEDROOMKITCHENKITCHEN1/32/3EQEQ2/31/3EQEQEQ8' - 0"EQEQEQ5' - 6"EQEQEQ EQ2/3 1/32/31/3EQEQEQ EQEQ EQBEQ EQEQEQBEQEQEQ EQEQ EQEQEQEQ EQEQEQEQ EQAAAEQ EQEQ 'C' EQ 'C'EQ 'B'EQ 'B'EQ 'A' EQ 'A'EQ EQEQ EQEQ EQA.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"999BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedB-A1.14BUILDING BLEVEL TWO -REFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.141BLDG B - LEVEL TWO, RCP (PART A)1/4" = 1'-0"B-A1.142BLDG B - LEVEL TWO, RCP (PART B)MATCH LINEMATCH LINEABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 AACEBBBBBBBBBBCCCEXITESDSDSDSDSDSDEQEQEQ 8' - 11 7/8" EQ1/3 2/3EQ EQ1/3 2/3EQ EQ4' - 6" 6' - 0" 9' - 8 1/8" 6' - 5 3/4"EQ 6' - 11 3/4" EQ1/3 2/3EQ 9' - 0" EQEQ EQEQ EQEQEQEQEQ EQ1' - 6"3' - 5"2' - 7"EQ EQEQEQBATHROOMA.F.F.GWB on Mtl Stud7' - 6"BEDROOMBEDROOMBEDROOMBATHROOMA.F.F.GWB on Mtl Stud7' - 0"KITCHENKITCHEN9EQ EQ9AEBCBC AABBB BEC BBBCEB BEXITSDSDSDSDSDSDSDSDSDEQ EQ2/3 1/3EQ EQ2/3 1/3EQ 14' - 0" EQEQ EQEQ EQ1/3 2/3EQ EQ2/3 1/3EQ EQEQ 8' - 0" EQ1/3 2/3EQ EQEQ EQ5' - 6"2/3 1/3 0"EQ EQEQ EQEQ EQBEQ EQEQEQBEQEQEQ EQEQ EQEQ EQEQEQEQEQ EQEQ EQEQ EQEQEQ EQAAAAEQ EQEQ EQEQ 'C' EQ 'C'EQ EQEQ EQEQ 'A'EQ 'A'EQ EQEQ 'B' EQ 'B'BEDROOMBEDROOMBEDROOMBATHROOMBATHROOMBATHROOMA.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"999BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedB-A1.15BUILDING BLEVEL THREE -REFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.151BLDG B - LEVEL THREE, RCP (PART A)1/4" = 1'-0"B-A1.152BLDG B - LEVEL THREE, RCP (PART B)MATCH LINEMATCH LINEABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 AACEBBBBBBBBBBCCCEXITSDSDSDSDSDSDEQ EQEQ 9' - 0" EQ1/3 2/3EQ EQEQ EQ1/3 2/3EQ 7' - 5 3/4" EQ6' - 0"4' - 6" 6' - 0"EQ 9' - 0 3/8" EQEQEQEQEQEQ EQEQ EQEQ EQEQ EQEQ EQEQ 5' - 0" EQBATHROOMBEDROOMBEDROOMBEDROOMBATHROOMKITCHENA.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.9EQ EQ9AEBCBC AABBB BEC BBBCEB BBEXITSDSDSDSDSDSDSDSDSDEQ EQ2/3 1/3EQ EQEQ 14' - 0" EQEQ EQ1/3 2/3EQ EQ2/3 1/3EQ 8' - 0" EQEQ EQ1/3 2/3EQ EQ5' - 6"EQ EQ2/3 1/3EQ EQEQEQEQEQBBEQ EQEQEQ EQEQEQEQEQ EQEQ EQEQ EQEQ EQEQ EQAEQ EQEQ EQBEDROOMBATHROOMBATHROOMBATHROOMBEDROOMBEDROOMEQEQEQ EQW.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.A.