Loading...
HomeMy WebLinkAbout2019-08-12 Oxoboxo Lofts - Addendum 7  Information contained in this document is proprietary and confidential and may not be disseminated to any party other than the intended recipient without the written consent of Paul B. Bailey Architect, LLC.   ADDENDUM 7  Issue Date: August 5, 2019  Oxoboxo Lofts  42 Pink Row, Uncasville, CT    General Information:    This Addendum shall become a part of the Contract and the Contractor shall be bound thereby.   Changes to the Drawings and Specifications Following the Final Construction Documents dated  10/12/2018.    This Addendum reflects changes addressing comments from Building Official:    1. Revised wall tags for corridor walls on building plans and updated wall types.  2. Add H.C. accessibility signage.  3. Add openings at Building A crawl space walls for access the mechanical equipment.  4. Remove ‘fitness room’ label at Building F.  5. Designate H.C. accessible washer and dryer at Building B.  6. Add details for laundry counter at Building B.  7. Remove stove at Building F kitchen.  8. Revised HVAC return air grill at Building A Level 2.    Building Official’s comments to be addressed in a later Addendum:    1. ComCheck.  2. Smoke detector locations.    This Addendum includes the following RFI, drawings and specs:      1. RFI DP 103 ‐ 2019‐07‐22 BLDG INSPECTOR's QUERIES ‐ answered by PBA ‐ 190724   2. Architectural drawing sheets:  R.5 Wall Types  A6.3 Cabinet and Laundry Room Details  A7.1.2 All Buildings Signage Schedule  A7.1.3 Buildings A, D, & E Signage Plans    Information contained in this document is proprietary and confidential and may not be disseminated to any party other than the intended recipient without the written consent of Paul B. Bailey Architect, LLC.   A7.1.4 Building B Signage Plans  A7.1.6 Buildings C. F. L Signage Plans  A7.1.8 Buildings H, J, K, & M Signage Plans  A‐A1.0 Building A Level 0 Plan  A‐A1.1 Building A Level 1 Plan  A‐A1.2 Building A Level 2 Plan  B‐A1.1 Building B Level SB Plan  B‐A1.2 Building B Level B Plan  B‐A1.3 Building B Level 1 Plan  B‐A1.4 Building B Level 2 Plan  B‐A1.5 Building B Level 3 Plan  B‐A1.6 Building B Level 4 Plan  D‐A1.1 Building D Plans  E‐A1.1 Building E Plans  F‐A1.1 Building F Level 1 Plan  F‐A3.1 Building F Sections  F‐A6.1 Building F Toilet and Kitchen Plans and Elevations  F‐A7.0 Building F finish Schedule  G‐A1.1 Building G Level 1 Part A Plan  G‐A1.2 Building G Level 1 Part B Plan  HJ‐A1.1 Building H Plan  HJ‐A1.2 Building J Plan  HJ‐A1.3 Building J Plan  K‐A1.1 Building K Level 1 Plan  M‐A1.4 Building M Level 1 Part A Plan  M‐A1.5 Building M Level 1 Part B Plan  M‐A1.6 Building M Level 1 Part C Plan    3. MEP sheets:  ABC‐MD1.3  ABC‐EL1.B  ABC‐EL1.3  DE‐EL1.1  F‐EL1.1  GH‐EL1.1  LM‐EL1.1   E3.3    END OF ADDENDUM 7  Request For Information RFI DP No. 103 Project Information Project: Address: Oxoboxo Lofts 42 Pink Row Uncasville, CT Responder and Date Submitted Date: Company: Attn: Subject: 7/22/19 Paul B. Bailey Architect Susan Odell BLDG INSPECTOR PLAN REVIEW - QUESTIONS INFORMATION REQUESTED Attached are the Building Inspector’s 7/8/19 questions required for sign-off for the Building Permit. Please respond. Expedited Response Requested Response Requested By: RESPONSE Responder: Company: Date: Plan Review CommentArchitect’s Response1 2015 IEBC Section 310.6 Alterations of a Facility. SEe Section 410.6Answered by requirement of comment #32 (letter from Architect). See attached letter.2 Drawing ‐ H‐J KP2.1 & HJ‐A1.1: Boiler Room ‐ East Corridor walls should be W2.The only difference between walls types W‐1 and W‐2 is resilient channel vs. hat channel, which would only affect the acoustic rating. The fire rating is the same for both wall types. The wall type with the resilient channel, W‐1, is the wall type that should be used at both unit separation walls and at unit/corridor walls to meet acoustic rating requirements. We will correct the drawings to show W‐1 at all of these locations.3Drawing ‐ H‐J KP2.1 & HJ‐A1.1: Accessible Units are not defined. All units in Buildings H and J are Type B units.4Drawing ‐ H‐J KP2.1 & HJ‐A1.1: West Wall of Boiler Room type is not shown between Apt & Boiler Room. Wall type W‐1 is shown on G‐A1.2.5Drawing ‐ H‐J KP2.1 & HJ‐A1.1: All Walls are not W2See answer to comment #2 above.6 Laundry Room ‐ Are washers & dryers required to be Handicap accessible?We will provide enlarged plan of the Laundry Room showing 1 accessible washer and 1 accessible dryer.7Two Types of Units One & two Bedroom ‐ The One Bedroom units do not have handicap access to Laundry Room & StairsFloor levels in Bldgs G, H, J, K & M are being revised to all be at the same level, per latest direction from DEEP regarding flood elevations, which will improve the accessible path throughout this group of buildings. All units will have easier access to the Laundry Room. The stairs will be eliminated.8 Drawing ‐ HJ‐A1.2 Handicap Room?All units shown on this sheet are Type B units.9 Drawing ‐ HJ A1.3 Wrong type of wall noted between Meter Room & Bedroom 1 in Unit J‐1 See answer to comment #2 above.10 Section 1107.6.1.1 Accessible units shall be dispersed among various classes of units.See attached commentary on IBC Section 1107.6.2.2.1 for explanation. 11Section 1107.6.2.2.2 Where there are four or more units as residences in a single structure shall be Type B units.All units that have an accessible path to them are either Type A or Type B units.12General Note For Accessibility ‐ Number of Units up to 75 requires one roll‐in shower and three without for a total of four unitsPer IBC Section 1107.6.2.3, this chart applies to R‐2 uses other than live/work units, apartment houses, monasteries & convents. Per the commentary, it applies to congregate housing types such dormitories, boarding houses, fraternities and sororities, and non transient hotels and motels.13Question Building M: Basement? Area? Any Storage? Any Separations Walls? Ceilings Rated? Ceilings "R" Factor? Are you calling these Buildings Type B Units?The basement is below the flood plain and therefore storage of anything of value is not allowed. This area will have very limited access and will not be used. The floor members provide a 1‐hour rating per heavy timber definition. 14IEBC Section 1012: Buildings and/or portions therofAccessibility Section 1012.1.4 shall comply with 1012.8, 1012.8.2.1 through 6 apply1012.8.2(1): At least one accessible building entrance. We comply. See C‐4.2 Handicap Accessibility Plan. See attached letter for any conditions where an accessible building entrance is technically infeasible.1012.8.2(2): At least one accessible route from an accessible building entrance to primary function areas. We comply. See C‐4.2 Handicap Accessibility Plan.1012.8.2(3): Signage complying with Section 1111 of the IBC. We comply. See sheet C‐7.0 for site signage and A‐7.1.1 through A‐7.1.8 for room identification signage. See Electrical Lighting Plans and Lighting Fixture Schedule on E3.3 for exit signs. The exit signs at all accessible doors (as shown on C‐4.2 Handicap Accessibility Plan) will be updated to an exit sign with the HC symbol. See answer to comment #18 below for other signs that we need to add to Sheets A‐7.1.1 through A‐7.1.8.1012.8.2(4) Accessible parking, where parking is provided. We comply. See C‐7.0 for parking layout.1012.8.2(5) At least one accessible passenger loading zone, where loading zones are provided. Loading zones are not being provided at this project.1012.8.2(6) At least one accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance. We comply. See sheets C‐4.2 for accessible routes connecting accessible routes with accessible entrances. See sheet C‐7.0 for accessible parking locations.15 Are calling these Buildings Type B units? All units that have an accessible path to them are either Type A or Type B units.16 Star with Building ‐ Level B ‐ Bedroom One has no Emergency EgressPer IBC Section 1030.1, "...provisions shall be made for emergency escape & rescue openings in Group R‐2 occupancies in accordance with Tables 1006.3.2(1) and 1006.3.2(2). These tables list conditions where one means of egress is allowed in Group R‐2 occupancies, and state in footnote "a" that one means of egress is allowed if the building is sprinklered and if emergency escape & rescue openings are provided. All of the buildings in our project have 2 means of egress, therefore emergency escape & rescue openings are not required.17 Building A: W4 New Shaft for what? Floor grate in floor upper corridor level?Shaft is for the 10x8 RA duct shown on sheet ABC‐MD1.B. Will ask for clarification from the Mechanical Engineer on how the return air is handled on the upper corridor level ‐ we agree that a floor grate is the logical answer but it is not clear on the drawing. Drawing will be updated to call out a floor grate if that is the intention of the Mechanical Engineer.18Signs per Section 111 IBC. Section 410.4.2(3) Handicap Signage Type at Entrance Location not shown. Drawing A‐A1.1IBC 1111.1(5): indentify accessible entrances where not all entrances are accessible with the International Symbol of Accessibility. Since not all building entrances are accessible, we will add the International Symbol of Accessibility at the accessible entrances shown on C‐4.2.19 Drawing A‐A1.0 Crawl Space ‐ Ventilation not shown or addressed per Section 1203.4, IBCIBC Section 1203.4 states "The space between the bottom of the floor joists and the earth under any building...shall be provided with ventilation openings...." The crawl space in Building A has an existing concrete slab that will remain, so there is a slab between the "earth" and the bottom of the floor joists. Because of that, we do not think this section applies to Building A.20 Drawing A‐A1.0 crawl Space ‐ Access openings required per Section 1209, IBC We will show access panels in all cross walls.21Drawing A‐A1.11 ‐ Smoke Detectors per IBC Section 907.2.11.11(1). Locations not per code.We will update smoke detector locations to be immediately adjacent to the bedrooms. Per conversation with you, we will check all 2 bedroom units for this issue.  22 Building B: Level SD ‐ Boiler Room. What size boiler or boilers in project? (In Bldgs B & H) See sheet P2.1 for the fixture schedule and attached cut sheet.23Level B, DrawingB‐A1.2 ‐ Laundry Room Counter top ‐ section needs to be at accessible level. One washer & one dryer needs to be accessibleWe will provide updated countertop section showing it at an accessible level. We will provide enlarged plan of the Laundry Room showing 1 accessible washer and 1 accessible dryer.24 Bldg C: Level One ‐ Lower Level and Level Two Upper Level ‐ smoke detector locations?We will update smoke detector locations to be immediately adjacent to the bedrooms. Per conversation with you, we will check all 2 bedroom units for this issue. 25 Bldg D: No issues. Great!26 Bldg E: No issues. Great!27 Bldg F: Use ‐ Assembly, Occupant Load?Use group is A‐2. Occupant loads and use group are shown on the life safety plan. See sheets LS1.1 ‐ LS1.6.28 Drawing F‐A6.1 Detail 8, range hood ‐ commercial type? Dinette/Kitchen We will remove the stove/oven from this Community Kitchen.29 Bldg F: Two Accessible Means of Egress required. See stairs at rear corner. Two means of egress are required, only one has to be accessible. 30 Map R‐1 R‐2 Use Group ‐ Construction Classification Not ListedSheet R1.1 shows Type 3B for Buildings A, B, C, D, E and F. We will add Type 3B to the columns for Buildings G, H, J, K, M and L.31 Building J reduces at existing wall opening. Does projection interfere with hallway?Reason for wall extension into path is existing structural condition. FM to determine if acceptable, per our conversation.321012.8 For each building that does not comply with Section 1012.8 of the IEBC have the Architect or Applicant furnish a document stating their opinion of why it is technically infeasible to comply. State reason for each item in Section 1012.8.2 individually.See attached letter.331012.4.1 #7 Emergency Escape and Rescue Opening not required?? Please furnish code section.IEBC 1012.4.1 #7 is an exception to the requirement in 1012.4.1 to provide means of egress that complies with the requirements of Chapter 10 of the IBC, specifically an exception to the size of emergency escape and rescue opening. This exception would only apply if emergency escape and rescue openings were required by Chapter 10 of the IBC. Per answer to comment #16, the issue of emergency escape and rescue openings does not apply to our project since we have 2 means of egress in every building. Therefore, 1012.4.1 #7 is not applicable as an allowed exception.  