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"W.B.W.B.W.B.W.B.W.B.999BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedB-A1.16BUILDING BLEVEL FOUR -REFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.161BLDG B - LEVEL FOUR, RCP (PART A)1/4" = 1'-0"B-A1.162BLDG B - LEVEL FOUR, RCP (PART B)MATCH LINEMATCH LINEABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 CEC BEB BBBB BB BSDSDSDSDSDSD2/31/3EQEQ2/31/3EQEQEQ5' - 5 5/8"EQ2/31/3EQEQ2/31/3EQEQ1/32/3EQEQ8' - 0"5' - 6 1/8"BEQ EQEQ9' - 0"EQEQEQEQ EQEQEQEQ EQ9EQEQ 9B CE B CBB E B BBBB BB BSDSDSDSDSDSD7' - 0 3/8"4' - 0"1/32/3EQEQEQ7' - 0"EQ1/32/3EQEQEQEQ4' - 9 3/4"5' - 6 5/8"4' - 11 3/8"EQEQEQ8' - 0"EQEQEQEQEQ2/31/3EQEQ2/31/3EQ EQEQEQEQ EQEQ EQ EQEQ9 SD992/31/3BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedC-A1.11BUILDING CREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"C-A1.111BLDG C - LEVEL ONE, RCP1/4" = 1'-0"C-A1.112BLDG C - LEVEL TWO, RCPABDECFGHJKLMNORTHSITE KEY PLANBATHROOMBATHROOMBATHROOMBATHROOMCL -7' 0"CL -7' 0"BEDROOMKITCHENBEDROOMCL -7' 0"CL -7' 0"KITCHENBEDROOMKITCHENKITCHENBEDROOMBEDROOMBEDROOMBEDROOMBEDROOMNo. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 ABCEB B B B B B B BCECACCEXITSDSDSDSDSD2/3 1/3EQ EQ1/3 2/3EQEQEQ EQ2/3 1/3EQ EQEQ 9' - 0" EQEQ 7' - 0" EQ5' - 0"2/3 1/3EQ EQEQ EQEQEQEQ EQEQEQEQ EQEQEQEQ EQEQ EQEQ EQEQEQEQ EQEQ EQEQ EQ9SDMIN.3' - 6"99BBB B B B B B B ACCEEBABSDSDSDSD SD1/3 2/3EQ EQ2/3 1/3EQ EQ1/3 2/3EQ EQEQ 7' - 0" EQ2/3 1/3EQ EQEQ 8' - 0" EQEQ 7' - 0" EQ5' - 0"2/3 1/3EQ EQEQ EQEQ EQEQ EQEQ EQEQEQEQ EQEQEQEQ EQEQ EQ99SD9BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedD-A1.11BUILDING DREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"D-A1.111BLDG D - LEVEL ONE, RCP1/4" = 1'-0"D-A1.112BLDG D - LEVEL TWO, RCPNOTE: CEILINGS IN BLDG 'D', 1ST FLOOR, SHALL BE @ 9'A.F.F. ABDECFGHJKLMNORTHSITE KEY PLANBATHROOMBATHROOMBATHROOMBATHROOMELECTRICAL ROOMKITCHENKITCHENBEDROOMBEDROOMBEDROOMBEDROOMBEDROOMCL -8' 0"CL -8' 0"No. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 EBAAAAAAAAABBBBBBBB B EXITEXITSDSDSDSDSDSDSD1/3 2/3EQ 6' - 0" EQEQ EQ1/3 2/3EQ EQEQ EQEQ 6' - 0" EQEQ EQEQ EQEQ 7' - 0" EQEQ A EQ B EQ B EQ AEQ 1EQ 2EQ 2EQ 1EQEQEQ EQEQ EQ4' - 0"EQAAABBBBB B B B B BEECCCCCCCSD SDSDSDSDEQ EQEQ EQEQ 7' - 0" EQEQ EQEQ EQ2/3 1/3EQ EQ2/3 1/3EQ EQ1/3 2/31/3 2/3EQ 6' - 0" EQEQ EQEQ 8' - 0" EQEQ EQEQ EQEQ EQEQ EQEQ EQEQ EQ7' - 11 5/8"8' - 0"99SD9BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedE-A1.11BUILDING EREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"E-A1.111BLDG E - LEVEL ONE, RCP1/4" = 1'-0"E-A1.112BLDG E - LEVEL TWO, RCPNOTE: CEILINGS IN BLDG 'E', 1ST FLOOR, SHALL BE @ 9'A.F.F. ABDECFGHJKLMNORTHSITE KEY PLANBATHROOMBATHROOMBATHROOMCL: 8' 0"CL: 8' 0"No. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONEXITCBB2/3 1/3 EQ7' - 0"EQ BEQEQ 2/31/3B1/32/3EQ 7' - 0"EQC EQ EQ EQEQCBB1/32/3EQEQEQ EQ 2/31/3EQEQEQEQEQ EQ EQEQB3' - 0"EQ EQB1/32/3B3' - 0"EQ7' - 0"EQ EQEQ BB 3' - 0"EQEQ2/31/3EQ7' - 1"EQ BBEQ9' - 0"EQEQEQBEQ EQ EQ EQCB2/31/3EQ EQEQ EQEQEQ B EQEQ 3' - 0"BBBBBEQ 7' - 0"EQ 2/31/3BBB1/32/3EQ7' - 0"EQ3' - 0"EQ EQCCEQEQEQEQEQEQEQEQB2/31/3EQ EQ B EQ EQ 1/32/3B 3' - 0"EQEQBB EQ7' - 0"EQ 2/31/3W.B.W.B.W.B.W.B.W.B.W.B.W.B.A.F.F.GWB on Mtl Stud7' - 6"W.B.W.B.BATHROOMBATHROOMA.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"BATHROOMBATHROOMBATHROOMW.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.A.F.F.GWB on Mtl Stud7' - 6"BATHROOMW.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.A.F.F.GWB on Mtl Stud7' - 6"W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.W.B.A.F.F.GWB on Mtl Stud7' - 6"AAAAAAAAAAAEQ EQEQ EQSDSDEFEFSDUNIT G5SDSDEFEFUNIT G6UNIT G7SDEFEFSDEFUNIT G8SDEFSDUNIT G4SDEFEFSDEFUNIT G3SDEFSDEFUNIT G2SDBEDROOMBEDROOMBEDROOMBEDROOMBEDROOMBEDROOMBEDROOMKITCHENKITCHEN KITCHENKITCHENKITCHENKITCHEN KITCHENLVINGLVING LVINGLVINGLVINGLVINGLVINGMIN. 3'-6"9999999ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedG-A1.11BUILDING GLEVEL 1 -REFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063ABDECFGHJKLMNORTHSITE KEY PLAN1/4" = 1'-0"G-A1.111BUILDING G REFLECTED CEILING PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONCCCEQEQEQ EQEQEQEQ EQEQEQEQCEQ EQEQEQ B B2/31/3EQ EQ EQEQ 1/32/3B 1/32/3EQ EQBEQEQEQEQ BBEQEQEQ EQ EQ BBEQ 7' - 0"EQ1/3 2/3 B EQ EQ 3' - 0"B1/3 2/3 EQ EQ 10' - 0"10' - 0"10' - 0"3' - 6"4' - 6"10' - 0"A.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"A.F.F.GWB on Mtl Stud7' - 6"BATHROOMBATHROOMBATHROOMAAAAAAAW.B.W.B.W.B.W.P.W.P.W.P.W.P.W.B.W.P.W.B.W.B.W.B.W.B.W.B.W.B.W.B.AEFEFSDSDSDSDEFEFUNIT G1EFUNIT G9SDSDBEDROOM BEDROOMBEDROOMBEDROOMKITCHENKITCHENLIVINGLIVINGLIVINGKITCHENSD999SD9ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedG-A1.12BUILDING GLEVEL 1 -REFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063ABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 AAAADB B B B BBBEXIT SDSDSDSDSDSDSDEQ EQ 2/31/3EQ EQ 1/32/3EQ 9' - 0" EQ EQEQBEQ EQ EQEQBEQEQEQ A EQ A BB5' - 10"10' - 0 1/8"5' - 9 7/8"EQ B EQ BBEQEQEQEQEQEQ8' - 0"10' - 0" 8' - 0" 7' - 0" EQ EQ 6' - 0 1/8"10' - 0"10' - 0"E Q EQEQ EQEQ EQ AAAAAAAAAABATHROOMCEFEQEQ A.F.F.GWB on Mtl Stud7' - 6"EQEQBEDROOMKITCHENE BEQEQ2/3 1/3SD EFLIVINGUNIT H1W.P.W.P.W.P.W.P.W.P.AAEXITEXITKITCHENEF LIVINGBEDROOMUNIT H2W.P.W.P.W.P.9SD99SD9BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedHJ-A1.11BUILDING HREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"HJ-A1.111BLDG H - LEVEL ONE, RCPABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 ACCCCCB B B B B B B BBBABBB B B B B BBBBBBEEEEEEXITEXITSD SDSDSDSDSDSDSDSDSDSDSD2JM-A1.12JM-A1.1EQEQ1/3 2/3 EQEQ2/3 1/3 EQ9' - 0"EQEQEQEQ10' - 0"EQ10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"EQ EQ BBBEQEQEQEQ BBB EQEQ3 ' - 0" 3' - 0"EQEQEQEQEQ EQEF BATHROOMA.F.F.GWB on Mtl Stud7' - 6" EQEQEQEQ KITCHENLIVINGBEDROOMBEDROOMBEDROOMUNIT H26' - 6"UNIT J81/32/3EQ EQ BEDROOMKITCHENEQ EQ 3' - 6"2/31/3EQ EQEFEQ EQ EQEQEQEQ3' - 0 "3' - 6"6' - 0"7' - 9"7' - 9"12' - 5" 6' - 0"EQEQEQEQEFEFEQEQEQEQ W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.2/31/3EQ EQ BEDROOMBATHROOMA.F.F.GWB on Mtl Stud7' - 6"W.P.W.P.W.P.W.P.LIVINGLIVINGBATHROOMA.F.F.GWB on Mtl Stud7' - 6"W.P.W.P.W.P.W.P.W.P.EQEQEQEQ3' - 0"KITCHENEFEQEQW.P.W.P.W.P.W.P.W.P.AAAAAAAAAAAAW.P.W.P.W.P.UNIT J7BEDROOMKITCHENEFLIVINGW.P.W.P.W.P.W.P.W.P.BEQ EQ4' - 0"4' - 0"6' - 0"W.P.W.P.W.P.W.P.EQ EQ 1/32/3EQEQEQ EQEFA.F.F.GWB on Mtl Stud7' - 6"BATHROOMBEDROOMUNIT J1BATHROOMEQEQEQEQUNIT J2EFA.F.F.GWB on Mtl Stud7' - 6"W.P.1/32/3EQEQ W.P.W.P.W.P.EQEQ4' - 0"W.P.W.P.W.P.4' - 0"9' - 7"4' - 0"EQEQ BEDROOMLIVINGKITCHEN4' - 0"EQ EQ BEQEQEQ EQEFW.P.W.P.W.P.BEDROOMEQEQEQEQ1/32/3EQ EQSD 9SD9SD99SD9SDSD99SD99BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedHJ-A1.12BUILDING JREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"HJ-A1.121BLDG J - LEVEL ONE, RCP (PART A)ABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 CCCCCCB B B B B B B B B B B B B BBBBEEEEEE XITEXIT SDSDSDSDSDSDSDSDSDSDSDSDSDSDBEQEQEQ EQ BEQ EQ EQEQBEQEQEQ EQEQEQEQEQBEQEQEQEQBB B B EQ EQ EQEQEQEQEQ EQ 10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"10' - 0"9' - 11 1/2" 10' - 