34Per IBC Section 1030.1 ‐ R2 Buildings with sprinklers and two means of egress and rescue openingsSee answer to comment #16 above.35 What is water source/supply See sheet C5.0 for water & fire connections to utility in the street36 2015 IECC ‐ Comchek required. Data not found. We will provide a Comchek.37 Boiler Sizes not provided See sheet P2.1 for the fixture schedule and attached cut sheet.38Review reveals 2 boiler rooms ‐ one in B and one in H. What other buildings do they service?The boiler in Bldg B serves Bldgs A, B, C, D, E. The boiler in Bldg H serves Bldgs G, H, J, K, M.39 Size of boilers will dictate number of exits from each boiler room. Only one at present. See attached cut sheet for size of boilers.40 Details for accessible ramps at entrances not provided See attached sheet C6.1 41 Accessibility to Bldg M is too remoteFloor levels in Bldgs G, H, J, K & M are being revised to all be at the same level, per latest direction from DEEP regarding flood elevations. The main entrance to this group of buildings is at Building H, and this entrance is accessible. The doors with steps at the east end of Building M are to be used for egress only. The door at the west end of Building M that has an accessible ramp is provided for convenience ‐ it is the closest location to a HC parking space in the lower parking area. It is not a substitute for accessibility at the main entrance, which is in Bldg H. 42 Occupancy Load in Common Areas not clear or listed. See Sheets LS1.1‐LS1.6 for all occupancy counts43 Permits required for elevators Will be provided by GC during construction44 Permits (State) for Boilers required. Will be provided by GC during construction45 Drawing F‐A1.1 Fitness Room, F‐A1.2 Community Room ‐ shown on entire floor?We will correct labels on this sheet to show that this space is the Community Room. The Fitness Room is on the first floor of Building E. 46 Lobby ‐ mailboxes ‐ are they for all units?The lobby in Bldg B has mailboxes that serve residents in Bldgs A, B, C, D, E. The lobby in Bldg H has mailboxes that serve residents in G, H, J, K, M. P A U L B. B A I L E Y • A R C H I T E C T • LLC 1 1 0 A U D U B O N S T R E E T N E W H A V E N , C O N N E C T I C U T 0 6 5 1 0 P H: 2 0 3 7 7 6 8 8 8 8 F A X: 2 0 3 7 7 2 1 3 6 5 July 24, 2019 Vernon D. Vesey II, Building Official Town of Montville Building Department 310 Norwich-New London Turnpike Uncasville, CT 06382 Dear Vern, This letter addresses the areas of the Oxoboxo Lofts project at 42 Pink Row, Uncasville, that have been determined to be technically infeasible or otherwise not required to have handicap accessibility. 1) Requirement for Type A Dwelling Units: The project meets the requirements for new construction for the provision of Type A Dwelling Units as described in IBC Section 1107.6.2.2.1 as amended by the Connecticut 2018 Building Code. 2) Requirement Type B Dwelling Units: Per the exception in IEBC Section 1205.15 concerning Accessibility Requirements for historic structures undergoing a change of occupancy, Type B dwelling units required by Section 1107 of the IBC are not required to be provided in historical buildings. Nonetheless, we are providing Type B units where practical to do so. 3) Through IEBC Section 1205.15, Accessibility Requirements for an Historic Structure undergoing a change of occupancy: Requirement for at least one accessible building entrance per IEBC Section 1012.8.2 (1): a. G, H, J, K, M Building Group: One accessible building entrance is provided at the main entrance to this building group located at Building H. A secondary accessible building entrance is provided in this building group in Building M for convenient access to an accessible parking space. This building group has one floor level so all units in this group are accessible for visitors, and all are Type B units. b. A, B Building Group: One accessible building entrance is provided at the main entrance to this building group located at Building B Level 1. A secondary accessible building entrance is provided in this building group at Level 2 of Building A for convenient access to an accessible parking space. This building group has many floor levels. The floor levels that are not accessible are: i. Building A Level 1 – Type B Dwelling Units are not required per item #2 above. We are providing them where practical to do so. It is not practical at this floor level to do so. There are no public spaces at this floor level. ii. Building B Sub-Basement – Only contains mechanical and maintenance spaces, which are not required to be accessible. iii. Building B Level 4 – The elevator shaft in Building B is not permitted to penetrate through the historic roof per State Historic Preservation Tax Credit requirements, so Level 4 contains the elevator overrun. Type B Dwelling Units are not required per item #2 above. We are providing them where practical to do so. It is not practical at this floor level to do so. There are no public spaces at this floor level. c. Building C: Level 2 contains two Type A units. Level 1 contains two units which are not required to be Type B Units, and it is not practical to provide Type B Units at this level due to site impracticality. There are no public spaces at this floor level. d. Building D: There are no public spaces in Building D. There is an electrical room, which is not required to be accessible. There are no type B units on either level because it is not practical to do so. e. Building E: All areas of Level 1 are accessible, due to the public nature of all areas on this level. There are two units on Level 2 of this building, which are not Type B units, as it is not practical to do so. There are no public spaces on Level 2 of this building. f. Building F: All areas of Level 1 are accessible, due to the public nature of all areas on this level. The public area of Level 2 is accessible. The Mechanical Room on Level 2 is not required to be accessible. g. Building L: All areas of Building L are maintenance spaces, which are not required to be accessible. As discussed previously, if the Maintenance Office currently shown in Building L poses a concern for the need for accessibility, we will eliminate that office and just have maintenance storage in Building L. 4) Through IEBC Section 1205.15, Accessibility Requirements for an Historic Structure undergoing a change of occupancy: Requirement for at least one accessible building entrance to primary function areas per IEBC Section 1012.8.2 (2): Primary function areas include: a. Mailboxes at the main entrances to Buildings B and H, which are both accessible. b. Laundry Rooms in Buildings B and H, which are both accessible. c. Offices, Restroom and Fitness Room in Building E, which are all accessible. d. Community Room with Kitchenette and Restrooms in Building F, which are accessible. e. Playground outside of Building M, which has an accessible path from all buildings. The path is circuitous due to existing site conditions but it is provided. 5) Through IEBC Section 1205.15, Accessibility Requirements for an Historic Structure undergoing a change of occupancy: Requirement for signage complying with section 1111 of the IBC per IEBC Section 1012.8.2 (3): a. This is being provided throughout the project in all applicable conditions. 6) Through IEBC Section 1205.15, Accessibility Requirements for an Historic Structure undergoing a change of occupancy: Accessible parking, where parking is provided per IEBC Section 1012.8.2 (4): a. Each of the three parking areas have accessible parking spaces. 7) Through IEBC Section 1205.15, Accessibility Requirements for an Historic Structure undergoing a change of occupancy: At least one accessible passenger loading zone, where loading zones are provided, per IEBC Section 1012.8.2 (5): a. There are no loading zones in this project. 8) Through IEBC Section 1205.15, Accessibility Requirements for an Historic Structure undergoing a change of occupancy: At least one accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance per IEBC Section 1012.8.2 (6): a. There are accessible routes from all accessible parking spaces that connect to accessible building entrances nearby, and that connect to the overall site accessibility path. Sincerely, Susan B. Odell, AIA, CPHC® Senior Project Architect, Paul B. Bailey Architect, LLC Typical Specifications For Dynaforce®Domestic Hot Water Supply Models DR(W) 0300 –DR(W) 5000 99-0130Rev 06 The domestic hot water boiler shall be a CAMUS Dynaforce®model _______ having a recovery capacity of ___________gph (lph) at100ºF (56ºC) for DHW The domestic hot water boiler shall be design certified by CSA International and shall meet the requirements of ANSI Z21.10.3, andCSA 4.3. The domestic hot water boiler shall be vented as a Category II or IV condensing appliance. Performance Overview: -Domestic hot water boiler shall operate up to 99%thermal efficiency-Heat exchanger shall be a fully condensing vertical cylindrical counter-flow water tube design with 439 grade tubes and 316Lheaders of stainless steel construction and all welded design with constant allowable system return temperatures of 40F.-Fine tuned combustion premix providing homogeneous air and gas combustion mix to a radial burner incorporating a knitted stainless steel wrap insuring stable light off and efficient clean combustion.-5:1 gas input turn down ratio with sustained efficient combustion characteristics throughout entire modulating range-Oxides of Nitrogen (NOx) of 9 ppm corrected to 3% oxygen.-Category II venting certification with Category II and IV venting options.-The domestic hot water boiler is fully factory fire tested to obtain optimum combustion characteristics and to establish certified gas input rates.-System safety and operating devices and controls are fully configured, calibrated and factory tested.-Models consist of an input range of 300 MBTUH to 4999 MBTUH-The boiler shall comply with the energy efficiency requirements of the latest edition of the ASHRAE 90.1 Standard Combustion Chamber:The combustion chamber shall be an all welded stainless steel construction and an integral part of the heat exchanger which shall bean all welded vertical cylindrical stainless steel counter-flow design consisting of an upper burner section for primary heat transfer and alower section for extracting latent heat from flue gases. Stainless steel access heat exchanger wraps shall be provided for ease of service and inspection of the external heat exchanger and an easily removable radial fired knitted fiber stainless steel burner to accessthe internal combustion chamber for inspection, service, and cleaning. A window view port shall be provided for visual inspection of theboiler combustion during firing. Heat Exchanger:The stainless steel heat exchanger shall be inspected and tested to A.S.M.E. Section IV requirements. The A.S.M.E. Section IV seal ofapproval will not be provided as standard for jurisdictions not requiring the A.S.M.E Section IV seal of approval. The stainless steel heatexchanger shall be a 12 pass construction with a maximum working pressure of 160 psig (1100 kPa). The heat exchanger shall be of 439 grade stainless steel welded construction with a vertical cylindrical counter-flow water tube design complete with integral 439 gradestainless steel finned heat transfer tubes and 316L waterways. The heat exchanger design shall be capable of 40oF constant systemreturn temperatures and have a fully condensing heat exchanger complete with condensate trap and drains. A pressure relief of valve of__________ lb/hr shall be furnished with the heater. Gas Train:The gas train shall consist of a pressure regulating electro-hydraulic proportional air/gas main gas actuator providing a slow opening,fast closing shutoff valve and proportional 1:1 air/gas ratio control, a fast closing safety shutoff gas pressure regulator with 1 PSIallowablestaticpressure,and a low gas pressure switch.Optional high gas pressure switch is available.A factory pre-set combination metering valve and orifice shall be provided for setting combustion parameters. Models DR 300 –DR 5000 operate with a 5:1 turndownratio. Burner/Combustion:The combustion air fan draws gas under negative pressure and mixes it with air to generate a fine tuned air gas mixture which is delivered under positive pressure to the radial knitted stainless steel burner.Combustion modulation is established by either a pulsewidth modulation signal on models (DR300 –DR1000) or by a variable frequency drive on models (DR1200 –DR5000). The burnershall be a 100% stainless steel vertical mounted radial fired type with stainless knitted metal fiber construction. The burner shallcombust a precise amount of premixed combustion air and gas to provide equal distribution of heat for heat transfer throughout the entire heat exchanger. Combustion products are exhausted under minimum back pressure.Combustion operates with a 5:1 turn downratio while sustaining combustion characteristics throughout the entire modulating range. Operation of up to 99% thermal efficiency andshall be certified for Oxides of Nitrogen (NOx) of 9 ppm corrected to 3% oxygen. Firing Mode: The burner combustion shall operate as proportional modulating with a 5:1 turndown ratio with a minimum 20% firing rate. Multipleboiler “Cascade” firing