0" 4' - 5"EQEQEQ EQ 10' - 0"10' - 0"EQEQBEQ E Q2/31/31/32/3EQ EQLIVING W.P.BEDROOMW.P.W.P.W.P.EQEQEQ EQ EQ EQ 4' - 0"9' - 1"4' - 0"KITCHENEFW.P.EQEQ4' - 0"W.P.W.P.W.P.W.P.W.P.A.F.F.GWB on Mtl Stud7' - 6"EFBEDROOMBATHROOM1/32/3EQ EQ W.P.W.P.EQ EQ1/32/3BEDROOMBATHROOMEFA.F.F.GWB on Mtl Stud7' - 6"W.P.W.P.W.P.EQEQ4' - 0"10' - 2"4' - 0"LIVINGEQEQEQEQ EFKITCHENEQEQ4' - 0"W.P.W.P.UNIT J3UNIT J4UNIT J5EFBATHROOMA.F.F.GWB on Mtl Stud7' - 6"LIVINGEQEQ EQEQEFKITCHEN4' - 0"4' - 0"6' - 0"4' - 0"4' - 0"B EQEQEQEQEFBATHROOMA.F.F.GWB on Mtl Stud7' - 6"BEDROOMW.P.W.P.W.P.W.P.W.P.W.P.AAAAAAAAAAAAAAA.F.F.GWB on Mtl Stud7' - 6"EFBATHROOMBEDROOM1/32/3EQ EQ W.P.W.P.W.P.W.P.BEDROOM2/31/3EQ EQW.P.W.P.W.P.W.P.EQEQEQEQ EFKITCHENB B 4' - 0"4' - 0"EQEQEQ EQ LIVINGB4' - 0"4' - 0"7' - 2"4' - 0"UNIT J6W.P.W.P.W.P.W.P.2/31/3EQ EQ BEDROOMEFA.F.F.GWB on Mtl Stud7' - 6"BATHROOM9SD9SD9W.P.W.P.SD99SD99BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedHJ-A1.13BUILDING JREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"HJ-A1.131BLDG J - LEVEL ONE, RCP (PART B)ABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. AACCCCBBBBB BBBBB BB E EEBE EXITEXITSDSDSDSDSDSDSDSDSDSDSDSDSDSD1/3 2/3 EQEQBEQEQEQEQ EQ EQ EQEQEQEQEQ EQAAAAEQ EQ EQ EQ EQEQ AEQ EQEQEQEQEQ AEQEQ EQEQBBEQ EQ BB1/3EQEQBEDROOM UNIT K2EFBATHROOMA.F.F.GWB on Mtl Stud7' - 6" EQEQ 4' - 0"4' - 0" 9' - 11" 4' - 0"LIVINGEQEQKITCHENEQ EQ EQEQEF2/3 1/3 EQEQBEDROOMBEQEQ EQEQW.P.W.P.W.P.W.P.W.P.W.P.W.P.EQEQEQEQ EFKITCHENLIVINGB4' - 0" 4' - 0"EQEQEQEQEQEQ 4' - 0"EFA.F.F.GWB on Mtl Stud7' - 6"BATHROOMBEDROOM1/3 2/3 EQEQUNIT K1W.P.W.P.W.P.W.P.W.P.BEDROOM1/32/3 EQEQW.P.W.P.EQ EQ4' - 0"EFBATHROOMA.F.F.GWB on Mtl Stud7' - 6"W.P.LIVINGBEQEQEQEQ 4' - 0" 10' - 11" 4' - 0"EQEQKITCHENEFEQ EQEQEQEF EFKITCHENLIVINGUNIT K4UNIT K3EQEQEQ EQA.F.F.GWB on Mtl Stud7' - 6"BATHROOMB4' - 0"11' - 11" 4' - 0"EQEQEQEQEQEQ4' - 0"W.P.W.P.W.P.W.P.BEDROOMW.P.W.P.9W.P.9W.P.9W.P.SD99REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedK-A1.11BUILDING KREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"K-A1.111BLDG K - LEVEL 1 CEILINGABDECFGHJKLMNORTHSITE KEY PLANMATCH LINE BUILDING MMATCH LINE BUILDING MNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 EAAEEEB B B B B BBBBB B BBBBBBB EXITEXIT EXIT SDSDSDSDSDSDSDSDSDSDSDSDSDEQEQEQ EQ EQEQ EQEQEQEQEQ EQ AAAAAAAAEQ EQEQEQEQEQEQALIVINGUNIT M1W.P.BATHROOMEFA.F.F.GWB on Mtl Stud7' - 6"EQEQEQ EQEFKITCHENB4' - 0"10' - 4"4' - 0"6' - 0"2/31/3EQ EQ W.P.W.P.W.P.W.P.W.P.UNIT M21/32/3EQ EQ W.P.A.F.F.GWB on Mtl Stud7' - 6"EFBATHROOMLIVINGB B 4' - 0"4' - 0"EQEQ6' - 0"KITCHENEQEQEQEQEF W.P.W.P.W.P.W.P.UNIT M62/3 1/3EQ EQBEDROOMBEDROOMBEDROOM2/3 1/3EQEQBEDROOMKITCHENB B B 6' - 0"4' - 0"4' - 0"EQEQEQEQ EQEQEFLIVINGBATHROOMEQ EQEQ EQEFA.F.F.GWB on Mtl Stud7' - 6"BEDROOM3' - 4"6' - 9"EQEQ 3' - 4"6' - 9"EQEQ BEDROOMW.P.W.P.W.P.W.P.W.P.W.P.W.P.B 4' - 0"10' - 4"4' - 0"6' - 0"EQEQEQEQKITCHENEFEF BATHROOMA.F.F.GWB on Mtl Stud7' - 6"W.P.W.P.W.P.W.P.W.P.UNIT M7LIVINGW.P.W.P.BEDROOMW.P.B1/32/3 EQEQSDABSDEFEEQEQEQEQ EQ EQ DD3' - 0"4' - 6"3' - 0"3' - 0"DD3' - 0"3' - 0"4' - 9"3' - 0"DD3' - 0"3' - 0"5' - 9"3' - 0"DD3' - 0"9' - 5"3' - 0"3' - 0"W.P.9SD9EQ EQ W.P.W.P.W.P.99SD9W.P.9BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedM-A1.11BUILDING MREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"M-A1.111BLDG M - LEVEL ONE, RCP (PART A)ABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 AAAACCCCCDDDDEEEEESDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDB B B B B B BB B B B BBBBBBBB BBB EEFBATHROOMEQEQEQEQ A.F.F.GWB on Mtl Stud7' - 6" EQ EQEQEQKITCHENEF B 5' - 0"13' - 1"5' - 0"6' - 0"W.P.W.P.LIVINGUNIT M82/31/3EQ EQBEDROOM 2/31/3EQ EQBEDROOM W.P.W.P.W.P.W.P.W.P.EQEQ1/32/31/32/3EQ EQ BEDROOMBEDROOMW.P.W.P.W.P.W.P.W.P.W.P.W.P.LIVINGKITCHENEQEQEQEQ EFEFEQEQEQ EQB 6' - 0"5' - 0"13' - 1"5' - 0"BATHROOMA.F.F.GWB on Mtl Stud7' - 6" EQEQEQEQEQEQEQEQEF BATHROOMA.F.F.GWB on Mtl Stud7' - 6"UNIT M9UNIT M10B 6' - 0"4' - 0"10' - 2"4' - 0"3' - 0"3' - 0"D3' - 0"EQEQDDDD3' - 0"3' - 0"3' - 0"3' - 0"3' - 0"3' - 0"6' - 10"3' - 4"EQEQ 1/32/3EQEQLIVINGBEDROOMBEDROOM KITCHENEFEQEQEQ EQKITCHENEF3' - 0"EQEQB 5' - 0"13' - 6"5' - 0"UNIT M3LIVING3' - 4"6' - 8"EQ EQ BEDROOMBATHROOMEQEQEQEQEFA.F.F.GWB on Mtl Stud7' - 6"W.P.W.P.W.P.W.P.W.P.W.P.2/31/3EQ EQ BEDROOMBATHROOMEQEQEQ EQ EFA.F.F.GWB on Mtl Stud7' - 6"LIVINGUNIT M4B B 5' - 0"5' - 0"EQEQ6' - 0" 6' - 0"D3' - 0"7' - 5"3' - 0"3' - 0"EQEQEQEQ EFKITCHEN2/31/3BEDROOMBEQEQ EFBATHROOMEQEQEQEQA.F.F.GWB on Mtl Stud7' - 6"W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.EQEQ 9SD9W.P.W.P.W.P.EQ EQSDW.P.W.P.W.P.W.P.9EQEQ SD9W.P.SD9W.P.9SD9BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedM-A1.12BUILDING MREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"M-A1.121BLDG M - LEVEL ONE, RCP (PART B)ABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 AAAAAADDDDCCCCEEEEBBBBEXIT SDSDSDSDSDSDSDSDSDSDSDSDSDB B B B B B B B B B B BUNIT M11EFBATHROOMW.P.UNIT M5EQ EQEQ EQEFA.F.F.GWB on Mtl Stud7' - 6" EQEQ EQEQEQEQ3' - 0" EQ EQ 1/32/3BEDROOMKITCHENB 4' - 0"10' - 5"4' - 0"LIVINGW.P.W.P.W.P.W.P.W.P.2/31/3EQEQ W.P.W.P.W.P.FSPRINKLER ROOMBEQ EQ1/32/3BEDROOMB EQEQEQEQKITCHENEF4' - 0"9' - 9"4' - 0"LIVING3' - 0"EQEQ1/32/3EQ EQ BEDROOMEFEQEQEQ EQA.F.F.GWB on Mtl Stud7' - 6"BATHROOMW.P.W.P.W.P.W.P.W.P.W.P.W.P.W.P.SDW.P.W.P.W.P.W.P.9EQEQW.P.9SD9SD9SD9W.P.9BCDAELIGHTING LEGENDBASELITE - WAREHOUSE SHADE 16" - BLACK (FURNISH WITH CORD FOR FIELD ADJUSTED HEIGHT)LITHONIA LIGHTING - LED LAMP STEP BAFFLE TRACK KIT BR20 LED LAMPPHILIPS - SLIMSURFACE 7" LED ROUND 2700KPROGRESS - LED CORD HUNG WAREHOUSE LIGHT-BRUSHED NICKELLITHONIA LIGHTING - CONTEMPORARY SQUARE VANITY - 2" 3000K CHROMEEXITEXIT LIGHTEXTERIOR WALL MOUNTED LIGHT @ 84" A.F.F.HARD WIRED SMOKE/CARBON MONOXIDE DETECTORSDCEILING HATCH FOR MECHANICAL ACCESSUTILITY 4 FOOT FLOURESCENTFW.B.BEAM BRACING AT TOP OF INTERIOR PARTITION. WALL BRACING SYMBOLSW.P.POST UP BRACING AT TOP OF INTERIOR PARTITION. REFLECTED CEILING PLAN SYMBOL LEGENDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONAREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OFCEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT, UNLESS OTHERWISE NOTED, IS 8'-0" A.F.F.AREA INDICATES NEW TAPED & PTD 5/8" GWB CEILING SYSTEM, COORDINATE INSTALLATION OF CEILINGS AT UPPER FLOORS WITH THE ROOF TYPES, THE CEILING HEIGHT TO FOLLOW SLOPE OF THE ROOF STRUCTUREAREA INDICATES EXPOSED METAL DECKING AND STEEL STRUCTURE TO BE PRIMED AND PAINTEDAREA INDICATES EXISTING STRUCTURE TO REMAIN EXPOSED (ABATE AS REQUIRED, REMOVE ALL EXISTING PAINT, SAND/PREP, APPLY MIN 3 COATS PAINT), ALL DUCTWORK TO REMAIN EXPOSED (PAINTED), ALL EXPOSED CONDUIT (PAINTED) TO BE COORDINATED W/ ARCHITECT PRIOR TO INSTALLATIONScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWAs indicatedM-A1.13BUILDING MREFLECTEDCEILING PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"M-A1.131BLDG M - LEVEL ONE, RCP (PART C)ABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date3 Permit Set 2/26/194 Addendum 03 4/12/199 Permit ReviewComments8/5/19