algorithms are proportional modulation.Light off shall be at no more than 50% input to assure rumble free softstart.Combustion shall be optionally suitable for natural gas, propane and dual fuels operation. Typical Specifications For Dynaforce®Domestic Hot Water Supply Models DR(W) 0300 –DR(W) 5000 99-0130Rev 06 Controls:Standard controls include a SOLA electronic proportional integrated combination ignition limit/operator control accurate to 1oF (0.5oC)having a 4-20 mA output signal suitable for control of a variable frequency motor drive or a pulse width modulation signal output for modulating fan speeds. Controls are lead lag “Cascade” ready for control of up to eight boilers c/w Indoor outdoor reset and lead lagcontrol. Control shall be equipped and ready with 4-20 mA remote set point or modulating control,capable with 0-10 VDC remote setpoint and modulating control.Control is BMS Modbus RTU protocol ready and capable of other alternate protocol conversions withadditionaloptionalgateway protocol converter.Control shall be supplied with a mounted touchscreen display which shall also providefor control system configuration and set up,readouts of boiler target, differential and inlet/outlet temperatures as well as accumulated runtime, enunciator diagnostics, and firing rates.Touchscreen display shall provide full diagnostics including real time data logging andsupport for up to eight (8) boilers in “Cascade”sequencing application, MODBUS ready. The complete control package shall bemounted on the front panel with a hinged door for easy access to all control modules.The boiler safety control string shall be furnishedwith controls for low gas pressure, optional high gas pressure, fan air proving, blocked flue, water pressure, high limit, stack limit and flow switch.A flow switch shall be installed on the boiler outlet.Additional control safeties shall include flue gas stack temperature,flame rectification, fan speed, and soft high limit. Ignition Module:The ignition module shall employ a direct igniter with 3 tries for ignition followed by lockout for DR 300 -DR 2500.A proven pilot is used on DR 3000 –DR 5000. Trial for ignition shall proceed with 15 seconds between retrials.Ignition control shall include times for pre-purge, pre-ignition, ignition, and post purge. Venting Options The following venting options shall be utilized: Category II Venting –single or combined vent*Category IV Outside Air (Horizontal & Vertical) Category IV Through-wall Venting (Horizontal & Vertical) Outdoor VentingCategory II & IV Direct Venting *Category II combined vent shall only employ an engineered designed vent system prepared by a certified vent manufacturer The following category II and IV optional vent materials shall be utilized -Stainless or AL29-4C for all system applications-PPE or polypropylene for all system applications -PVC for select low temperature systems only –consult factory-CPVC for domestic hot water systems and select low temperature systems –consult factory External Jacket and Fasteners: The external jacket shall be of 430 stainless steel mirror finish panels and a powder paint coated access top cover assembled utilizinginterference fit locks and minimal non-strip self tap screws for ease of removal and access to the heat exchanger and combustion air /gas control. Input & Output Model Input[MBTU/hr]Output[MBTU/hr] 0300 300 2820350350329 0400 399 375 0500 500 4700600600564 0800 800 752 1000 1000 940 1200 1200 1138140014001327 1600 1600 1517 1800 1800 1706200020001896 2500 2500 2370 3000 3000 2835350035003307 4000 4000 3780 4500 4500 4253500049994724 Heat Exchanger Water Content Model WaterContent(Gal) 300 5.7 350 5.7 400 6.35006.3 600 6.6 800 6.6 1000 8.912008.9 1400 9.6 1600 9.918009.9 2000 11.4 2500 13.2300015.6350018.6 4000 18.6450020.1500021.2 Voltage Requirement Model Voltage Requirement Max Amp Draw – Heater Only 300 - 2000 120VAC, 60Hz 20 2500 120VAC, 60Hz 30 3000- 3500 208/230VAC, 60Hz*30 4000 - 5000 208/230VAC, 60Hz, 3 Phase**30 1200 - 5000Δ 460VAC, 60Hz, 3 Phase 10 *This is a 4-wire power supply requiring two (2) lives, a neutral and a ground**This is a 5-wire power supply requiring three(3) lives, a neutral and a groundΔOptional power supply available uponrequest 99-0130Rev 06 SUBMITTAL DATA SHEET –DYNAFORCE®–DOMESTIC HOT WATER SUPPLY Engineer: _______________________Job Location: ______________________Date: ______________________________________ Prepared by: ____________________ ______________________ Buyer’s Name: _____________________ Quote #: ____________ Job Name: ______________________Buyer’s Address: _________________________________________ Recovery Capacity Model 100oFRiseGPH 56oCRiseLPH 80oFRiseGPH 44oCRiseLPH 60oFRiseGPH 33oCRiseLPH 0300 348 1,317 418 1,582 556 2,105 0350 406 1,536 487 1,843 650 2,461 0400 464 1,756 557 2,108 742 2,809 0500 581 2,199 697 2,638 930 3,520 0600 697 2,638 836 3,165 1,115 4,220 0800 929 3,516 1,115 4,220 1,486 5,625 1000 1,161 4,395 1,393 5,273 1,858 7,033 1200 1,405 5,318 1,686 6,382 2,248 8,510 1400 1,639 6,204 1,967 7,446 2,622 9,925 1600 1,873 7,090 2,248 8,510 2,997 11,345 1800 2,108 7,980 2,530 9,577 3,373 12,768 2000 2,342 8,865 2,810 10,637 3,747 14,183 2500 2,918 11,046 3,502 13,257 4,669 17,674 3000 3,502 13,257 4,202 15,906 5,603 21,210 3500 4,085 15,463 4,902 18,556 6,536 21,335 4000 4,669 17,674 5,603 21,210 7,470 28,277 4500 5,252 19,881 6,302 23,856 8,403 31,809 5000 5,836 22,092 7,003 26,509 9,338 35,348 Heat Exchanger Head Loss & Flow Model 10oF Rise 15oF Rise USGPM ∆P-Ft.USGPM ∆P-Ft. 300 57.0 0.5 38.0 0.3 350 66.5 0.7 44.3 0.4 400 76.0 1.0 50.1 0.5 500 95.0 1.6 63.3 0.8 600 113.9 2.5 75.9 1.3 800 152.0 6.6 101.3 3.2 1000 189.8 11.4 126.5 5.4 Model 20oF Rise 25oF Rise US GPM ∆P-Ft.US GPM ∆P-Ft. 1200 113.8 10.0 91.0 6.6 1400 132.8 14.0 106.2 9.2 1600 151.8 14.1 121.4 9.3 1800 170.9 14.3 136.7 9.4 2000 189.8 20.8 151.8 13.6 2500 237.2 27.1 189.8 17.7 3000 284.6 27.3 227.7 17.8 3500 331.8 33.0 265.4 21.5 4000 379.5 36.9 303.6 24.0 4500 426.9 55.8 341.5 36.3 5000 474.0 60.0 379.2 39.0 Dynaforce®Dimensions Model Ø Dim. "L"(in.) Air Inlet Ø Dim. "V" (in.)Vent CAT. IV up to100 Ft.Equiv.Length (AsShipped) Ø Dim. "V"(in.) VentCAT. II Dim. "M"(in.)Ø Dim. "W"(in.) Water Ø Dim. "X"(in.) Gas Weight (lbs.) 300 6 4 4 5 1 1/2 3/4 500 350 6 4 5 5 1 1/2 3/4 500 400 6 4 5 5 1 1/2 1 500 500 6 5 5 5 1 1/2 1 560 600 8 5 6 5 2 1 585 800 8 6 6 5 2 1 640 1000 8 6 7 5 2 1 750 1200 10 7 8 5 2 1/2 1 1/4 845 1400 10 7 8 5 2 1/2 1 1/4 845 1600 12 7 9 5 2 1/2 1 1/4 875 1800 12 8 9 5 2 1/2 1 1/4 1115 2000 12 8 10 5 3 1 1/4 1138 2500 12 9 10 5 1/2 3 1 1/2 1250 3000 12 9 10 5 1/2 3 1 1/2 1425 3500 12 10 12 7 4 2 1840 4000 12 10 12 7 4 2 1912 4500 14 12 12 7 1/2 4 2 1/2 2000 5000 14 12 12 8 4 2 1/2 2200 Please consult submittal drawings located onwww.camus-hydronics.com for detaileddimensional references. Model # ____________________________________# Of Units _________Type of Gas __________ Total Input ________________BTU/hr Total Output _______________BTU/hr Recovery Rate _______________USGPH @ _________0F Optional Accessories ________________________________________________________________________ WALL TYPE 02WALL TYPE 04 -RATED ELEVATOR CMU WALLFIRE RATING: 3 HR UL # (U914)SOUND RATING: STC ± 56 FOR CMU W/SOLID CORE7 5/8" CMU, MORTAR CORES SOLID1. INCLUDES A BEAD OF ACOUSTICAL SEALANT AROUND PERIMETER OF WALL, SEAL ALL PENETRATIONS AND HOLES.2. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 01 -RATED WALLFIRE RATING: 1 HR UL # (U465) SOUND RATING: STC ± 54 (RAL-TL90-344)6" METAL FRAMING @ 16" O.C.5/8" FIRECODE "X" GWB3" MIN. SOUND ATTENUATIONFIRE BLANKET, (SAFB)1/2" 25 GA. RESILIENT CHANNELS@ 16" O.C. VERTICALLY5/8" FIRECODE "X" GWB1. FIRE CAULK ALL PENETRATIONS.2. FIRE BLOCKING AT AIR SPACE PRE CODE3. EXTEND TO RATED HORIZONTAL ASSEMBLY.4. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 03 -RATED STAIRWELL WALL5/8" GWB1. FIRE CAULK ALL PENETRATIONS.2. FIRE BLOCKING AT AIR SPACE PRE CODE3. EXTEND TO RATED HORIZONTAL ASSEMBLY.4. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 07 -FURRING WALL3" MIN. SOUND ATTENUATIONFIRE BLANKET, (SAFB)6" METAL FRAMING @ 16" O.C.4" METAL FRAMING @ 16" O.C.5/8" GLASROC SHEATING TYPE XGYP. PANEL (2 LAYERS)3/8" GWBWALL TYPE 05 -UNRATED INTERIOR ACOUSTIC PARTITION5/8" GWB3" MIN. SOUND ATTENUATIONFIRE BLANKET, (SAFB)4" METAL FRAMING @ 16" O.C.5/8" GWBFIRE RATING: N/ASOUND RATING: STC ± 56WALL TYPE 04A -RATED INFILL CMU WALLFIRE RATING: 1 HR UL # (U914)SOUND RATING: STC ± 56 FOR CMU W/SOLID CORE5 5/8" CMU, MORTAR CORES SOLID1. INCLUDES A BEAD OF ACOUSTICAL SEALANT AROUND PERIMETER OF WALL, SEAL ALL PENETRATIONS AND HOLES.2. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 05A -UNRATED INTERIOR PARTITION5/8" GWB4" METAL FRAMING @ 16" O.C.5/8" GWBFIRE RATING: N/ASOUND RATING: STC ± 561. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 06 -UNRATED INTERIOR ACOUSTIC PARTITION5/8" GWB3" MIN. SOUND ATTENUATIONFIRE BLANKET, (SAFB)6" METAL FRAMING @ 16" O.C.5/8" GWB1. INCLUDES A BEAD OF ACOUSTICAL SEALANT AROUND PERIMETER OF WALL, SEAL ALL PENETRATIONS AND HOLES.2. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.1. INCLUDES A BEAD OF ACOUSTICAL SEALANT AROUND PERIMETER OF WALL, SEAL ALL PENETRATIONS AND HOLES.2. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 06A -UNRATED INTERIOR PARTITION5/8" GWB6" METAL FRAMING @ 16" O.C.5/8" GWBFIRE RATING: N/ASOUND RATING: STC ± 561. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.FIRE RATING: 1 HR UL # (U465) SOUND RATING: STC ± 54 (RAL-TL90-344)FIRE RATING: N/A SOUND RATING: STC ± 54 (RAL-TL90-344)WALL TYPE 8 -EXTERIOR WALLEXPOSED FACE OF EXISTING WALL TO REMAIN EXPOSED. GENTLY CLEAN SURFACE.EXTISTING EXTERIOR WALLFIRE RATING: NRSOUND RATING: NR5/8" GWB6" METAL FRAMING @ 16" O.C.FIRE RATING: N/ASOUND RATING: N/A1. INCLUDES A BEAD OF ACOUSTICAL SEALANT AROUND PERIMETER OF WALL, SEAL ALL PENETRATIONS AND HOLES.2. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 07A -FURRING WALL5/8" GWB4" METAL FRAMING @ 16" O.C.FIRE RATING: N/ASOUND RATING: N/A1. INCLUDES A BEAD OF ACOUSTICAL SEALANT AROUND PERIMETER OF WALL, SEAL ALL PENETRATIONS AND HOLES.2. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 07B -FURRING WALL5/8" GWB1 5/8" METAL FRAMING @ 16" O.C.FIRE RATING: N/ASOUND RATING: N/A1. INCLUDES A BEAD OF ACOUSTICAL SEALANT AROUND PERIMETER OF WALL, SEAL ALL PENETRATIONS AND HOLES.2. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.WALL TYPE 8A -EXTERIOR WALL1" SEMI-PERMEABLE RIGID FOAM EXTRUDED POLYSTYRENE INSULATION (R-5) FRICTION FIT AGAINST WALLVAPOR PERMEABLE AIR AND WATER BARRIER LIQUID-APPLIED MEMBRANEEXTISTING EXTERIOR WALLFIRE RATING: NRSOUND RATING: NRWALL TYPE 8B -EXTERIOR WALL1" SEMI-PERMEABLE RIGID FOAM EXTRUDED POLYSTYRENE INSULATION (R-5) FRICTION FIT AGAINST WALLVAPOR PERMEABLE AIR AND WATER BARRIER LIQUID-APPLIED MEMBRANEEXTISTING EXTERIOR WALLFIRE RATING: NRSOUND RATING: NR1 5/8" METAL FURRING STUD @ 16" O.C.1/2" AIR SPACE5/8" GWBVARIES1" VARIES5/8"1"1/2"1"VARIES3 1/8"WALL TYPE 9 -EXTERIOR BRICK VENEER WALLBRICK VENEER1" AIR SPACEFIRE RATING: 2 HR UL # (U349) SOUND RATING: NR1 1/2" RIGID INSULATIONFIRE-RATED OSB SHEATHING (2-SIDED)6" METAL STUDS2 LAYERS TYPE X 5/8" GWBWALL TYPE 9A -EXTERIOR BRICK VENEER WALLBRICK VENEER1" AIR SPACE1 1/2" RIGID INSULATION8" METAL STUDS3 1/2" MINERAL WOOL BATT INSULATION2 LAYERS TYPE X 5/8" GWB3 1/2" MINERAL WOOL BATT INSULATIONFIRE RATING: 2 HR UL # (U349) SOUND RATING: NRWALL TYPE 10 -EXTERIOR BOARD AND BATTEN WALLVERTICAL WOOD BOARD AND BATTEN1 1/2" RIGID INSULATION6" METAL STUDS2 LAYERS TYPE X 5/8" GWB3 1/2" MINERAL WOOL BATT INSULATIONFIRE RATING: 2 HR UL # (U349) SOUND RATING: NRFIRE-RATED OSB SHEATHING (2-SIDED)FIRE-RATED OSB SHEATHING (2-SIDED)BRICK VENEER1" AIR SPACEFIRE RATING: 2 HR UL # (U349) SOUND RATING: NR1 1/2" RIGID INSULATIONFIRE-RATED OSB SHEATHING (2-SIDED)4" METAL STUDS2 LAYERS TYPE X 5/8" GWB3 1/2" MINERAL WOOL BATT INSULATIONWALL TYPE 9B -EXTERIOR BRICK VENEER WALLWALL TYPE 07C -BEARING WALLSHEATHING (SEE STRUCTURAL DRAWINGS).6" METAL FRAMING @ 16" O.C.(SEE STRUCTURAL DRAWINGS).FIRE RATING: N/ASOUND RATING: N/AWALL TYPE 07D -RATED SHAFT WALL2 LAYERS 5/8" FIRECODE "X" GWB3" MIN. SOUND ATTENUATIONFIRE BLANKET, (SAFB)CONTINUOUS ACOUSTIC SEALANT AT ALL PERIMETERS.1. FIRE CAULK ALL PENETRATIONS.2. FIRE BLOCKING AT AIR SPACE PRE CODE3. EXTEND TO RATED HORIZONTAL ASSEMBLY.4. USE MOLD RESISTANT GWB ON BATHROOM, KITCHEN & LAUNDRY WALL SIDES.4" C-H METAL STUDS @ 16" O.C.1" GYPSUM LINER PANELFIRE RATING: 1 HR UL # (U437) SOUND RATING: STC ± 50 (RAL-OT-04-019)BRICK VENEER1" AIR SPACEFIRE RATING: 2 HR UL # (U349) SOUND RATING: NR1 1/2" RIGID INSULATION8" CMUWALL TYPE 12 -EXTERIOR BRICK VENEER WALLNOT USED 9ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1" = 1'-0"R.5WALL TYPESDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063No. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 WAW1W2W3W4W5W6W7W8W9A-A2.112A-A3.22A-A3.21A-A3.11A-A3.1A-A2.13A-A2.144A-D1.04A-D1.0W7AW7CW7AW7CW7CW7CW7CW7CW7CD-61NEW BEARING WALLS.SEE STRUCTURAL DRAWINGS.NEW SHAFT ABOVE.EXISTING CONCRETE LEDGE TO REMAIN.EXISTING CONCRETE ENCAST CAST IRON COLUMN TO REMAIN (TYPICAL).NEW 3' WIDE X4' HEIGH OPENING AT CRAWL SPACE BEARING WALLS.9F01ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"A-A1.0BUILDING A -LEVEL 0 PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"A-A1.01BLDG A - CRAWL SPACENo. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 WAW1W2W3W4W5W6W7W8W9A-A2.112A-A3.22A-A3.21A-A3.11A-A3.1UNIT A-1(2 BEDROOM)UNIT A-2(1 BEDROOM)55' - 5"UNIT A-3(2 BEDROOM)W5W5W1W5W1W5W1W5W1W1W5W7W15' - 5"4"8' - 11"2' - 0"19' - 5"2' - 9"6' - 10"4"4' - 4"3' - 6"3' - 6"2' - 5"6' - 6"10' - 2 7/8" 11' - 5 1/4" 8' - 5 1/4" 5' - 7 1/8"2' - 6"9' - 1 1/4"A-A2.149' - 4" 8' - 0" 8' - 0" 8' - 0" 8' - 1" 8' - 0" 8' - 0"9' - 10"W5TOILETTYPE-1TOILETTYPE-16' - 11 1/2"10' - 4 3/4"11 5/8"4' - 7 1/4" 3' - 5 3/8" 3' - 9 3/8" 5' - 7 1/4"KITCHENTYPE-1KITCHENTYPE-2KITCHENTYPE-3TOILETTYPE-2D-3D-3D-4D-2D-1D-4D-2BD-2D-1D-1D-2D-2BY3Y1TRANSOM WINDOW ABOVE9' - 4"W5W5W7AW7AW5W5W1W1W5W5W5A-2A-3A-2A-2A-2A-2A-2A-2A-2A-2A-2A-2A-2W1TRANSOM WINDOW ABOVETRANSOM WINDOW ABOVEW11/AB-A1.18' - 5"4" 11' - 7"4"2' - 10" 5' - 9"11"5' - 7"D-7D-37D-602' - 3 1/4"6' - 6"1' - 1 3/8"11' - 11 5/8"2' - 6"2' - 6"13' - 3"6' - 6"2' - 2"4' - 7"9' - 5"10' - 4"4"8' - 0"6"6' - 0"8"3' - 1"4" 4' - 4"D-4D-2D-2BD-4D-5BD-21' - 6 7/8"13' - 0 3/8"2' - 4 7/8"2' - 4 5/8"17' - 5 5/8"4 3/8"D-4D-3CD-3CD-5BW7AW51' - 10"STAIR A-1STAIR AB-150' - 2"50' - 2"63' - 7 3/4"CLOSETCLOSETCLOSETCLOSETCLOSETW11AB-A3.11AB-A3.12AB-A3.22AB-A3.22AB-A3.32AB-A3.38W2W28W7ESEQ EQ A-2W9BY37B-A5.67B-A5.6W5W5W5W5W5W5W5W5W7AW5PARTITION TAGS ADDEDBEDOOM 2BEDOOM 1COAT CLOSETLINENRAIN LEADER TO SPLASH BLOCK (TYP.)BEDOOMLINENCLOSETCOATCLOSETCORRIDORLINENCLOSETCOATCLOSETBEDOOM 2BEDOOM 1GUARD RAILINGW9AW9W7AScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"A-A1.1BUILDING A -LEVEL 1 PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063MARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"A-A1.11BUILDING A - LEVEL ONE, ENLARGED PLANABDECFGHJKLMNORTHSITE KEY PLANABNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/195 Addendum 04 4/23/196 Construction Set 6/11/199 Permit ReviewComments8/5/199999999 WAW1W2W3W4W5W6W7W8W92A-A3.22A-A3.21A-A3.11A-A3.167' - 5"UNIT A-4(1 BEDROOM)H.C.UNIT A-5(1 BEDROOM)UNIT A-6(2 BEDROOM)H.C.W5W1W5W5W5W1W1W1W1W5W5W5W5W5W54' - 2"4"10' - 4"8' - 1 1/2"3' - 1"16' - 1"2' - 6"15' - 8 7/8"5' - 1"4' - 6"6"10' - 4"15' - 2"3' - 6 1/8"2' - 4 7/8"5' - 1"8' - 11"4"11' - 3"4"9' - 10"5' - 1"6"8' - 5"4"2' - 3"19' - 2"10' - 6 5/8"2' - 6"11' - 7 1/8"2' - 3"2' - 9"1' - 1"5' - 2 1/4"8' - 11"4"3' - 8"4"11' - 0"6"9' - 11"4"7' - 11"6"14' - 3"4"3' - 4"4"6' - 2"7' - 0 1/4"9' - 0 5/8"A-A2.14A-A2.12W5W1W19' - 4" 8' - 0" 8' - 0" 8' - 0" 8' - 1" 8' - 0" 8' - 0" 9' - 4"TOILETTYPE-110' - 8"11' - 4"TOILETTYPE-3TOILETTYPE-3KITCHEN TYPE-49' - 10 5/8"2' - 1"9' - 10"8' - 11"4"3' - 8"4"2' - 8"4"6' - 2"1' - 10"6" 6' - 2"4"3' - 5"4"5' - 5" 2' - 6"6"8' - 0"4"5' - 11"4"2' - 1"4"7' - 5"2' - 4 7/8"3' - 6 1/8"KITCHENTYPE-5KITCHENTYPE-6D-2D-1D-3D-5D-2BD-4D-2D-4D-1D-3D-5D-2AD-2D-1D-3ED-4D-4D-2BD-2W2W2W1W1W7AW7AW5W5W5W5W5W5W7AW5W5W5W5W5W5W5W5W5W5A-1A-1A-1A-1A-1A-1A-1A-1A-4A-1A-1A-1A-1A-1A-1A-1A-1W1W11/A A3.3D-5D-7CLOSETCLOSET18' - 8"17' - 3"17' - 11 3/4"6' - 9 1/4"69' - 11"W5CLOSET8' - 11 1/8" 5' - 1"CLOSET 5' - 1 1/8"1AB-A3.11AB-A3.12AB-A3.22AB-A3.22AB-A3.32AB-A3.3EQ EQ W9BA-4D-38A-4SIMILAR WINDOW ABOVE4A-D1.04A-D1.08W2PARTITION TAGS ADDEDNEW PEDESTRIAN BRIDGE TO PARKINGCOATCLOSET LINENCLOSET BEDROOMBEDROOMCORRIDORCOATCLOSET LINENCLOSET W7A2' - 1"RAIN LEADER TO SPLASH BLOCK (TYP.)BEDROOM 1BEDROOM 2COATCLOSETLINENCLOSETSTAIR A-2STAIR AB-2AB CONNECTORDNW9W9ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"A-A1.2BUILDING A -LEVEL 2 PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"A-A1.21BUILDING A - LEVEL TWO, ENLARGED PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPABDECFGHJKLMNORTHSITE KEY PLANABNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/195 Addendum 04 4/23/196 Construction Set 6/11/199 Permit ReviewComments8/5/19999999 L2.2L2.EL2.FL2.GL2.HL2.JL2.KL2.ML2.NL2.1L2.L4B-A3.44B-A3.4BUILDING B31' - 2"29' - 3"31' - 2"29' - 3"STAIR 2ELECTRICAL METER ROOMMAINTENANCE ROOMBOILER ROOMSPRINKLER ROOMW1W1W1W5W3W3W1W1W1W119' - 4 1/4"9' - 2 1/4"6' - 0 3/8"6' - 10"29' - 4"12' - 5 1/8"19' - 0"25' - 1"10' - 0"9' - 1 3/8"25' - 3 1/4"23' - 10 5/8"14' - 0 3/8"17' - 11 3/4"18' - 1 1/8"15' - 1 1/8"31' - 4"9' - 4"8' - 2 7/8"35' - 7"18' - 11 3/8"6' - 1 1/2"25' - 7 1/4"10' - 3 3/4"4' - 2 1/4"4' - 3 3/4"7' - 9"9' - 8"1' - 0 3/8"1' - 2 7/8"5' - 9 3/8"13' - 1 1/2"2B-A3.22B-A3.23B-A3.33B-A3.3D-9BD-7D-9BD-9BD-9B1' - 3 7/8"3' - 0 1/8"3 1/8"2' - 11 5/8"6 5/8"EXISTINGSLABNEWSLABEXISTINGSLABNEWSLAB31' - 2"29' - 3"RAIN LEADER TO SPLASH BLOCK (TYP.)1B A5.1W5AW5A31' - 2"D-41D-40PARTITION TAGS ADDEDW5AW7AW5AUPCORRIDORCORRIDORCORRIDORScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"B-A1.1BUILDING BPLANS -LEVELSBDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.11BUILDING B - LEVEL SB, ENLARGED PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date1 Addendum 01 2/1/196 Construction Set 6/11/199 Permit ReviewComments8/5/1999999 L2.2L2.KL2.ML2.NL2.1L2.LB-A2.27UNIT B-1(2 BEDROOM)TYPE AW1W5W3W5W1W5W7W3W111' - 10"12' - 1 1/2"9' - 10"12' - 9 1/4"4' - 5 3/4"1' - 2"1' - 0"2' - 0" 25' - 11 7/8"18' - 2"11' - 10 1/8"15' - 8 5/8"5' - 10 1/2"17' - 0 3/8"9' - 6 3/8"5' - 5 1/4"7' - 7 3/4"2B-A3.22B-A3.21B-A3.11B-A3.136"TOILETTYPE-5KITCHENTYPE-72' - 7"5' - 7"2' - 0 7/8"2' - 0 7/8"D-7D-4D-4D-1D-2BD-2D-8D-6Y1TRANSOM WINDOW ABOVEW1W1W5W5W7AW5A-5A-5A-5D-2W5W711' - 2 7/8"W7D-32' - 4"5' - 0"4' - 0 1/4"2B A5.1W5AW5ANEW FLOOR INFILLPARTITION TAGS ADDEDCOAT CLOSETBEDROOM 1 BEDROOM 2CLOSETCLOSETMECH. CLOSETSTAIR B2UPDNCORRIDORRAIN LEADER TO SPLASH BLOCK (TYP.)W52' - 0"L2.2L2.CL2.DL2.EL2.FL2.GL2.HL2.JL2.KL2.14B-A3.44B-A3.4B-A2.28UNIT B-2(2 BEDROOM)2' - 0"MECHELEVATORW1W5W4W1W1W1W5W18' - 9 1/4"7' - 11 5/8"5' - 8"15' - 5 1/2"12' - 0 1/8"8' - 5"4' - 10 3/8"6' - 6 1/8"16' - 2 7/8"13' - 4 7/8"21' - 2 5/8"13' - 6 1/4"15' - 10 1/2"16' - 6 1/8"15' - 10 1/8"14' - 5 3/4"4' - 8 1/8"10' - 2"10' - 0 3/4"4"2' - 1 1/2"4' - 1 7/8"7' - 6 1/4"5' - 1 1/8"9' - 9"6' - 11"2' - 5"5' - 0 7/8"1' - 5 7/8"9' - 3 1/4"1' - 5 5/8"12' - 1 1/8"15' - 11"3' - 0 1/8"6' - 1"2' - 5"10' - 2"12' - 9 1/4"26' - 10 7/8"3' - 5 5/8"3' - 5 1/2"2B-A3.22B-A3.23B-A3.33B-A3.31B-A3.11B-A3.1KITCHENTYPE-8TOILETTYPE-410' - 9 7/8"2' - 7 1/4"2' - 7 1/4"4' - 10 3/8"10' - 3 1/8"D-8D-1D-2D-2D-4D-2BD-8D-4AD-6A-5W4W4W4W4NEW FLOOR INFILLW5AW5AW5ATRANSOM WINDOW ABOVEY3W7AW1W5W5W5W5W5W5W5W1W1W1PARTITION TAGS ADDEDLAUNDRYCOUNTERTOPWALK-IN CLOSETBEDROOM 1BEDROOM 26' - 0"2' - 1 1/2"CLOSETCOAT CLOSETCORRIDORMECH.CLOSETRAIN LEADER TO SPLASH BLOCK (TYP.)D-42CORRIDORB-A5.61D-3CF02D-3C4A6.33A6.33A6.3H.C. ACCESSIBLE WASHER AND DRYER999ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"B-A1.2BUILDING BPLANS -LEVEL BDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063MARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"B-A1.21BUILDING B - LEVEL B, ENLARGED PLAN (PART A)1/4" = 1'-0"B-A1.22BUILDING B - LEVEL B, ENLARGED PLAN (PART B)MATCH LINEMATCH LINEABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/195 Addendum 04 4/23/196 Construction Set 6/11/199 Permit ReviewComments8/5/199999 L2.2L2.AL2.BL2.CL2.DL2.EL2.FL2.GL2.HL2.150' - 2"50' - 2"UNIT B-4(2 BEDROOM)UNIT B-5(1 BEDROOM)UNIT B-6(1 BEDROOM)UNIT B-7(STUDIO)MECH. CLOSETMECH.CLOSETMECH.CLOSETMAILBOXESW1W1W5W5W1W5W1W4W4W5W5AW5W1W5W5W1W5W5W18' - 0 1/2"4' - 11"4' - 7"4"11' - 3" 4" 5' - 10"6"2' - 2" 4" 4' - 7" 8" 8' - 9" 1' - 3" 2' - 1"4"3' - 3" 4" 9' - 7"22' - 3"12' - 2 5/8"7' - 10"4"4' - 7" 4" 2' - 0"4"7"6' - 6" 10" 2' - 4"6"2' - 10"4"2' - 6" 7' - 1"6"5"8' - 7"4' - 6"6' - 4"6"6' - 4"4"5' - 10" 5' - 8"4"11' - 6"6' - 3" 8" 8' - 0" 1' - 0" 8' - 0" 4" 2' - 1"4"10' - 4"2' - 1 1/4"6' - 3"6"5' - 4" 4" 4' - 9"4"1' - 10"1' - 1"16' - 6"10' - 2"6' - 2"6"10' - 2" 4" 2' - 1"4"3' - 8"4"13' - 3"30' - 2 3/8"16' - 7 1/4"6" 4' - 7"4"2' - 7"4"8' - 9"6"2B-A3.22B-A3.23B-A3.33B-A3.3A-5A-5A-5A-5A-5A-7A-10A-5A-5A-5A-5A-5A-5A-5B-A6.42TOILETTYPE-6KITCHENTYPE-11KITCHENTYPE-12KITCHENTYPE-13TOILETTYPE-7TOILETTYPE-102' - 7 1/4"3' - 1 1/4"2' - 1 1/4"2' - 11"4' - 2"10' - 4"7' - 1"4"2' - 9"4"15' - 2"W5A6' - 1 1/2"4"2' - 2"4"3' - 4"2' - 2 1/8"5' - 9 1/8"2' - 10 3/4"D-1D-1D-2D-3CD-2D-2D-2BD-4D-3D-6D-2D-4D-6D-1D-3D-6D-4BA-7D-1TRANSOM WINDOW ABOVEW4W4W5AELEVATORW5W1W1W5AD-5AD-5AD-5AY3A-5W5W5W5W5W1W1W5W5W5PARTITION TAGS ADDEDCLOSETBEDROOMCOAT CLOSETLINENCLOSETCOAT CLOSETB-A5.62CORRIDORW5LINENCLOSETCLOSETBEDROOMCOATCLOSETLINENCLOS.CLOSETCORRIDORCORRIDORD-39W4AW4AVESTIBULE2' - 9"W7B2' - 2"2' - 8"L2.2L2.HL2.JL2.KL2.ML2.NL2.1L2.L4B-A3.44B-A3.4UNIT B-3(1 BEDROOM)TYPE 'A'UNIT B-4(2 BEDROOM)MECH. CLOSETMECH. CLOSET50' - 2"W1W5W1W1W1W5W1W5W6W5W34"9' - 10"5' - 7"24' - 3 3/4"9' - 10"15' - 9 5/8"30' - 2 7/8"5' - 6 5/8"3' - 4 3/8"2' - 0 7/8"3' - 2 3/4"5' - 7 5/8"10' - 2"10' - 2"12' - 2 1/8"1' - 10 7/8"12' - 11"6' - 0 7/8"5' - 4 1/4"6' - 6 1/2"14' - 6 1/4"11' - 4 1/4"6' - 7 3/8"14' - 1 1/2"4' - 1 1/2"4' - 2"14' - 1 1/2"2' - 5"5' - 2"4"1' - 11" 2' - 9"6"2' - 1" 5' - 1"2' - 0"4' - 8 1/4"2' - 1 1/4"7' - 9 1/8"16' - 5"10' - 0 1/2"17' - 2 7/8"7' - 8 3/4"2B-A3.22B-A3.22C-A3.12C-A3.1A-5A-5A-5A-5A-5A-5A-5A-5A-5A-5A-5A-5KITCHENTYPE-10B-A6.37TOILETTYPE-8TOILETTYPE-93' - 7 1/4"7' - 2 1/8"2' - 7 1/4"3' - 3 5/8"14' - 0 7/8"2' - 7 1/4"4' - 9 7/8"2' - 1"2' - 1"4' - 6"KITCHENTYPE-9D-7D-1D-4BD-4BD-2BD-2D-1D-2D-3D-1D-2D-2D-4BD-3D-6D-62B-A5.4TRANSOM WINDOW ABOVE2B-A5.52B-A5.51B-A5.41B-A5.4W5NEW FLOOR INFILL1B A5.2Y1A-6AAA-6AAA-6AAW5W5W7AW3W3W5W5W1W5W5W5W1W7AW1W7AW7ABEDROOMW5LINENCLOSETCLOSETW5AW5ASTAIR B2UPDNCOAT CLOSETBEDROOM 1 BEDROOM 2CLOSETCLOSETCORRIDORCOAT CLOSETRAIN LEADER TO SPASH BLOCK (TYP.)D-5ALINENW7AW52' - 0"ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"B-A1.3BUILDING BPLANS -LEVELONEDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.32BUILDING B - LEVEL ONE, ENLARGED PLAN (PART B)MARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"B-A1.31BUILDING B - LEVEL ONE, ENLARGED PLAN (PART A)MATCH LINEMATCH LINEABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/195 Addendum 04 4/23/196 Construction Set 6/11/199 Permit ReviewComments8/5/199999999 L2.2L2.AL2.BL2.CL2.DL2.EL2.FL2.GL2.HL2.160' - 8"UNIT B-10(1 BEDROOM)UNIT B-11(1 BEDROOM)UNIT B-12(1 BEDROOM)MECH.CLOSETW1W5W5W5W1W5W1W4W5W1W1W1W58' - 0 1/2"4' - 2 3/8"8' - 0 1/2"3' - 11"15' - 1 1/4"6" 4' - 7" 4" 11' - 3" 4" 5' - 10" 6" 2' - 2" 4" 4' - 7" 8" 8' - 9"1' - 3"2' - 6" 4" 2' - 10" 4" 9' - 6"6"9' - 1"6' - 4"6"6' - 4"4" 5' - 10" 5' - 8"4"11' - 6"9' - 8 5/8"9' - 5 1/4"9' - 0 3/8"10' - 2"5' - 10"30' - 2 3/8"2B-A3.22B-A3.23B-A3.33B-A3.3KITCHENTYPE-11KITCHENTYPE-12KITCHENTYPE-13W5W5W5MECH. CLOSET6' - 2" 6" 10' - 2"4"2' - 1"4"4' - 0" 13' - 3"2' - 8"5' - 10"2' - 1 1/4"3' - 1 1/4"2' - 7 1/4"W1W4W5W5W5MECH.CLOSET2' - 1 1/4"4' - 2"6' - 3" 6" 5' - 4" 4" 4' - 9" 4" 2' - 11" 16' - 6"2' - 2"7' - 0"4"2' - 10"4"15' - 2"6"8' - 9"4"2' - 7"4"4' - 7"6"10' - 5 7/8"2' - 10 1/2"7' - 10"4' - 0 5/8"30' - 1"11' - 6"22' - 3"TOILETTYPE-10TOILETTYPE-7TOILETTYPE-6OD-4AD-1D-2D-2D-2D-1D-2BD-4D-5BD-3D-6D-1D-3CD-2D-2D-5BD-4D-6D-3D-6A-6A-6A-6A-6A-6A-8A-6A-6A-13A-6A-7A-10A-6A-6A-6TRANSOM WINDOW ABOVEW4W4NEW FLOOR INFILLNEW WOOD FLOOR5' - 9"4"2' - 11"4"7' - 3"2' - 6"4"2' - 10"6"3' - 2"3' - 11"4"2' - 3"7"4"2' - 0"4"4' - 7"4"7' - 10"6"Y3W5W5W5W5W7AW1W1W1W5W1W5W5W7AW5W5W5W1PARTITION TAGS ADDEDCOAT CLOSETW5CLOSETLINENCLOSETBEDROOMCOAT CLOSETBEDROOMW5F21CLOSETCOATCLOSETELEVATOR8' - 0"1' - 0"2' - 11" 4" 4' - 9"4"2' - 1"4"LINENCLOS.CORRIDORB-A5.63BEDROOMWALK-INCLOSETW7B2' - 8"L2.2L2.HL2.JL2.KL2.ML2.NL2.1L2.LB-A2.27UNIT B-8(1 BEDROOM)TYPE AUNIT B-9(2 BEDROOM)MECH.CLOSETMECH.CLOSET60' - 8"W1W5W1W5W5W5W1W1W1W3W5W5W7W3W1W56' - 1 7/8"8' - 4 3/8"9' - 10"15' - 7 3/8"15' - 9 5/8"30' - 2 7/8"2' - 6" 4' - 1" 6" 10' - 2"4"3' - 3" 4" 2' - 1"4"9' - 10"12' - 2 3/4"2' - 7 1/4"4' - 9 7/8"1' - 10 7/8"4' - 6"2' - 1"2' - 1"4' - 1 3/8"10' - 2"12' - 10 3/4"6' - 0 7/8"17' - 5"5' - 4 1/4"14' - 0 7/8"14' - 6 5/8"2' - 6"2' - 1" 5' - 1" 4" 2' - 0"4"4' - 9"4"2' - 2"10' - 0 1/8"2' - 1"4' - 10"2B-A3.22B-A3.2TOILETTYPE-8KITCHENTYPE-9TOILETTYPE-9KITCHENTYPE-103' - 3 5/8"2' - 7 1/4"7' - 2 1/2"D-7D-1D-4BD-4BD-2BD-2D-1D-2D-3D-3AD-2D-2D-4BD-6D-6A-6A-6A-6A-6A-6A-6A-6A-6A-6A-6A-6A-6Y1TRANSOM WINDOW ABOVE4' - 0 1/8"6' - 6 1/2"3' - 2 3/4"2' - 0 7/8"5' - 7"4"3' - 4"2B A5.2NEW FLOOR INFILLA-6AAA-6AAA-6AAW5W5W1W5W5W1W5W5W5W5W7APARTITION TAGS ADDEDBEDROOMW5CLOSETLINENCLOSETW5AW5AW5ASTAIR B2UPDNCOATCLOSETCLOSET CLOSET BEDROOM 2BEDROOM 1COATCLOSETCORRIDORRAIN LEADER TO SPLASH BLOCK (TYP.)4" 2' - 0" 2' - 8"D-5AScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"B-A1.4BUILDING BPLANS -LEVELTWODakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.42BUILDING B - LEVEL TWO, ENLARGED PLAN (PART B)ABDECFGHJKLMNORTHSITE KEY PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"B-A1.41BUILDING B - LEVEL TWO, ENLARGED PLAN (PART A)MATCH LINEMATCH LINENo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/195 Addendum 04 4/23/196 Construction Set 6/11/199 Permit ReviewComments8/5/19999999 REF.REF.DWDWL2.2L2.AL2.BL2.CL2.DL2.EL2.FL2.GL2.HL2.1B-A2.2869' - 11"UNIT B-15(1 BEDROOM)UNIT B-16(1 BEDROOM)UNIT B-17(1 BEDROOM)W5W1W5W5W5W1W4W1W5W1W18' - 0 1/2"4' - 3"12' - 3 1/4"6' - 4 1/4"10' - 2"5' - 9 5/8"6' - 10" 6" 6' - 4"4"11' - 3"4"12' - 4"6' - 8" 6" 30' - 8"2B-A3.22B-A3.23B-A3.33B-A3.31B-A3.11B-A3.1KITCHENTYPE-11KITCHENTYPE-12KITCHENTYPE-13W5W5W5MECH.CLOSET6' - 8"6"10' - 2"4"2' - 1"4"3' - 8"4"13' - 9"4' - 7"4"2' - 1"4"6"5' - 4"4"2' - 8"5"5' - 9"6"2' - 2"4"4' - 7"8"8' - 9"8"8"5"2' - 1"4"2' - 10"4"9' - 7"2"4"9' - 6"3' - 1 1/4"2' - 6 5/8"MECH.CLOSET10' - 10"2' - 1 1/4"4' - 2"5' - 4 1/4"7' - 0 1/4"4' - 6 3/4"6"4' - 7"4"2' - 7"4"8' - 9"6"7' - 10"4"7' - 0"4"7"2' - 2"4"4' - 0"4"2' - 10"6"9' - 11"3' - 0"4"2' - 11"4"6' - 3"7' - 1 3/8"4"2' - 9 1/4"MECH4' - 2 3/8"2' - 7 1/4"22' - 9"7' - 10 1/4"4' - 1"30' - 7"2' - 3"6' - 3"4"2' - 11"4"3' - 0"9' - 6 1/8"W1W5W5W5TOILETTYPE-10TOILETTYPE-7TOILETTYPE-6A-13A-7A-10A-5A-5A-9A-9A-9A-9A-9A-9A-5A-5A-5A-9A-8D-1D-2D-2D-4AD-2BD-4D-5BD-3D-6D-4BD-2D-2D-5BD-4D-6D-3D-1D-1D-6D-2TRANSOM WINDOW ABOVENEW FLOOR INFILL10' - 5 7/8"14' - 7"10' - 0 5/8"ELEVATORW4W4W48' - 0"1' - 0"2' - 11"4"4' - 9" 4" 2' - 1" 4"8' - 9 1/4"Y3W5W5W5W1W1W1W7AW5W5W1W5W5W1W7AW5W5W5W1W1W1W5F21PARTITION TAGS ADDEDCOATCLOSETCLOSETLINENCLOSETBEDROOMCORRIDORCOATCLOSETLINENCLOS.CLOSETB-A5.64COATCLOSETBEDROOMBEDROOMWALK-INCLOSETCORRIDORW4AW4AW4AW4AL2.2L2.HL2.JL2.KL2.ML2.NL2.1L2.LB-A2.27UNIT B-13(1 BEDROOM)TYPE AUNIT B-14(2 BEDROOM)69' - 11"MECH.CLOSETMECH.CLOSETW1W5W1W1W1W5W3W5W5W55' - 6 5/8"9' - 10"8' - 4 7/8"9' - 10"4' - 9" 2' - 2"16' - 0 7/8"3' - 4 3/8"2' - 0 7/8"30' - 8 7/8"5' - 6 5/8"5' - 4 1/4"30' - 9 1/4"4' - 1 1/2"14' - 7"11' - 9 1/2"10' - 6 1/8"11" 2' - 1" 5' - 1" 4" 2' - 0" 4"4' - 9"2' - 1"2' - 6"6' - 6 7/8"2B-A3.22B-A3.21B-A3.11B-A3.1W5KITCHENTYPE-9KITCHENTYPE-1014' - 1 7/8"5' - 2"4"1' - 11" 2' - 10"4"7' - 3"4"2' - 7"4"6' - 6 1/2"3' - 3 5/8"14' - 6 7/8"12' - 6 1/8"2' - 7 1/4"4' - 9 7/8"1' - 10 7/8"2' - 1"4' - 2"TOILETTYPE-8TOILETTYPE-9A-5A-5A-5A-5A-5A-5A-8A-8A-8A-8A-8A-8A-8D-7D-1D-1D-2D-3D-5AD-4BD-2D-2D-6D-4BD-4BD-2BD-2D-6D-3AY1TRANSOM WINDOW ABOVE2B-A5.42' - 1"13' - 4 7/8"4' - 6"1B A5.3NEW FLOOR INFILLA-6AAA-6AAA-6AAW5W3W7AW3W3W5W5W5W5W5W1W1W1W5W1W5W5W5W5W5W5W5W5W5W5W7AW7AW7AW7APARTITION TAGS ADDEDBEDROOMCLOSETLINENCLOSETSTAIR B2UPDNCOATCLOSETCLOSET CLOSETCOATCLOSETBEDROOM 1 BEDROOM 2CORRIDORScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"B-A1.5BUILDING BPLANS -LEVELTHREEDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-0631/4" = 1'-0"B-A1.52BUILDING B - LEVEL THREE, ENLARGED PLAN (PART B)ABDECFGHJKLMNORTHSITE KEY PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"B-A1.51BUILDING B - LEVEL THREE, ENLARGED PLAN (PART A)MATCH LINEMATCH LINENo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/195 Addendum 04 4/23/196 Construction Set 6/11/199 Permit ReviewComments8/5/19999999 L2.2L2.AL2.BL2.CL2.DL2.EL2.FL2.GL2.HL2.1B-A2.2879' - 11"UNIT B-20(1 BEDROOM)UNIT B-21(1 BEDROOM)UNIT B-22(1 BEDROOM)W5W1W5W1W5W5W4W1W5W1W1W114' - 10 1/8"10' - 8 1/4"28' - 11 3/8"28' - 11 3/8"10' - 2"5' - 10"16' - 5 1/8"29' - 0"8' - 4 3/8"5' - 3 3/8"22' - 3"2B-A3.22B-A3.23B-A3.33B-A3.31B-A3.11B-A3.1KITCHENTYPE-11KITCHENTYPE-12KITCHENTYPE-13MECH.CLOSETW5W5W5MECH.CLOSETMECH.CLOSET5' - 3"6"10' - 2"4"2' - 1"4"3' - 8"4"12' - 2"3' - 1 1/4"2' - 7 1/4"5' - 4 1/4"7' - 0 1/4"13' - 0 3/4"5' - 0 1/4"1' - 10 1/4"4' - 1 1/4"2' - 1 1/4"TOILETTYPE-10TOILETTYPE-74' - 2"9' - 7 3/8"7' - 8"4"8' - 10 1/8"6"2' - 3 5/8"25' - 10 7/8"2' - 7 1/2"2' - 11 1/8"4"7' - 5 5/8"6"7' - 0"6"6' - 1"6"1' - 4"5' - 0"4"11' - 3"4"10' - 8"2' - 3"4' - 1 1/4"7' - 10 1/4"TOILETTYPE-6AD-1D-2D-2D-1D-2BD-4D-5AD-3D-6D-4BD-1D-2D-2D-6D-3D-4BD-5AD-1D-4AD-6A-13A-5A-54' - 1 3/4"11' - 3 1/4"11' - 7 3/4"10' - 6"4"4' - 3"3' - 0"NEW FLOOR INFILLC-1C-1C-1C-1C-1C-1C-1C-1C-12AB 1.2ELEVATOROVERRUNW4W4W48' - 9 1/4"7' - 11 5/8"C-1C-1C-1C-1C-1A-10A-10W5W5W5W7AW1W5W5W5W5W5W5W5W5W5W5W5W1W5W5W1W1W1W5W5W5W7AW1W1F22W5W5F22COATCLOSETBEDROOMLIVNG/DININGLINENCLOSET4' - 2"4"2' - 1"4"5' - 10"4"2' - 8"4"4"5' - 6"6"2' - 2"4"4' - 7" 8" 8' - 9"8"8"5"2' - 1" 4" 2' - 10"4"9' - 7"2"4"10' - 9"10"8' - 0"CLOSET4" 4' - 9"4"18' - 3"COATCLOSETLIVING/DINING1' - 0"2' - 11"4"4' - 9"4"CLOSETBEDROOMLINENCLOSETB-A5.65D-7COATCLOSETWALK-INCLOSETBEDROOMCORRIDORLIVING/DININGA-13C-2ABOVE3' - 2"6' - 6"4"2' - 1"4"2"4"4' - 7"4"7' - 7"6"9' - 0"4"2' - 7"4"4' - 2"6"L2.2L2.HL2.JL2.KL2.ML2.NL2.1L2.L4B-A3.44B-A3.4B-A2.27UNIT B-18(1 BEDROOM)UNIT B-19(2 BEDROOM)MECH.CLOSET79' - 11"W1W5W5W5W1W1W5W7W3W5W5W5W59' - 10"5' - 6 5/8"8' - 4 3/8"9' - 10"14' - 5 1/4"4' - 9" 2' - 2"15' - 5 1/8"3' - 4 3/8"2' - 0 7/8"3' - 7 3/4"16' - 2 5/8"19' - 5 1/8"5' - 6 5/8"6' - 0 5/8"28' - 11 5/8"12' - 2 1/8"10' - 2"2' - 7 1/4"4' - 9 7/8"1' - 10 7/8"4' - 9 7/8"2' - 1"2' - 1"4' - 1 3/8"8' - 5 7/8"10' - 11 1/2"11' - 7 1/2"9' - 0"2' - 1 1/2"1' - 11 5/8"6' - 7"2' - 6" 4' - 1"14' - 6"4"14' - 1 1/2"2' - 0"1' - 8 3/4"5' - 10"22' - 8 1/4"9' - 9 1/2"11' - 9 1/4"2' - 1 1/4"9' - 4"2' - 8 5/8"5' - 3 5/8"5' - 3 3/8"5' - 3 3/8"7' - 11 1/8"18' - 8"2B-A3.22B-A3.21B-A3.11B-A3.1KITCHENTYPE-9MECH.CLOSETKITCHENTYPE-10A5' - 3"6"5' - 4"4"6' - 7" 4" 2' - 7" 4" 13' - 6"W1TOILETTYPE-8TOILETTYPE-9D-7D-1D-4BD-4BD-2BD-2D-1D-2D-3D-2D-5D-4BD-3D-2D-6D-6A-11C-1C-1C-1C-1C-12B A5.311' - 7"NEW FLOOR INFILLC-1C-1C-1C-1C-1C-1W3W5W5W5W1W5W1W1W5W1W5W5W5W5W5W5W5W5W7AW1W7AW7AW7APARTITION TAGS ADDEDBEDROOMCLOSETLINENCLOSETLIVING/DININGSTAIR B2DNCOATCLOSETBEDROOM 1BEDROOM 2CLOSETCLOSETCOATCLOSETLIVING/DININGCORRIDOR7' - 3" 4" 2' - 7" 4"ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"B-A1.6BUILDING BPLANS -LEVELFOURDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063ABDECFGHJKLMNORTHSITE KEY PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"B-A1.62BUILDING B - LEVEL FOUR, ENLARGED PLAN (PART B)1/4" = 1'-0"B-A1.61BUILDING B - LEVEL FOUR, ENLARGED PLAN (PART A)MATCH LINEMATCH LINENo. Description Date1 Addendum 01 2/1/194 Addendum 03 4/12/195 Addendum 04 4/23/196 Construction Set 6/11/199 Permit ReviewComments8/5/1999999 OAO1O2O3O4O52D-A3.12D-A3.11D-A3.11D-A3.142' - 3 1/2"UNIT D-1(2 BEDROOM)UNIT D-2(1 BEDROOM)W1W5W5W5W1W5W1W1W1D-A2.112D-A2.115D-A2.113D-A2.114KITCHENTYPE-18KITCHENTYPE-17TOILETTYPE-16TOILETTYPE-1514' - 7" 6" 2' - 2"4"13' - 4"6"2' - 6"4"6' - 1"4"2' - 1" 4" 14' - 6"3"4' - 0"4"3' - 0"4"5' - 11"3' - 8"6"9' - 10"17' - 2" 6"4' - 6"4"5' - 0"8' - 10"4"2' - 2"4"2' - 4"4"2' - 10"4"10' - 1"8' - 6"4"11' - 4"4"3' - 2"4"2' - 2"4"6' - 0"20' - 2"4"12' - 0" 6" 7' - 6"6"16' - 9"3"2' - 11"4"5' - 6"7"6"3' - 7"7' - 4"6' - 9"2' - 5 7/8"6' - 1 1/4"3"7' - 0"4"10' - 7"4"4' - 11"4"4' - 0"3"4"3' - 9"4"3' - 3"3"W8BW8BW8BW8BW8BW8BW8BW8BW8BW8BW8BB-4AB-1AB-1AB-1AB-1AB-1AB-3AB-9AB-9AB-10AB-10AB-3AB-2AD-2D-4BD-2D-2AD-3D-2AD-5AD-2AD-4BD-3D-48D-47W5W5W5W5AW5AW7AW7W5W5W5W5W5W8BW5W5W5W5W5COATCLOSETLINENCLOS.CLOSETELECTRICALROOMBEDROOM 2CLOSETLINENCLOS.STAIR D1CLOSETBEDROOMPARTIAL HEIGHT WALLCOATCLOSETD-46RAIN LEADER (TYP.)2' - 3"4"17' - 7"4"6' - 6" 4" 5' - 2"6"3' - 7"4"3' - 7"6" 2' - 3"14' - 7"3"D-4BW5AW5ABEDROOM 1D-62B-11AW8B3" 2' - 2" 4"W1OAO1O2O3O4O52D-A3.12D-A3.11D-A3.11D-A3.153' - 7"UNIT D-3(2 BEDROOM)UNIT D-4(1 BEDROOM)W14' - 10 1/2"KITCHENTYPE-17KITCHENTYPE-18TOILETTYPE-153"14' - 10"4"2' - 1"4"13' - 4"6"2' - 6"4"6' - 1"4"2' - 1"4"14' - 6"3"3"4' - 6"4"9' - 10" 4" 2' - 1"4"10' - 2"3"4' - 6"3"8' - 6"4"15' - 10"4"5' - 1" 1' - 9"8"6"7' - 6"6" 16' - 9"3" 7' - 6"3"3" 4' - 8"4"4' - 1"4"7' - 8"4"10' - 2"3"2' - 2"24' - 8" 2' - 8" 5' - 2"6"7' - 6"6"2' - 2"4"2' - 8" 2' - 9" 8' - 10"4"3"3' - 0"4"5' - 6"7"6"3' - 7"7' - 4"6' - 9"3"3"4' - 1"4"4' - 11"4"10' - 1"4"2' - 8"4"4' - 6"3"3"8' - 9"3"5"4"9' - 2"3"8' - 6"3"8' - 9 7/8"W8BW8BW8BW8BW8BW8BTOILETTYPE-17B-6AB-4AB-1AB-1AB-1AB-1AB-1AB-1AB-2AB-1AB-1AB-1AB-1AB-1AB-1AB-1AAB-2AB-2AB-1AD-2AD-2D-4D-5D-2D-3D-4D-2AD-5AD-2AD-4BD-1D-3DD-1W8BW5W5W5W5W5W5W5W5W5W5W5W7AW7AW5W1W1W1W1W7AW7W5W5W5W1W5W5W5W5W5W5W8BW8BW8BW8BPARTITION TAGS ADDEDCOATCLOSETBEDROOM 1BEDROOM 2CLOSETCLOSETLIN.CLOS.LINENCLOSETCLOSETCOATCLOSETBEDROOMPART HEIGHT WALLSTAIR D1ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"D-A1.1BUILDING DPLANSDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063MARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"D-A1.11BUILDING D - LEVEL ONE, ENLARGED PLAN1/4" = 1'-0"D-A1.12BUILDING D - LEVEL TWO, ENLARGED PLANABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/197 Addendum 05 6/27/199 Permit ReviewComments8/5/199999999 3E-A3.13E-A3.11E-A3.11E-A3.142' - 11"W1W1W5W5W1RECEPTIONOFFICEOFFICEWAITINGAREAHC LAV.FILECABINETSJANITOR CLOSETMECHANICALROOMCONFROOMFITNESS ROOMW1W5W5COPYW5W5W523' - 11"6"4' - 1"6"4' - 5"6"7' - 7"4"11' - 9"4"8' - 10"3"3"27' - 8"3"3"15' - 2"6"5' - 11"6"5' - 7"3"10' - 1"6"10' - 2"1' - 3"5' - 7"3"3"23' - 11"6"4' - 1"6"4' - 4"6"5' - 2"4"2' - 2"4"12' - 7"4"7' - 11"3"3"9' - 1"4"8' - 1"4"4' - 5"4"5' - 1"3"3" 9' - 10"4"8' - 1"4"9' - 1"3"E-A2.118E-A2.119B-5AB-5AB-5AB-5A2E-A3.12E-A3.1KITCHENTYPE-20TOILETTYPE-18W8BW8BW8BW8BW8BW8BW8BD-8D-11D-10D-10D-9D-12D-13D-13D-11D-11D-9D-51D-50DROP CEILING ABOVEW1W1D-49D-51W1STAIR E1W8BW58' - 11"3"5' - 8"CORRIDORC-3C-31AB23E-A3.13E-A3.11E-A3.11E-A3.1UNIT E-2(1 BEDROOM)UNIT E-3(2 BEDROOM)W5W1W5W5W5W5W5W5W5W5W1W5W5W5W5W513' - 11"4"5"9' - 2" 6" 4' - 3" 6" 4' - 1" 1' - 4"4"2' - 9"7' - 1"4"15' - 3"4"2' - 2"3"3"2' - 9"5' - 4"4"2' - 1"4"3' - 2"3"13' - 11"4"1' - 10"4"7' - 5"6"4' - 3"6"6' - 6"4"4' - 3"4"2' - 2" 20' - 1" 3"3"12' - 8"4"2' - 1"4"1' - 1"5' - 1"4"5' - 8"3"3"7' - 5"13' - 4"6' - 10"3"6' - 11"2' - 9"4' - 1"4"2' - 1"4"11' - 2"3"4"3' - 7"4"2' - 1"4"3' - 7"3"1' - 3"5' - 7"4"2' - 1"4"4' - 2"4"13' - 7"3"3"9' - 1"4"11"4"17' - 0"3"3"13' - 11"4"9' - 7"6"4' - 3"6"11' - 1"4"7' - 7"4"14' - 4"3"3' - 9"3"6' - 3"4"1' - 8"4"1' - 0"4"17' - 8"3"E-A2.118E-A2.1192E-A3.12E-A3.1KITCHENTYPE-21KITCHENTYPE-22TOILETTYPE-19TOILETTYPE-20W8BW8BW8BW8BW8BW8BD-3D-5D-4D-2D-1D-1D-2AD-5AD-3D-4D-2D-2D-4B-5AB-5AB-5AB-5AB-5AB-5AB-5AB-7AE-1ABB-7A6' - 5"NEW FLOOR INFILLW8BW1W1W5W5W5W5W5W5W8BW5W5W7AW7W5W5W5COATCLOSETLINENCLOS.W7ACLOSETBEDROOMBEDROOM 1DNDNSTAIR E1STAIR E2STAIR E3BEDROOM 2CLOSETCOATCLOSETCLOSETLINENCLOS.ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"E-A1.1BUILDING EPLANSDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063ABDECFGHJKLMNORTHSITE KEY PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"E-A1.11BUILDING E - LEVEL ONE, ENLARGED PLAN1/4" = 1'-0"E-A1.12BUILDING E - LEVEL TWO, ENLARGED PLANNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/199 Permit ReviewComments8/5/199999999999 1F-A3.11F-A3.1F-A2.222F-A2.1214F-A3.14F-A3.111 3/4"8' - 4 1/2"ELEVATORJanW4W5Kitchenette15' - 3 1/8"4"6 7/8"2' - 11 3/8"4"4' - 6 3/8"7 1/2"5' - 9 1/2"7 1/2"5' - 11"6"5' - 11 1/4"4"3' - 11 5/8"6' - 1 3/4"4"3' - 6"Toilet7' - 2 3/4"NEW WALKWAY AND MEZZANINE ABOVEF-A2.2233F-A3.13F-A3.11F-A3.21F-A3.22F-A3.12F-A3.12F-A3.22F-A3.26' - 7"2' - 6"29' - 11"27' - 11"A-8AAA-8AAA-8AAStorageF-A6.11F-A6.16F-A6.19D-54D-9AD-2AD-2AToiletD-2ACOMMUNITY ROOM5' - 10"5' - 10 3/8"NEW TUBE STEEL COLUMNS BRACES AND STEEL FRAMING ABOVE. SEE STRUCTURAL DRAWINGS.1' - 3 1/4"4' - 6 1/4"4"2' - 5 3/4"4"20' - 5 1/2"6' - 7"21' - 1"6 3/4"16' - 1" 10' - 6 5/8" 9' - 1 3/8"5 7/8"27' - 11"W4W4W4W5W5W5W6W7AW5W5W7APARTITION TAGS ADDED99ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"F-A1.1BUILDING F PLAN-LEVEL 1DakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063ABDECFGHJKLMNORTHSITE KEY PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"F-A1.12BUILDING F - LEVEL ONE, ENLARGED PLANNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 BLDG F - LEVEL 127' - 10 7/8"BLDG F LEVEL 241' - 2 7/8"3F-A3.13F-A3.11F-A3.21F-A3.211' - 3 5/8"13' - 4"NEW TUBE STEEL COLUMNS AND FRAMING AT MEZZANINE (SEE STRUCTURAL DRAWINGS).W9BF13BLDG F - LEVEL 352' - 6 1/2"BLDG F - LEVEL 127' - 10 7/8"4F-A3.14F-A3.1BLDG F LEVEL 241' - 2 7/8"3F-A3.13F-A3.11F-A3.21F-A3.2NEW STEEL AND CONCRETE WALKWAY TO MECHANICAL MEZZANINE.NEW PREFIN ALUM ENTRYSYSTEM W/TRANSOM & SIDELIGHT W/TEMP & INSULATED GLASSNEW SINGLE PLY ROOF MEMBRANE ASSEMBLY ON 4.5" RIGID INSUL OVER EXISTING WOOD DECK2" PTD SQ STL TUBE FRAME W/PTD (OR COATED) WIRE FABRIC W/ PERIMETER FRAMEEXISTING STEEL BEAMS TO REMAIN.NEW ELEVATOR OVERRIDE.9BLDG F - LEVEL 127' - 10 7/8"1F-A3.11F-A3.1BLDG F LEVEL 241' - 2 7/8"13' - 4"2F-A3.12F-A3.12F-A3.22F-A3.2NEW CONCRETE AND STEEL MEZZANINE.NEW STRUCTURAL BRACING (SEE STRUCTURAL DRAWINGS).NEW COOLING TOWER ON HOUSEKEEPING SLABNEW 4" WOOD CLAPBOARD WALLSINGLE PLY ROOF MEMBRANE OVER TAPERED RIGID INSUL, MIN 3" T.BRICK PARAPET WITH CLAY TILE ROOF COPINGNEW CONCRETE SLABEXISTING STEEL STRUCTUREDEFLECTION TRACK @ TOP OF WALL W/ FIRE RATED SEALANT EACH SIDE & CONT FIRE SAFING INSULATION5/8" TAPED AND PTD 5/8" GWB OVER REINFORCED 8" CMU ELEVATOR SHAFT2" PTD SQ STL TUBE FRAME W/PTD (OR COATED) WIRE FABRIC W/PERIMETER FRAMENEW PREFIN ALUM BOX GUTTER OVER NEW FASCIA & SOFFIT ASSEMBLYNEW EXTERIOR WINDOW IN EXISTING OPENING.NEW EXTERIOR CONCRETE ROOF DECK.NEW PTD 8" GALV STL TUBE COLUMN (CLOSED TOP)NEW CLAY PARAPET ROOF TILES, MUDSET, OVER S.S. THROUGH-WALL FLASHINGNEW ALUM THRESHOLDBLDG F - LEVEL 352' - 6 1/2"NEW STEEL SHIPS LADDER TO MECHANICAL ROOF ABOVE.NEW LANDING AND STAIR.BLDG F - LEVEL 127' - 10 7/8"1F-A3.11F-A3.1BLDG F LEVEL 241' - 2 7/8"13' - 8"13' - 4"5' - 0"2F-A3.12F-A3.12F-A3.22F-A3.2NEW TUBE STEEL COLUMNS, STEEL FRAMING AND CONCRETE DECK AT MECHANICAL MEZZANINE.NEW EXTERIOR WALL BEYOND.NEW CONCRETE SLABAND ROOFING MEMBRANEEXISTING STRUCTURE BEAM TO REMAIN.NEW MEMBRANE ROOF SYSTEM OVER EXISTING WOOD DECKING.NEW BRICK VENEER CLAD ELEVATOR OVERRIDE.BLDG F - LEVEL 352' - 6 1/2"NEW D.H. WINDOW FIXED AND GLAZED WITH TRANSLUCENT GLASS AT ELEVATOR SHAFT.NEW CONCRETE UNDERPINNING OF EXISTING WALL AT NEW ELEVATOR PIT.PROVIDE WATERPROOFING AROUND NEW CONCRETE ELEVATOR PIT BEYONDScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"F-A3.1BUILDING FSECTIONDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063ABDECFGHJKLMNORTHSITE KEY PLAN1/4" = 1'-0"F-A3.11BUILDING F - CROSS SECTION 11/4" = 1'-0"F-A3.12BUILDING F - CROSS SECTION 21/4" = 1'-0"F-A3.13BUILDING F - CROSS SECTION 51/4" = 1'-0"F-A3.14BUILDING F - CROSS SECTION 4No. Description Date3 Permit Set 2/26/196 Construction Set 6/11/199 Permit ReviewComments8/5/19 ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROWF-A7.0FINISHSCHEDULE -BLDG FDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063No. Description Date3 Permit Set 2/26/199 Permit ReviewComments8/5/1999 10G-A3.410G-A3.4UNIT G-5(2 BEDROOM)UNIT G-6(1 BEDROOM)UNIT G-7(1 BEDROOM)G-A2.1311G-A3.411G-A3.43G-A3.13G-A3.11G-A3.11G-A3.1E-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATW232G-A3.12G-A3.1UNIT G-4(1 BEDROOM)UNIT G-3(1 BEDROOM)D-55D-1D-1D-2D-2D-4BD-3D-4BD-4AD-4AD-14D-3D-4BD-2D-1D-3D-3D-1D-1D-4BD-2D-4BD-1D-3D-1D-2D-1D-1D-113' - 0 1/2"5' - 11 1/8"10' - 7 1/4"6' - 8"2' - 4 3/4"10' - 2 1/4"10' - 5 1/8"2' - 4 3/4"6' - 4 1/4"10' - 4 7/8"10' - 2 1/4"2' - 4 3/4"6' - 1 3/8"10' - 7 3/4"10' - 4 7/8"6' - 4 1/4"2' - 4 3/4"10' - 4 1/4"7' - 2 1/2"3' - 5 1/4"9' - 6 1/4"9' - 2 3/8"16' - 2 1/8"2' - 6 1/4"10' - 7 3/4"10' - 4 7/8"2' - 6 1/4"16' - 7"7' - 2 1/2"2' - 6 1/4"10' - 5 1/4"9' - 1 1/2"10' - 1"12' - 0 7/8"5' - 10 3/8"14' - 6 5/8" 5' - 0 3/4"6' - 5 1/4"6' - 9 3/4"3' - 9 3/8" 5' - 11 1/4"2' - 6 1/4"6' - 7 1/4"5' - 4 5/8" 10' - 1"3' - 11 3/4" 4' - 1 1/2" 6' - 3" 3' - 11 1/4" 2' - 7 1/8"6' - 5 1/4"5' - 0 1/2" 11' - 4 7/8"6' - 6 3/8"6' - 3" 4' - 5 1/2" 3' - 7 3/4"10' - 1" 4' - 11"6' - 5 1/4"2' - 7 1/8"3' - 11 1/4"6' - 9"6' - 2 3/8"6' - 5 1/4"5' - 0 1/2"W5W5W5W1W1W1W1W1W5W5AW5AW5W1W1W5W5W5W5W1W5AW5AW5AW5AW1W1W5AW5AW5AW5W5W5W5W5W1W1W1W1W5AW5AW5AW5W5W5W5W5W1W5W5W5W5W5W5AW5AW5AW5AW1W5AW5AW5W1W1W1W1W1W1W7AW7AW7AW7AW7AW7AW7AW7AW7AW5W5AW5AW5AD-1D-2D-4BD-1KITCHEN(TYPE -23)KITCHEN(TYPE -24)D-5D-54' - 3 3/4"1' - 3 5/8" 4' - 9"5' - 4 1/8"1' - 8 1/4"D-5D-5TOILET(TYPE -26)TOILET(TYPE -24)KITCHEN(TYPE -23)TOILET(TYPE -24)TOILET(TYPE -25)KITCHEN(TYPE -24)TOILET(TYPE -25)STORAGE CLOSETH-2AE-1ACTW1CLOSETCLOSETCLOSETCORRIDORBEDROOM 1BEDROOM 1COATCLOSETLINENCLOSETBEDROOMLINENCLOSETCLOSETCOATCLOS.COATCLOS.LINENCLOSETBEDROOMCLOSETCOATCLOSETCOATCLOS.LINENCLOS.CLOSETLINENCLOS.CLOSET7' - 11 1/4"1' - 11 5/8"W5A30' - 5"830' - 5"8ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"G-A1.1BUILDING GLEVEL 1 PART ADakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063ABDECFGHJKLMNORTHSITE KEY PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"G-A1.11BUILDING G - LEVEL ONE, ENLARGED PLAN (PART A)MATCH LINE -SEE SHEET G-A1.2NEW 1 1/2" BRICK INFILLAT EXISTING HIGH WINDOW OPENING NEW WINDOW IN EXISTING REVISEDOPENING WITH NEW GRANITE WINDOWSILL AND BRICK INFILL BELOWNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/19MATCH LINE -SEE SHEET G-A1.29999999999 BUILDING H(SEE SHEET HJK-A1.1)30' - 5"30' - 5"UNIT G-1(2 BEDROOM)UNIT G-8(1 BEDROOM)UNIT G-9(1 BEDROOM)W1W13G-A3.13G-A3.11G-A3.11G-A3.1E-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-1ATE-3ATRANSOM WINDOW BOVEW22G-A3.12G-A3.1UNIT G-2(1 BEDROOM)UNIT G-3(1 BEDROOM)30' - 5"30' - 5"30' - 5"D-3D-2D-4BD-1D-3D-4BD-2D-1D-1D-4AD-2D-2D-1D-5AD-1D-3D-4BD-2D-1D-2B5' - 0 1/2"6' - 5 1/4"2' - 6 7/8"4' - 1 1/2"6' - 3"7' - 11 1/4"9' - 10 3/8" 10' - 1"8' - 1 1/4"6' - 3"3' - 11 1/4"2' - 7 1/8"6' - 5 1/4"4' - 9 1/2" 6' - 5 1/4" 2' - 7 1/8" 4' - 1 1/4"6' - 3" 1' - 10" 4' - 8 3/8"5' - 4 1/4"11' - 10 5/8"2' - 10 1/4"15' - 10 1/2"16' - 7 5/8"2' - 6 1/4"10' - 5 3/4"1' - 9 1/4"10' - 1 3/8"6' - 1 3/8"2' - 4 3/4"10' - 2 5/8"10' - 4 1/4"2' - 4 3/4"6' - 4 7/8"10' - 5 3/4"10' - 3 1/8"2' - 4 3/4"6' - 3 3/4"10' - 7 1/4"10' - 1 5/8"2' - 4 3/4"16' - 5 3/8"2' - 6 1/4"10' - 7 1/4"12' - 6 3/8"D-14' - 7 1/4"12' - 1 1/8"1' - 0 3/8"8' - 1 3/8"2' - 6 1/4"2' - 6 1/4"12' - 0 3/4"11' - 0 1/8"4' - 6 7/8"3' - 11 3/8"6' - 5 1/2"6' - 2 7/8"W1W5W5W1W5W5W5AW5AW5AW1W1W5AW5AW5W5W5W5W5W1W5AW5W1W1W1W5AW5AW5AW5AW5W5W5W5W1W5W5W5W5W5W5AW5AW5W5AW5W5W5W5W1W1W1W5AW1W1W1BOILER ROOMSPRINKLER ROOMW1W7AW7AW7AW7AW7AW7AW7AW7AW7AW5AD-3D-8D-8D-4D-4D-4AKITCHEN(TYPE -25)TOILET(TYPE -24)KITCHEN(TYPE -23)TOILET(TYPE -24)TOILET(TYPE -27)TOILET(TYPE -25)KITCHEN(TYPE -24)KITCHEN(TYPE -23)D-5D-5D-54' - 9" 1' - 8 7/8" 4' - 3 3/4"1' - 3 5/8"NEW WINDOW IN REVISED WINDOW OPENINGE-1AAE-1AAPARTITION TAGS ADDEDBEDROOMCLOSETCOATCLOSETLINENCLOSET2' - 0 5/8"2' - 1 1/2"COATCLOSETLINENCLOSETCLOSETBEDROOMBEDROOMBEDROOMBEDROOMCLOSETCLOSETWALK-INCLOSETY1WALK-INCLOSETCLOSETCOATCLOSETLINENCLOSET30' - 5"30' - 5"30' - 5"30' - 5"88ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"G-A1.2BUILDING GLEVEL 1 PART BDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063ABDECFGHJKLMNORTHSITE KEY PLANMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"G-A1.21BUILIDING G - LEVEL ONE, ENLARGED PLAN (PART B)MATCH LINE -SEE SHEET G-A1.1No. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/19MATCH LINE -SEE SHEET G-A1.1M AT C H L INE -SEE S H EET HJ-A1 .1 M AT CH L INE -SEE S H EET HJ-A1 .1 9999999 BUILDING HBUILDING JUNIT H-1(1 BEDROOM)UNIT H-2(2 BEDROOM)30' - 5"METERROOMLAUNDRYROOMBOILER AND SPRINKLERROOMJANITORMAILBOXESLOBBYW1W1W1W1W1W5W1W1W1W1W1W1W1W1W134' - 3 7/8"13' - 8"1' - 0"9' - 10"6"6"6' - 4"6" 1' - 11" 6" 9' - 11"13' - 6 5/8"13' - 5 7/8"32' - 4" 32' - 2"REFER TO BUILDING G FOR DIMENSION6' - 7 3/8"6' - 3"8' - 6 3/4"5' - 7 1/8"21' - 6 5/8"17' - 7 3/4" 10' - 5"6' - 2 1/8"2' - 0 7/8"2' - 0 7/8"4' - 3 5/8"10' - 7 1/8"10' - 7 3/8"1' - 8 3/8"3' - 1 1/4"10' - 3 3/4"9' - 8 1/8"9' - 6 7/8"3' - 7 3/8"19' - 6 3/8"9' - 10 1/8"4' - 8 1/2"10' - 0 7/8"10' - 2 7/8"19' - 7 1/2"20' - 7 1/8"4' - 0 5/8"9' - 10 1/8"1' - 9 7/8"2' - 7"4"4' - 9 1/4"9' - 10 1/8"11' - 2 1/8"6' - 3 1/4"2' - 7 3/4"REFER TO BUILDING J FOR DIMENSIONREFER TO BUILDING J FOR DIMENSION6' - 2 3/8" 12' - 1 3/8"18' - 4 1/8"15' - 11"12' - 1 1/4" 4' - 5 1/4"2HJ-A3.12HJ-A3.11HJ-A3.11HJ-A3.1D-2AD-2D-1D-2D-3DD-2D-4D-8D-8D-4AD-4AD-1D-1D-1D-2E-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1ATE-3AE-3AE-1AA88W1W1W1W1W1W5W5W5W5W5W1W5W5W5W7AW7AW5W5W5W5W7W7W5W58' - 5 1/2"3HJ-A3.13HJ-A3.11.G-A3.11.G-A3.14G-A3.14G-A3.1D-4D-2BD-4BD-2D-1D-4D-2D-2D-1D-5AD-4ABATHROOM(TYPE 31)D-2BKITCHEN(TYPE 27)BATHROOM(TYPE 32)KITCHEN(TYPE 26)NEW STRUCTURAL STEEL LINTEL ATNEW OPENING IN EXISTING MASONRY WALLMAILBOXES TRANSOM WINDOW ABOVEW5 Y1W1W5W7AW1W1D-3BEDROOM 1COAT CLOSETLINEN CLOSETW5CLOSETBEDROOM 230' - 5"D-4CW2W5W1F038830' - 5"30' - 5"30' - 5"888H.C. ACCESSIBLE DRYERH.C. ACCESSIBLE WASHER5A6.3999ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"HJ-A1.1BUILDING HPLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063MARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"HJ-A1.11BUILDING H - LEVEL ONE, ENLARGED PLANABDECFGHJKLMNORTHSITE KEY PLANMATCH LI N E TO S H EET G A1.2 M AT C H LINE TO SHEE T G A1.2 MATCH LINE TO SHEET K A1.1MATCH LINE TO SHEET K A1.1M ATC H L INE TO SHEET HJ -A1.3No. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/194 Addendum 03 4/12/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/1999999999999 BUILDING JUNIT J-7(1 BEDROOM)UNIT J-6(2 BEDROOM)UNIT J-5(2 BEDROOM)UNIT J-4(1 BEDROOM)UNIT J-3(2 BEDROOM)UNIT J-2(2 BEDROOM)30' - 5"W1W1W5W5W1W5W5W1W5W5W1W5W5W1W1W1W5W5W1W5W5W5W7AW510' - 1 1/4"17' - 1 3/4"8' - 0"2' - 6 1/2"9' - 0 3/4"2' - 0 7/8"5' - 4 1/4"2' - 7"10' - 2 1/8"6' - 2 1/8" 2' - 2 7/8"10' - 2 1/8"2' - 2 7/8"10' - 1 1/4"6' - 2 1/8"10' - 1 1/4"3' - 0 7/8"9' - 0 1/8"7' - 7 1/8"2' - 6 5/8" 1' - 10 1/8" 4' - 6 1/8"9' - 7 1/8"18' - 2 7/8"10' - 1 1/4"6' - 2 1/8"2' - 1 1/8"2' - 0 7/8" 11' - 11 5/8"10' - 1 1/4"15' - 2 1/2"2' - 8 7/8"9' - 2 3/8"1' - 9 1/8" 7' - 7 1/8"2' - 6 1/2"12' - 11" 20' - 10 1/2"27' - 9 3/4"10' - 2 1/4"6' - 2 1/8"2' - 0 7/8"5' - 0 1/8"4' - 10 1/8"10' - 2 1/4"11' - 11 1/8" 14' - 3 7/8"9' - 11 3/8"6' - 2 1/8"3' - 5 7/8"11' - 7 3/4"2' - 0 7/8"14' - 0 5/8"6' - 2 1/8"9' - 10 7/8"2' - 0 7/8"10' - 1 3/8"6' - 2 1/8"4' - 9 1/4"5' - 0 1/8"2' - 0 7/8" 11' - 10 7 /8" 14' - 3 7/8"10' - 1 3/8"27' - 8"9' - 2 3/8"2' - 1 5/8"2' - 6 1/2"8' - 0"12' - 5 7/8"33' - 5"20' - 9 5/8"8' - 0 7/8"5' - 1 1/2"5' - 11 3/4"5' - 11 3/4" 6' - 0 5/8"3HJ-A3.23HJ-A3.27' - 8 1/4"D-2D-2D-2D-4AD-4AD-1D-3DD-2D-2AD-4D-2AD-2D-2D-4AD-4AD-3DD-3CD-1D-2AD-3DD-4AD-2AD-2AD-4D-1D-5AD-2D-4AD-2D-2AD-3D-1E-4AE-4AE-4AE-4AE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAH-2AH-2AD-4AD-4AW55' - 0"10' - 0"10' - 0"D-5AD-5A4' - 0 1/2"4' - 1 3/8"4' - 0 1/2"4' - 0 1/2"4"1' - 4 1/4"4"BATHROOM(TYPE 33)BATHROOM(TYPE 34)KITCHEN(TYPE 31)BATHROOM(TYPE 40)3' - 6 3/8"4"1' - 4 1/4"4"4' - 5 1/4"D-5AKITCHEN(TYPE 32)BATHROOM(TYPE 38)BATHROOM(TYPE 39)KITCHEN(TYPE 33)BATHROOM(TYPE 37)KITCHEN(TYPE 30)1HJ-A3.21HJ-A3.2W5W5W5W5W7AW1W1W5W5W5W5W5W5W5W7AW5W5W5W5W5W7AW5W5W1W1W5W5W5W5W7AW5W5W5W5W5W5W5W7AW5W5W5W5W5W1W1W5COAT CLOSETLINEN CLOSETCLOSETCLOSETBEDROOM 2BEDROOM 2WALK-INCLOSETCLOSETCLOSETLIN.CLOS.BEDROOMCORRIDORCORRIDORD-57COATCLOSETCOATCLOSETBEDROOM 1BEDROOM 1CLOSETCOATCLOSETLINENCLOSETCLOSETCLOSETBEDROOM 2BEDROOM 1COAT CLOSETLINENCLOSETCLOSET30' - 5"830' - 5"8ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"HJ-A1.2BUILDING J PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063MARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"HJ-A1.21BUILDING J - LEVEL ONE, ENLARGED PLAN (PART B) M ATCH LI NE MATCH LI NE ABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/1999999999999 BUILDING JUNIT H-2(2 BEDROOM)UNIT J-8(2 BEDROOM)UNIT J-7(1 BEDROOM)UNIT J-2(2 BEDROOM)UNIT J-1(2 BEDROOM)METERROOMW1W1W1W1W5W5W1W7AW5W5W1W1W1W5W5W12' - 1 1/8"7' - 1 1/4"10' - 8 7/8"12' - 0"22' - 8 7/8"10' - 2 1/8"10' - 2 1/8"6' - 2 1/8" 2' - 2 7/8" 12' - 1 5/8" 7' - 7 1/8"2' - 6 5/8"12' - 0 3/8"4' - 0 7/8"5' - 10"2' - 1 1/8" 6' - 2 3/8" 6' - 2 3/8" 6' - 0 3/4"7' - 3"10' - 1 1/4"10' - 11 3/4" 2' - 2 7/8"10' - 1 1/4"6' - 2 1/8"17' - 8"20' - 0 5/8"5' - 10 3/8"2' - 0 7/8"9' - 0 3/4"2' - 6 1/2"8' - 0"2' - 7"14' - 7 3/8"4"5' - 1 1/4"10' - 2 1/8"15' - 3"10' - 0"22' - 6 5/8"10' - 1 1/4"2' - 1" 11' - 11 5/8"10' - 1 1/4"6' - 2 1/8"12' - 0 3/8"4' - 0 7/8"5' - 10 3/8"2' - 1 1/8" 7' - 7 1/8"2' - 6"12' - 11 5/8" 6' - 2 1/8"10' - 2 1/8"11' - 11 5/8" 4"2' - 1"10' - 2 1/8"5' - 9 5/8"2' - 9 7/8"10' - 1 1/8"2' - 1 1/4"7' - 7 1/8"2' - 6 5/8"12' - 11 5/8"19' - 4 1/2"20' - 10 5/8"4HJ-A3.24HJ-A3.22HJ-A3.22HJ-A3.220' - 10 5/8"HJ-A6.21HJ-A6.22D-2AD-1D-2AD-2AD-2AD-1D-3DD-5AD-4AD-4AD-2D-2D-2AD-1D-4AD-4AD-3DD-2AD-4AD-4AD-3CD-2AD-4AD-4AD-2D-1D-2D-1D-2D-3DD-2D-4D-3CD-1D-4E-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAE-1AAD-5AD-5A4' - 0 1/2"4' - 1 3/8"4' - 0 5/8"4' - 0"D-4A9' - 9 1/4"4' - 11 7/8"D-5ABATHROOMTYPE 32KITCHENTYPE 28KITCHENTYPE 29KITCHENTYPE 34KITCHENTYPE 35BATHROOMTYPE 35BATHROOMTYPE 361HJ-A3.21HJ-A3.2W1W1W5W5W5W7AW5W5W5W5W5W5W5W5W5W58W5W1W1W5W7AW5W5W5W5W5W1W1W58W5PARTITION TAGS ADDEDBEDROOM 2BEDROOM 1WALK-INCLOSETCOATCLOSETLINENCLOSETCLOSETCLOSETCLOSETCLOSETLINENCLOSETCOATCLOSETCORRIDORCORRIDORCOATCLOSET4' - 0 1/2"4"4' - 0 1/2"4"1' - 4 1/4"4"1' - 5 1/8"4"4' - 0 1/2"4"4' - 0 1/2"CLOSETLINENCLOSETCLOSETCLOSETCLOSETW5W5LINENCLOSETCOATCLOSETBEDROOM BEDROOM 2BEDROOM 1WALK-INCLOSETBEDROOM 1CLOSETD-4A30' - 5"8ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"HJ-A1.3BUILDING J PLANDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063MARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUP1/4" = 1'-0"HJ-A1.31BUILDING J - LEVEL ONE, ENLARGED PLAN (PART A) MATCH LI N E M AT C H L INE ABDECFGHJKLMNORTHSITE KEY PLANNo. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/19999999999 K-A2.1312HJ-A3.12HJ-A3.11K-A3.11K-A3.12K-A3.12K-A3.13HJ-A3.13HJ-A3.13K-A3.13K-A3.1E-3AE-3AE-3AE-3AE-3AE-3AE-3AE-3AE-3AE-3AE-3AE-3AE-3AD-4D-4BD-4BD-2D-2D-2D-2D-5D-3DD-1D-1D-26D-4AD-3DD-3D-4AD-4AD-2AD-5AD-5AD-2AD-2D-4AD-4AD-9G6" 3' - 8"6" 10' - 9" 4"20' - 5" 6"10' - 3" 4"17' - 11" 4"10' - 0"UNIT K-2(2 BEDROOM)UNIT K-4(1 BEDROOM)UNIT K-1(1 BEDROOM)UNIT K-3(1 BEDROOM)TOILETTYPE 41TOILETTYPE 43TOILETTYPE 40TOILETTYPE 42KITCHENTYPE 36KITCHENTYPE 37KITCHENTYPE 38KITCHENTYPE 39MATCH LINE TO M.A1.1MATCH LINE TO M.A1.2MATCH LINE TO G.A1.2MATCH LINE TO HJ.A1.1MATCH LINE TO HJ.A1.1WINDOW ABOVEWINDOW ABOVEWINDOW ABOVEWINDOW ABOVEWINDOW ABOVEWINDOW ABOVEWINDOW ABOVEWINDOW ABOVEWINDOW ABOVEWINDOW ABOVEWINDOW ABOVEBEDROOM 1CLOS.CLOS.LINENCLOS.COATCLOSETCLOSETBEDROOM 2COATCLOS.LINENCLOSETBEDROOMCLOSETBEDROOMCLOS.CLOS.IDFCLOSETF-1F-1F-1F-1H-1AF-1F-1E-3AF-1F-1F-1F-1F-1F-1H-1A12' - 8"4"2' - 1"4"5' - 1"1' - 1"6"6' - 3"6"10' - 7"4"2' - 1"4"5' - 1"1' - 1"6"6' - 3"6"3' - 7"4"17' - 8"10' - 2"8"4"8' - 4"6"6' - 3"6"5' - 2"6"2' - 2"4"13' - 5"4"2' - 1"4"7' - 7"9' - 3"4"4' - 3"4"1' - 10"4"3' - 1"6"6' - 3"6"3' - 1"4"1' - 10"4"4' - 3"4"11' - 5"13' - 9"5"6"1' - 6"6"6' - 3"6"2' - 1"4"12' - 5"10' - 7 "6" 6' - 10"4"3' - 8"6" 1' - 1" 5' - 1"4" 2' - 1" 4"5' - 6"4" 5' - 6"6" 2' - 2"6" 7' - 5"6" 10' - 1" 4"2 ' - 1" 4" 5' - 2" 4"1' - 4" 4" 4' - 0" 4" 4' - 0" 18' - 6" 4' - 3" 59' - 4" 10' - 8"6" 5' - 7" 4" 5' - 8" 6" 6' - 2"4" 2' - 1" 4"4' - 11"4" 8' - 1"6" 8' - 2"4" 2' - 6"4" 5' - 2"4" 1' - 4" 4" 4' - 1"4"4' - 1" 6"8' - 8" 2' - 6"D-5WINDOW ABOVEWINDOW ABOVELIN.CLOS.COATCLOS.D-3DBEDROOMCLOS.CLOS.LIN.CLOS.D-2W5W5W5W5W5W5W1W7AW7AD-1W5W5W5W1W5W5W5W1W1W1W1W1W1W5F31W5F312' - 2"W5W5W5W5W5W5W6W1W1W1W1W1W1W1W5W7AW7AW5W5W1W1W1W5W5W6W5W7AW7AW1W5W5W5W5W5W1W1W5W1W7AW1W5W1W5W5W52' - 7"D-1W5W5W5W5W5W5W5W7AW7AW130' - 5"30' - 5"D-888W1W1ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"K-A1.1BUILDING K -LEVEL 1DakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063No. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/1910 Addendum 08 Date 101/4" = 1'-0"K-A1.11BLDG K - LEVEL 1 NEWMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPABDECFGHJKLMNORTHSITE KEY PLAN999999999999 33M-A2.1393M-A3.23M-A3.2E-2AE-2AE-2AE-2AE-2AE-2AE-2AE-1AAE-1AAE-1AAE-1AAE-2AE-2AE-2AE-2AE-2AD-1D-3DD-2D-5D-4D-3BD-4BD-3D-1D-5DD-2D-4BD-2D-2D-59D-4D-2D-3AD-2D-2D-1D-3DD-5BD-2D-4AD-2D-4AD-2BD-4BD-4BD-8UNIT M-1(1 BEDROOM)UNIT M-2(2 BEDROOM)UNIT M-6(2 BEDROOM)UNIT M-7(2 BEDROOM)BEDROOM 2BEDROOM 1CLOSETCLOSETCORRIDORCORRIDORCOATCLOSETCOATCLOSETCOATCLOSETLINENCLOS.CLOSETBEDROOMCLOSETBEDROOMLINENCLOS.CORRIDORBEDROOMCLOSETCLOSETLINENCLOSETCOATCLOSETBEDROOM 2BEDROOM 1CLOSETCLOSETLINENCLOSETCOATCLOSETKITCHENTYPE 46TOILETTYPE 48KITCHENTYPE 46TOILETTYPE 48KITCHENTYPE 42TOILETTYPE 46TOILETTYPE 45KITCHENTYPE 41TRANSOM WINDOW ABOVED-16"4' - 5"6"18' - 5"4"10' - 3"6"25' - 5"4"2' - 1"4"12' - 1"6"2' - 10"6' - 11"4"10' - 10"4"2' - 1"4"10' - 3"6"2' - 9"6' - 10"4"15' - 6"4"2' - 1"4"5' - 7"6"6' - 0"6' - 0"6"7' - 8"4"11' - 11"4"3' - 1"4"7' - 4"2' - 9"6"2' - 10"7' - 4"4"10' - 8"4"3' - 7"4"11' - 1"6"6' - 3"6"5' - 11"6"2' - 2"4"1' - 10"6"18' - 5"4"10' - 1"6"10' - 2"4"26' - 0"6"6' - 3"6"3' - 1"6"10' - 4"4"2' - 1"6"6' - 3"6"5' - 1"6"4' - 3"4"9' - 8" 6"5' - 6" 6" 2' - 6"6"10' - 5" 4"10' - 4" 2' - 1"4" 10' - 10"4"2' - 1" 4"5' - 1" 1' - 2" 6"5' - 6"6"5' - 1" 11" 6"7' - 7" 4"9' - 7" 2' - 1"2' - 7"10' - 8" 4"2' - 1" 4" 4' - 1" 4"2' - 10" 4" 3' - 1" 6"5' - 6" 6" 1' - 2" 5' - 1" 4"2' - 1" 4" 10' - 10" 11' - 7"4" 7' - 8"6"5' - 6"6"5' - 1"11"6"7' - 7"4"5' - 6"6"3' - 7" 6' - 7"6"3' - 8"6"30' - 5"30' - 5"30' - 5"W5W1W1W1W1W1W1W1W1W1W5W5W5W5W5W5W5W5W5W6W5W1W7AW7AW5W5W5W5W5W5W5W1W1W1W1W5W5W5W6W7AW7AW1W1W1W12' - 8"W5W5W5W5W5W5W5W5W7AW7AW5W52' - 7"4"1' - 10"1' - 10"4"W7AW7AW5W5W5W5W5W5W5W5W52' - 8"888ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"M-A1.4BUILDING MPLAN -LEVEL 1PART ADakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063No. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/191/4" = 1'-0"M-A1.41BLDG M - LEVEL 1 - PART A M ATC H L INE -SE E S H EET M -A1.5 MARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPABDECFGHJKLMNORTHSITE KEY PLANMATCH LI N E -S EE SHE E T M -A1.5 99999999999 33M-A2.137M-A2.1381M-A3.11M-A3.14M-A3.24M-A3.2UNIT M-8(2 BEDROOM)UNIT M-9(2 BEDROOM)UNIT M-3(2 BEDROOM)UNIT M-10(2 BEDROOM)UNIT M-4(2 BEDROOM)TRANSOM WINDOW ABOVEKITCHENTYPE 47TOILETTYPE 49BEDROOM 1BEDROOM 2CLOSETCLOSETCOATCLOSETLINENCLOSETBEDROOM 1BEDROOM 2CLOSETCLOSETCOATCLOSETLINENCLOSETKITCHENTYPE 46TOILETTYPE 48KITCHENTYPE 47TOILETTYPE 49BEDROOM 1BEDROOM 2COATCLOSETLINENCLOSETCLOSETCLOSETKITCHENTYPE 44TOILETTYPE 47TOILETTYPE 46TOILETTYPE 45BEDROOM 1BEDROOM 2CLOSETCOATCLOSETLINENCLOS.CLOSETCLOSETLINENCLOS.BEDROOM 2COATCLOSETKITCHENTYPE 43BEDROOM 2CLOSETCLOSETE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2AE-2A6"10' - 3"4"18' - 4"6"4' - 5"6"23' - 3"4"10' - 3"6"10' - 2"4"23' - 3"6"4' - 5"6"2' - 7"2' - 8"6"2' - 7"6"10' - 3"4"2' - 1"4"10' - 9"4"6' - 10"2' - 10"6"2' - 9"6' - 11"4"10' - 10"4"2' - 1"4"10' - 3"6"10' - 2"4"2' - 1"4"10' - 10"4"6' - 11"2' - 9"6"D-2D-3DD-1D-5BD-4AD-4AD-2D-4AD-4AD-2D-2D-5BD-3DD-1D-2D-2D-1D-3DD-5BD-2D-4AD-2D-4AD-2D-4AD-2D-3AD-4D-2D-2D-5D-4D-2D-5D-1D-3AD-2BD-4BD-4BD-26"6' - 3"6"11' - 1"4"3' - 7"4"8' - 2"4"7' - 4"2' - 10"6"2' - 9"6' - 10"4"13' - 5"4"3' - 7"4"10' - 6"4"3' - 1"6' - 10"6"6"6' - 3"6"2' - 7"20' - 11"4"1' - 9"4"8' - 1"6"7' - 5"4"1' - 10"4"25' - 8"2' - 7"4"4' - 8"4"5' - 0"6"D-26"6' - 3"6"2' - 1"4"9' - 0"6"3' - 1"6" 3' - 4"6" 6' - 10" 6"10' - 8"4"2' - 1"4"10' - 7"10' - 7"4"2' - 1"4"5' - 1"1' - 5"6"5' - 6"6"24' - 0" 3' - 7"6"5' - 6"4" 7' - 7"6"11"5' - 1"6" 5' - 6"6" 2' - 2" 4"5' - 2"4" 11' - 10" 10' - 8" 4"2' - 1"4" 4' - 1"4" 2' - 10"4" 3' - 1"6" 5' - 6"6" 1' - 2" 5' - 1"4" 2' - 1" 4"10' - 10" 9' - 7"4" 7' - 7"6" 6' - 1" 6" 5' - 6" 6"7' - 8" 4"11' - 7"2' - 1" 4" 2' - 2" 3' - 1"4"2' - 10"4"W1W1W1W5W1W7AW7AW6W1W1W5W5W5W5W5W5W5W5W5W1W5W5W5W5W5W5W5W5W5W5W5W6W7AW7AW1W5W1W1W1W1W5W6W5W7AW7AW1W5W5W5W5W5W5W5W5W5W1W130' - 5"30' - 5"88W1W1W5W1W5W5W5W5W5W7AW7AW5W5W5W5W1W5W5W7AW7AW5W5W5W1W5W1W1W5W5W5W5W5W7AW7AW5W5W5W5W1W5ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"M-A1.5BUILDING MPLAN -LEVEL 1PART BDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063No. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/191/4" = 1'-0"M-A1.51BLDG M - LEVEL 1 - PART BMARK Description8 EXISTING BRICK WALLEB EXISTING BRICK WALLEC EXISTING CONCRETE WALLES EXISTING STONE WALLEW EXISTING WOOD WALLW1 UNIT SEPARATION WALLW2 EXISTING BRICK WALLW3 STAIRWELL WALLW4 8" CMU WALLW4A 6" CMU WALLW5 4" STUD NON-ACOUSTIC INTERIOR PARTITIONW5A 4" STUD ACOUSTIC INTERIOR PARTITIONW6 6" STUD ACOUSTIC INTERIOR PARTITIONW6A 6" STUD NON-ACOUSTIC INTERIOR PARTITIONW7 6" FURRING WALLW7A 4" FURRING WALLW7B 1 7/8" FURRING WALLW7C 6" BEARING WALLW7D 4" SHAFT WALLW8B 1-5/8" FURRING WALLW9 EXTERIOR BRICK VENEER WALL WITH 6" STUD BACKUPW9A EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPW9B EXTERIOR BRICK VENEER WALL WITH 4" STUD BACKUPW10 EXTERIOR BOARD AND BATTEN WALL WITH 6" STUD BACKUPW11 INFILL BRICK WALL-15"W12 EXTERIOR BRICK VENEER WALL WITH 8" STUD BACKUPABDECFGHJKLMNORTHSITE KEY PLANM ATC H L INE -SE E S H EET M -A1.4 MATCH LI N E -SE E SHEE T M-A1 .4 MATCH LINE -SE E SHEE T M-A1 .6 MATCH LINE -SE E S HEE T M-A1.6 99999999 335M-A3.25M-A3.2E-2AE-2AE-2AE-2AE-1AE-1AE-1AE-1AE-2AE-2AE-2AE-2AD-2D-4AD-3D-1D-2D-2D-4D-2D-1D-2D-3DD-8D-4D-596"10' - 2"4"2' - 7"15' - 3"4"1' - 8"4"8' - 2"6"10' - 11"6"10' - 2"4"10' - 0"4"2' - 1"4"5' - 0"4"7' - 4"2' - 10"6"10' - 11"11' - 1"6"9' - 8"4"2' - 7"4"5' - 7"4"6' - 10"2' - 10"6"4' - 9"6"5' - 11"6"2' - 6"16' - 0"4"1' - 10"4"7' - 6"6"UNIT M-5(2 BEDROOM)UNIT M-11(2 BEDROOM)SPRINKLER ROOMCLOSETCOATCLOSETKITCHENTYPE 45TOILETTYPE 45TOILETTYPE 49KITCHENTYPE 46BEDROOM 1WALK-INCLOSETBEDROOM 2LINENCLOSETCLOSETBEDROOM 1BEDROOM 2CLOSETCOATCLOSETD-5AD-414' - 6" 4"5' - 0" 6"5' - 6" 6" 15' - 1" 4" 2' - 1"6" 11"5' - 1"6" 5' - 6"6" 7' - 8" 4"11' - 10" 10' - 10" 4" 2' - 1" 4" 5' - 1" 1' - 3" 6" 5' - 6" 6"7' - 7" 4" 16' - 1" 1' - 9"4" 4"3' - 1" 6"3' - 6" 6"7' - 0" 6"1' - 11"6"10' - 2"W1W5W5W5W6W7AW7AW5W1W5W5W5W5W1W1W1W1W1W1W5W5D-5LINENCLOS.W1W1W5W1W5W5W5W5W5W5W5W1W5W7AW7AW5W5W5W1W130' - 5"30' - 5"88ScaleDateDrawn ByChecked ByProject NumberUNCASVILLE, CT42 PINK ROW1/4" = 1'-0"M-A1.6BUILDING MPLAN -LEVEL 1PART CDakotaPartners, Inc.OXOBOXOLOFTSCheckerAuthor10/12/201816-063No. Description Date1 Addendum 01 2/1/193 Permit Set 2/26/196 Construction Set 6/11/198 Addendum 06 7/15/199 Permit ReviewComments8/5/191/4" = 1'-0"M-A1.61BLDG M - LEVEL 1 - PART C MATCH LINE -SE E SHEE T M-A1.5 M ATCH LINE -SEE S HEET M -A1.5 9999999 WA L2.2 L2.A L2.B L2.C L2.D L2.E L2.F L2.G L2.H L2.J L2.K L2.M L2.N L2.1 O1 O2 O3 O4 O5 W1 W2 W3 W4 W5 W6 W7 W8 W9 L2.L BUILDING G BUILDING D BUILDING B (LEVEL 3)BUILDING C BUILDING A UNIT A-4 (1 BEDROOM) H.C. UNIT A-5 (1 BEDROOM) UNIT A-6 (2 BEDROOM) H.C. UNIT B-13 (1 BEDROOM) TYPE A UNIT B-14 (2 BEDROOM) UNIT B-15 (1 BEDROOM) UNIT B-16 (1 BEDROOM) UNIT B-17(1 BEDROOM) HP-1 HP-1 HP-1 D-250 D-250 B-15010"ø 12"ø R6-600 THP-1 T C-200 B-150 B-150 A-100 HP-1 R-600 6"ø 12"ø 10"ø T HP-1 C-175 B-125 B-125 C-175 R6-60012"x10" 12"ø 9"ø10"ø 7"ø 8"ø A-75 A-75 10"x4"12"x6"6"x6"T 10"x8"6"x6"10"x8"4"x4"4"ø4"øT T 6"x6" 4"ø 4"ø T 6"x6"4"ø4"ø4"ø HP-6 HP-6 G-150 I-300 12x12 SAPLENUM G-12510x10 SAPLENUM T HP-6 E1-20 E1-20 E1-20 VD VD VD R2-290 10x10 RA DUCT DN 12x12 RA DUCT UP A-75 B-150 HP-6 G-125 I-275 T HP-6 10x10 SAPLENUM E1-20 VD E1-20 E1-20 E1-20 VD VD VD A-75 HP6 G-125 G-125 HP-6 12x12 SAPLENUM I-275G-125 H-200 T E1-20 E1-20 OA TO HP6(TYP OF ALL) HP-6 E1-20 VD VD 8x8 EA DUCT UP8x6 EA DUCT DN 8x10 EA DUCT UP, 8x8 EA DUCT DN E1-20 E1-20E1-20 E1-20 E1-20 E1-20 4"ø 4"x4" 4"ø 4"ø4"x4"4"ø 8"ø10"ø14x12 SA DUCTUP, 12x12 SADUCT DN,PROVIDE FIREDAMPER ATDECK R4-175 H-200 4x4 OA DUCT UP 4x6 OA DUCT DN 6x4 EA DUCT DN4"ø4x6 EADUCT DN 6"x4"8x8 OA DUCT UP8x6 OA DUCT DN OA CONNECTION TO HP6(TYP. OF 2) 4"ø RA-600 HP-6 RA-600B-3506"x4"4"x4"4"ø RA-400 4"ø4"x4"-275 RA-400 RA-6008"ø B-150 36" LONG ELECTRIC BASEBOARD HEATER 4"x4"4"x4" 4"ø FD FD FD FD FD R6-600 12"x10" 12"ø T HP-6 8X8 SA DUCT DN AXG AXGAXG AXG AXG AXG AXG AXG AXGAXG OA TO HP6(TYP OF ALL) 8X8 OA DUCT UP,8X6 OA DN 8X10 EA DUCTUP, 8X6 EA DN EWH-6 OA WA L2.2 L2.A L2.B L2.C L2.D L2.E L2.F L2.G L2.H L2.J L2.K L2.M L2.N L2.1 O1 O2 O3 O4 O5 W1 W2 W3 W4 W5 W6 W7 W8 W9 L2.L 9 9 9 Scale Date Drawn By Checked By Project Number UNCASVILLE, CT 1/8" = 1'-0" ABC-MD1.3 MECHANICAL DUCTWORK PLAN BLDGS 'A', 'B', 'C'- LEVEL 3 Dakota Partners, Inc. OXOBOXO LOFTS DA RS 11/01/2017 16-063 A B D E C F G H J K L M NORTH SITE KEY PLAN No.Description Date 9 Permit ReviwCommets 08/05/2019 UNIT B-1(2 BEDROOM)TYPE A UNIT B-2(2 BEDROOM) UNIT C-3(2 BEDROOM)TYPE A UNIT C-4(2 BEDROOM)TYPE A ELEVATOR BUILDING B BUILDING CBUILDING A BUILDING G BUILDING D A A A A A C C CC C C C C C B B B B B B B B B B B B B B B B B B B B B B B B C TPC4 TPC4 - 10 TPC4 - 3 TPC3 C C TPC3 - 10 TPC3 - 3 TPC4 - 10 TPB1 TPB2 TPB2 - 10 TPB2 - 3 C C C C C TPB1 - 3 TPB1 - 10 XE XE XE XE XEC HPB1 - 25 HPB1 - 25 TYP OF CORRIDOR LIGHTING ON BB OA WA L2.2 L2.A L2.B L2.C L2.D L2.E L2.F L2.G L2.H L2.J L2.K L2.M L2.N L2.1 O1 O2 O3 O4 O5 W1 W2 W3 W4 W5 W6 W7 W8 W9 L2.L XHC 9 XHC 9 Scale Date Drawn By Checked By Project Number UNCASVILLE, CT 1/8" = 1'-0" ABC-EL1.B ELECTRICAL LIGHTING PLAN BUILDINGS B-C LEVEL B Dakota Partners, Inc. OXOBOXO LOFTS DA RS 11/01/2016 16066.01 A B D E C F G H J K L M NORTH SITE KEY PLAN No.Description Date 9 Permit ReviewComments 08/05/2019 BUILDING G BUILDING D BUILDING B BUILDING C BUILDING A UNIT A-4(1 BEDROOM)H.C. UNIT A-5(1 BEDROOM)UNIT A-6(2 BEDROOM)H.C. UNIT B-13 (1 BEDROOM)TYPE A UNIT B-14(2 BEDROOM) UNIT B-15(1 BEDROOM) UNIT B-16 (1 BEDROOM) UNIT B-17 (1 BEDROOM) C BE B B B C TPB17 - 10 TPB17 C C C E B B B TPB16 - 10TPB16- 3 TPB16 C B B B C TPB15 - 10 C E TPB15 - 3 TPB14 BB B B C C TPB14 - 3 E B TPB14 - 10 B BB C C B C B B C TPB13 - 3 TPB13 - 10 TPB13 A A AAAAA A C C C C C C E E B B B B B B B BB B B B B TPA4 TPA6 TPA5C TPA4 - 10 TPA4 - 3 TPA5 - 10 TPA5 - 3 TPA6 - 10 TPA6 - 3 XEEM XEC XE EM EM A A HPB1 - 28 HPB1 - 28 CORRIROR LIGHTING ON THIS LEVEL A&B TO HPB1 CIRCUIT 28 B C OA WA L2.2 L2.A L2.B L2.C L2.D L2.E L2.F L2.G L2.H L2.J L2.K L2.M L2.N L2.1 O1 O2 O3 O4 O5 W1 W2 W3 W4 W5 W6 W7 W8 W9 L2.L HEHC 9 Scale Date Drawn By Checked By Project Number UNCASVILLE, CT 1/8" = 1'-0" ABC-EL1.3 ELECTRICAL LIGHTING PLAN BLDGS A-B-C LEVEL 3 Dakota Partners, Inc. OXOBOXO LOFTS DA RS 11/01/2016 16066.01 A B D E C F G H J K L M NORTH SITE KEY PLAN No.Description Date 9 Permit ReviewComments 08/05/2019 DN BUILDING D UNIT D-1(2 BEDROOM) UNIT D-2(1 BEDROOM) RECEPTION OFFICE KITCHEN OFFICE WAITINGAREA HC LAV. JAN. MECH'L CONFROOM FITNESSROOM BUILDING E B B B B B B B B C C C E E C D TPD1 - 10 TPD2 - 3 TPD2 - 10 HPE - 9 C C E HPE HPE - 11 HPE - 10 XE XE XE EM C C C C HPE - 9 HPE - 9 XE 1 A B 2 OAL2.A L2.B L2.C L2.D O1 O2 O3 O4 O5 CCC ELECTRICAL ROOM BEDROOM 1 BEDROOM 2 HPE - 20 XEHC9 XEHC 9 BUILDING D BUILDING E UNIT D-3(2 BEDROOM) UNIT D-4(1 BEDROOM) UNIT E-2 (2 BEDROOM)UNIT E-3 (2 BEDROOM) TPD4 C B B CB B C C B B TPD3 TPD3 - 3 TPD3 - 10 C TPD4 - 3 C C B TPD4 - 10 D D B B B B B B B B B B TPE3 C C CC E TPE3 - 3 C CC D TPE2 D D TPE2 - 10TPE2- 3 TPE3 - 10 HPE - 9HPE- 9 EM EM EM 1 A B 2 OAL2.A L2.B L2.C L2.D O1 O2 O3 O4 O5 Scale Date Drawn By Checked By Project Number UNCASVILLE, CT 1/8" = 1'-0" DE-EL1.1 ELECTRICAL LIGHTING PLAN BLDGS D-E - LEVELS 1 AND 2 Dakota Partners, Inc. OXOBOXO LOFTS Checker Author 11/01/2016 16066.01 A B D E C F G H J K L M NORTH SITE KEY PLAN No.Description Date Comments 08/05/20199 Permit Review ? ? COMMUNITY ROOM (OPEN ABOVE) KITCHENETTE JANTOILET FITNESS ROOM (OPEN ABOVE) TOILET C C CC CC C C E E CC HPF - 31 TO LTG ABOVE TO LTG ABOVE XHC 9 BOILER ROOM FITNESS ROOMBELOW COMMUNITY BELOW TOILETSBELOW A A AA A A AA A A C C C C HPF - 31 HPF TO SWITCH BELOWTO SWITCH BELOW XEHC 9 Scale Date Drawn By Checked By Project Number UNCASVILLE, CT 1/8" = 1'-0" F-EL1.1 ELECTRICAL LIGHTING PLANS BLDG F - LEVELS 1 AND 2 Dakota Partners, Inc. OXOBOXO LOFTS Checker Author 11/01/2016 16066.01 A B D E C F G H J K L M NORTH SITE KEY PLAN No.Description Date 9 Permit ReviewComments 08/05/2019 3 333 33BUILDING K BUILDING H BUILDING G B B B B BB BB B C C E CC C B B B B E E E E E E C C C E B B EC B TPG9 TPG9 - 10 TPG9 - 3 TPG8 TPG7 TPG8 - 3 TPG8 - 10 TPG7 - 3 TPG6 - 10 TPG5 - 3 TPG6 TPG5 TPG2 TPG1 TPG3 TPG4 TPG6 - 3 TPG3 - 10 TPG4 - 10 TPG1 - 10TPG2- 10 TPG3 - 3 XE EM EM UNIT G-5(2 BEDROOM) UNIT G-6 (1 BEDROOM) UNIT G-7(1 BEDROOM) UNIT G-8 (1 BEDROOM) UNIT G-9 (2 BEDROOM) UNIT G-4 (1 BEDROOM) UNIT G-3(1 BEDROOM) UNIT G-2(1 BEDROOM) UNIT G-1 (2 BEDROOM) LAUNDRY ROOM UNIT G-9(1 BEDROOM) TPG7 - 10 TPG5 - 10 TPG2 - 3 TPG1 - 3 TPG4 - 3 D B B B1 B BB B DB B B D C B B D B B B B B B1 D B D B B D B BDB B B D ? B A A A A A A A XEC A XEC A A A A A A B B B B B B TPK2 B B TPK4 BB B A A A HPH1 - 20 G G G G D TPH1D TPH1 - 10 E C C E D C E TPK4 - 10 HPH1 - 20 XF XF XF XF L2.M L2.N L2.L XHC 9 Scale Date Drawn By Checked By Project Number UNCASVILLE, CT 1/8" = 1'-0" GH-EL1.1 ELECTRICAL LIGHTING PLAN BUILDING 'G' AND 'H' Dakota Partners, Inc. OXOBOXO LOFTS DA RS 11/01/2016 16066.01 A B D E C F G H J K L M NORTH SITE KEY PLAN No.Description Date 9 Permit ReviewComments 08/05/2019 33333333 333 C CC B B B B B B B B B B B B B B B B B B BB B BBBB B B B B B BB B B B B B B B B B B B B B B B B B B B B B B B B B B B C E E TPM10 TPM10 - 10 TPM10 - 10 TPM10 - 10 TPM10 - 10 TPM10 - 3 TPM11 TPM11 - 10 TPM11 - 3 TPM11 - 10 TPM11 - 10 TPM11 - 10 TPM5 TPM5 - 3 TPM5 - 10 TPM5 - 10 TPM5 - 10 TPM5 - 10 TPM4 TPM3 E C E C D E C C A TPM4 - 10 TPM4 - 10 TPM4 - 10 TPM4 - 15 TPM4 - 10 TPM4 - 3 E D D TPM3 - 10 TPM3 - 10 TPM9 TPM9 - 10 TPM8 TPM7 - 10 TPM8 - 10 TPM8 - 3 TPM7 TPM7 - 3 TPM6 - 3TPM6- 10 TPM1 - 3 TPM1 - 10 TPM2 TPM2 - 3 TPM2 - 10 XE XEC XEC EM EM A A A A A A A A A A A A A A A HPH1 - 22 HPH1 - 22 HPH1 - 22 UNIT M-11(2 BEDROOM) UNIT M-10(2 BEDROOM) UNIT M-9(2 BEDROOM) UNIT M-8 (2 BEDROOM)UNIT M-7(2 BEDROOM) UNIT M-6(2 BEDROOM) UNIT M-1 (1 BEDROOM) UNIT M-2(2 BEDROOM) UNIT M-3(2 BEDROOM) UNIT M-4 (2 BEDROOM) UNIT M-5(2 BEDROOM) XF XF XF XF XE XF 3 XEHC 9 UNIT L-1(2-BEDROOM) C HPL HPL - 6 E F F F F G G G G MAINTENANCEOFFICE/ STORAGE Scale Date Drawn By Checked By Project Number UNCASVILLE, CT 1/8" = 1'-0" LM-EL1.1 ELECTRICAL LIGHTING PLAN BLDGS L AND M LEVEL 1 Dakota Partners, Inc. OXOBOXO LOFTS DA RS 11/01/2016 16066.01 A B D E C F G H J K L M NORTH SITE KEY PLAN No.Description Date 9 Permit ReviewComments 08/05/2019 J S S 3,5 3/5 1/3/5 3 HOMERUN CIRCUIT SYMBOLS 120 OR 277 VOLT 120 OR 277 VOLT 208 OR 480 VOLT 208 OR 480 VOLT SINGLE PHASE CIRCUIT PHASE CIRCUITSCONSECUTIVE SINGLE SINGLE PHASE CIRCUIT THREE (3) PHASE CIRCUIT (3 POLE) (2 POLE) S C F S S TS FACP FS IA FAAP S S/CO W F L TV S/CO NOTE: SEE SHEET P-1.0 FOR SITE LIGHTING DRAWINGS AND SITE LIGHTING FIXTURESCHEDULE. SEE BELOW CALCULATIONS. 34.3% OF THE SITE LIGHTING IS PHOTOVOLTAICPOWERED WITH INTEGRAL BATTERY STORAGE SO IT DOES NOT CONNECT AT ALL TO THEBUILDINGS ELECTRICAL POWER DISTRIBUTION SYSTEM. ENERGY USAGE CALCULATIONS PV:(25 FIX)(55 WATT/FIX)(12 HR/DAY)(365 DAY/YEAR)(1 KW/1,000 W) = 6,023KW/YEAR HARDWIRE: POLES - (6 FIX)(55 WATT/FIX)(12 HR/DAY)(365 DAY/YEAR)(1 KW/1,000W) = 1,445 KW/YEARHARDWIRE: BOLLARDS - (43 FIX)(17.1 WATT/FIX)(12 HR/DAY)(365 DAY/YEAR)(1KW/1,000 W) = 3,221 KW/YEARHARDWIRE: HAND RAILS - (820 FIX)(1.9 WATT/FIX)(12 HR/DAY)(365 DAY/YEAR)(1KW/1,000 W) = 6,824 KW/YEAR TOTAL HARDWIRE - 1,445 + 3,221 + 6,824 = 11,490 KW/YEAR % OF SOLAR = [6,023/(6,023 + 11,490)] = 34.4% NOTE: WHEN A FEEDER SUPPLIES AN ISOLATED GROUND PANEL OR SUB PANEL, AN ADDITIONAL GROUND WIRE SHALL BE PROVIDED WITH AND IDENTIFIED BY GREEN INSULATION WITH A YELLOW STRIPE. THE ISOLATED GROUND WIRESHALL BE ROUTED THROUGH PANELS IN ACCORDANCE WITH NEC SECTION 384-20 AND TERMINATE AT THE BUILDING INCOMING SEVICE. STANDARD FEEDER SIZES FOR 75°C THWN/THHN COPPER WIRE IN METAL OR NON-METALLIC CONDUIT HORN UNIT WITH ADA COMPLIANT STROBE WITHREQUIRED CANDELA (cd) RATING. HORN UNIT ONLYIF WITHIN APARTMENT/DWELLING UNIT SPEAKER UNIT WITH ADA COMPLIANT STROBE WITHREQUIRED CANDELA (cd) RATING 1-250MCM3-500MCM(5) 4"26A (7) 4" (11) 4" (8) 4" (6) 4" (14) 4" (16) 4" 30A 31A 32A 28A 29A 27A 3-500MCM 3-500MCM 3-500MCM 3-500MCM 3-500MCM 3-400MCM 1-500MCM 2-350MCM 2-500MCM 1-350MCM 1-400MCM 1-250MCM (4) 4" (5) 4" (5) 4" (2) 4" (2) 3" (2) 3" (2) 3" 23A 24A 25A 22A 21A 20A 19A (2) 3" (2) 2-1/2" 15A 18A 17A 16A 14A 13A 12A 3-1/2" 3-1/2" 3" 3" 2-1/2" 3-350MCM 3-300MCM 3-400MCM 3-400MCM 3-500MCM 3-500MCM 3-350MCM 1-#3/0 1-#4/0 1-#4/0 1-#2/0 1-#1/0 1-#1/0 1-#1 3-500MCM 3-250MCM 3-#4/0 3-500MCM 3-350MCM 3-250MCM 3-#4/0 1-#3 1-#2 1-#2 1-#3 1-#4 1-#4 1-#4 1 OR 3 PHASE, 3WIRE CABLE 1"4A 11A 10A 9A 8A 7A 6A 5A 2" 2" 2" 1-1/2" 1-1/4" 1-1/4" 1" CONDUIT 3A 2A 1A FDR NO. 1" 3/4" 3/4" 1-#103-#8 3-#3/0 3-#2/0 3-#1/0 3-#1 3-#4 3-#3 3-#6 1-#6 1-#6 1-#6 1-#6 1-#8 1-#8 1-#10 3-#12 3-#8 3-#10 1-#10 1-#10 1-#12 GROUND 4-250MCM 4-350MCM 4-500MCM 4-500MCM 4-250MCM 4-350MCM 4-500MCM 4-500MCM 4-400MCM 4-400MCM 4-500MCM 4-300MCM 4-350MCM 4-400MCM 4-500MCM 4-500MCM 4-500MCM 4-500MCM 4-500MCM 1900 (5) 4"1800 26B 2010 3040 2660 5320 6080 4180 6000 4000 5000 2500 3000 2000 32B 30B 31B 28B 29B 27B (16) 4" (14) 4" (11) 4" (8) 4" (7) 4" (6) 4" 620 760 760 1240 1675 1425 1005 1400 1600 1200 1000 800 700 600 24B 25B 23B 22B 21B 20B 19B 510 230 255 310 380 380 460 350 500 450 400 250 300 225 15B 18B 17B 16B 13B 14B 12B (5) 4" (5) 4" (4) 4" (3) 4" (2) 4" (2) 4" (2) 3" 4" (2) 3" (2) 2-1/2" 4" 2-1/2" 3" 3" 4-#4/0 4-#4/0 1800 19001-250MCM 2-500MCM 1-250MCM 1-400MCM 1-350MCM 2-350MCM 1-500MCM 5000 6000 4000 3000 2500 2000 6080 4180 5320 2660 3040 2010 1-#4/0 1-#4/0 1-#3/0 1-#1/0 1-#2/0 1-#1/0 1-#1 1200 1600 1400 1000 800 600 700 1-#3 1-#3 1-#2 1-#3 1-#4 1-#4 1-#4 350 450 500 400 250 300 225 1425 1675 1240 1005 760 620 760 380 460 510 380 255 310 230 3 PHASE, 4 WIRE CABLE 50 4B50 175 200 100 130 150 85 65 200 175 150 125 70 100 60 11B 10B 9B 8B 6B 7B 5B CALC. AMPS 50 30 20 40 30 20 NOM. AMPS 3B 2B 1B FDR NO. 4-#81" 2-1/2" 2" 2" 2" 1-1/4" 1-1/4" 1" 4-#2/0 4-#3/0 4-#1 4-#1/0 4-#4 4-#3 4-#6 3/4" 3/4" 1" CONDUIT 4-#8 4-#10 4-#12 501-#10 1-#6 1-#6 1-#6 1-#6 1-#8 1-#8 1-#10 175 200 125 150 70 100 60 1-#10 1-#12 1-#10 GROUND 40 20 30 NOM. AMPS 50 200 175 150 130 85 100 65 50 20 30 CALC. AMPS MANUFACTURERNUMBER PART/MODEL DESCRIPTION VOLTAGE LAMPS OPTIONS (1) 32W CFL120W516-41-32WABASELINE COEPD MATION 16" WAREHOUSE SHADE B (3)BR20 LED, 8W120LTKSTBF D (2) 1.5W LED3.6ELM2 BAFFLE TRACK KIT CEILING EXIT/EMERGENCY LITHONIA LIGHTING LITHONIA LITHONIA XEC EM LHQM 9.6 (2) 1.5W LED C WAREHOUSE CORD HUNG LEDPROSROSS LIGHTING P5094-0930K9 120 (1) 17W LED E XE (2) 1.5W LED9.6LHQMWALL MOUNTED EXIT/EMERGENCYLITHONIA WALL MOUNTED EMERGENCY 120CONTEMPORARY SQUARE VANITYLITHONIA LIGHTING FMVCSL-24 MVOLT (1) 26W LED (1) 17WLED120S7R827K10PHILIPSSURFACE ROUND CEILING LED 7" XM (2) 1.5W LEDFLOOR PROXIMITY EXIT SIGNLITHONIA XHC ADA EXIST SIGN W/ADA SYMBOLESW XM ESW CT700E STX-C-CT EXIT/EMERGENCY COMBOW/ADA SYSMBOL S S S BRANCH WIRING CONCEALED IN CEILING OR WALL DUPLEX RECEPTACLE OUTLET (+18" AFF - TYPICAL) GROUND FAULT CIRCUIT INTERRUPTER BRANCH WIRING HOME RUN (ARROW INDICATES CIRCUIT NUMBER) SINGLE - POLE SWITCH THREE - WAY SWITCH PANEL- GFCI JUNCTION BOX SURFACE - MOUNTED PANELBOARD SYMBOL DESCRIPTION ELECTRICAL SYMBOL LIST NATIONAL ELECTRICAL NOT APPLICABLE NOT TO SCALE MOLDED CASE CIRCUIT BREAKER LIGHTING PANELBOARD JUNCTION BOX GRD GFCI EQUIP ENCL EMT EM DWG DISC CCT C/B CAB C BR BAT AWG LIGHTING KILOWATT INCHES WP SCHD U/G TYP SW ELECTRICAL ABBREVIATIONS AFF AC RECPT DESCRIPTIONABBREVIATION GROUND-FAULT CIRCUIT-INTERRUPTER DRAWING EMERGENCY ELECTRICAL METALLIC TUBING ENCLOSURE EQUIPMENT GROUND ABOVE COUNTER ABOVE FINISHED FLOOR AMERICAN WIRE GAUGE BATTERY BRANCH CONDUIT CABINET CIRCUIT BREAKER CIRCUIT DISCONNECT KW LTG LP MCCB N.T.S. N/A NEMA IN JB WEATHERPROOF UNDER GROUND TYPICAL SCHEDULE SWITCH RECEPTACLE CEILINGCLG EXG EXISTING MANUALMAN NOT IN CONTRACTNIC DESCRIPTIONABBREVIATION SC SEPARATE CIRCUIT EQUIPMENT AND MATERIAL INDICATED ON THE DRAWING SHALL BE CONSIDERED AS "BASIS OF DESIGN". EQUAL PRODUCTS CAN BE SUBMITTED AND WILL BE CONSIDERED FOR APPROVAL STRICTLY SUBJECT TO OWNERS AND DESIGN PROFESSIONAL'S APPROVAL. SUBMIT SHOP DRAWINGS FOR APPROVAL PRIOR TO ORDERING FIXTURES. PROVIDE OWNER WITH WARRANTY, GUARANTEEING THAT IMPERFECT SYSTEM OPERATION AND ALL DEFECTS IN MATERIAL AND LABOR OF WORK WILL BE REPAIRED WITHOUT COST TO THE OWNER FOR A PERIOD OF ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION OF THE PROJECT. GIVE FULL COOPERATION TO OTHER TRADES, PROVIDING THEM WITH ALL NECESSARY INSTALLATION DETAILS. PROVIDE COMPLETE AND OPERATIONAL SYSTEMS INCLUDING ALL NECESSARY MATERIAL EQUIPMENT AND LABOR. THE TERM 'INDICATE' SHALL MEAN AS SHOWN ON THE CONTRACT DOCUMENTS (DRAWINGS, SPECIFICATIONS AND RELATED ATTACHMENTS). THE TERM 'PROVIDE' SHALL MEAN FURNISH, INSTALL, CONNECT AND MAKE OPERABLE. ALL EQUIPMENT AND MATERIALS SHALL BE LABELED, LISTED AND INSTALLED IN ACCORDANCE WITH MANUFACTURERS INTERACTIONS, RECOMMENDATIONS AND INSTRUCTIONS. THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND ARRANGE FOR ALL REQUIRED INSPECTIONS IN ACCORDANCE WITH STATE AND LOCAL GOVERNING AUTHORITIES. ALL WORK SHALL BE PERFORMED BY LICENSED WORKMEN IN ACCORDANCE WITH ALL APPLICABLE STATE, FEDERAL AND LOCAL CODES AND REGULATIONS INCLUDING BUT NOTLIMITED TO THE CURRENT NATIONAL ELECTRIC CODE (NEC). BECOME FAMILIAR WITH THE COMPLETE SET OF CONTRACT DOCUMENTS, AS ALL OTHER SPECIFICATION SECTIONS AND DRAWINGS ARE APPLICABLE TO THE WORK OF THIS DRAWING.FOLLOW THE JOB-SITE INSTRUCTIONS OUTLINED IN THE GENERAL CONDITIONS. ALL LOW VOLTAGE WIRING TO BE RUN WITH A MINIMUM OF 12" CLEARANCE FROM FLUORESCENT LIGHTING IN ALL DIRECTIONS. FIRE RATING OF ALL WALLS AND CEILINGS SHALL BE MAINTAINED. ANY FIRE BARRIERS THAT MUST BE PENETRATED SHALL MAINTAIN FIRE RATINGS THAT COMPLY WITH BOTH THENATIONAL FIRE PROTECTION ASSOCIATION AND UNDERWRITER LABORATORY'S STANDARDS AND SPECIFICATIONS. EMT CONDUIT SHALL BE USED FOR CONCEALED WALL & CEILING PENETRATIONS, RISERS AND MAY BE USED IN EQUIPMENT CLOSETS. ALL WIRING TO BE CONCEALED WHEREVER POSSIBLE. IF BUILDING STRUCTURE PREVENTS WIRE OR CABLE FROM BEING RUN INSIDE WALLS AND CEILINGS, ALL EXPOSED WIRING TOBE RUN IN METALLIC RACEWAY. IF ANY ASBESTOS OR MATERIALS CONTAINING ASBESTOS ARE ENCOUNTERED DURING EXECUTION OF THE PROJECT WORK IS TO BE HALTED. IT IS THE CONTRACTORS RESPONSIBILITY TO NOTIFY THE OWNER AND PROPER AUTHORITIES IF THEY HAVE DISCOVERED ASBESTOS. PROVIDE THE OWNER WITH ALL MANUFACTURERS WARRANTIES FOR EQUIPMENT AND MATERIAL FURNISHED. ANY HAZARDOUS MATERIALS ENCOUNTERED (SUCH AS PCB BALLASTS) SHALL BE DISPOSED OF PROPERLY. ALL PAPERWORK RELATING TO DISPOSAL SHALL BE MAINTAINED ON FILEFOR ONE YEAR FROM COMPLETION OF JOB. UNLESS OTHERWISE INDICATED PROVIDE COMMERCIAL GRADE, 20 AMPERE RECEPTACLES. UNLESS OTHERWISE INDICATED, INTERIOR BRANCH CIRCUIT WIRING USING 6 AWG AND SMALLER CONDUCTORS MAY BE ARMORED CABLE (TYPE AC) WHERE ACCEPTABLE TO LOCALCODES. UNLESS OTHERWISE INDICATED ALL ENCLOSURES FOR EQUIPMENT SHALL BE NEMA TYPE 1. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL FIELD CONDITIONS OR INTERFERENCES THAT MAY EXIST. CONTRACTOR SHALL VISIT THE JOB SITE, BECOME FAMILIAR WITHFIELD CONDITIONS AND ASSUME RESPONSIBILITY FOR THEM THEREOF, BEFORE BIDDING AND DURING EXECUTION OF WORK. 21. 20. 19. 18. 17. 16. 15. 14. 13. 12. 11. 10. 9. 8. 7. 6. 5. 4. 3. 2. 1. GENERAL ELECTRICAL NOTES DATA OUTLET MOTOR PC PHOTO CELL SMOKE DETECTOR ALL CONDUCTORS SHALL BE COPPER W/ THHN/THWN INSULATION. ALUMINUM CONDUCTOR WILL NOT BE ACCEPTED.22. UNLESS OTHERWISE NOTED ALL CIRCUITS SHALL BE 2#12 AWG & 1#12 GND IN 1/2"C23. ALL WIRING SHALL BE IN METAL CLAD CABLE OR (BX) OR IN FLEXIBLE METAL CONDUIT UNLESS OTHERWISE INDICATED ABOVE. PROVIDE A DEDUCT PRICE TO BE NON-METALLIC CABLE (ROMEX) WHERE CONCEALED.24. FLOOR OR COUNTERTOP MOUNTED DUPLEX RECEPTACLE OUTLET 240 VOLT OUTLET SPECIAL PURPOSE SINGLE RECEPTACLE OUTLET EXTERNALLY OPERATED DISCONNECT SWITCH SWITCH LEG WIRING AIR HANDLING UNITAH-# SMOKE AND CARBON MONOXIDE DETECTOR SURFACE CEILING MOUNTED LIGHT FIXTURE EXHAUST FAN/ LIGHT CONDENSING UNITCU-# WI-FI HOT SPOT TV CABLE OUTLET DIMMER SWITCH TIMER SWITCH MANUFACTURERS ASSOCIATION ADA COMPLIANT STROBE WITH REQUIRED CANDELA (cd) RATING - WALL FIRE ALARM CONTROL PANEL INDIVIDUAL ADDRESSABLE INPUT MODULE SPRINKLER TAMPER SWITCH TO BE MONITORED SPRINKLER FLOW SWITCH TO BE MONITORED ADA COMPLIANT STROBE WITH REQUIRED CANDELA (cd) RATING - CEILING SMOKE DETECTOR MANUAL PULL STATION FIRE ALARM SYMBOL LIST SYMBOL DESCRIPTION FIRE ALARM ANNUNCIATOR PANEL SMOKE DETECTOR CONNECTED TO ELEVATOR RECALL SYSTEM. LIGHT FIXTURE SCHEDULE DATA OUTLET MOTOR SWITCH COMBINATION SMOKE/CARBON MONOXIDE DETECTOR Scale Date Drawn By Checked By Project Number UNCASVILLE, CT 1/4" = 1'-0" E3.3 ELECTRICAL SCHEDULES Dakota Partners, Inc. OXOBOXO LOFTS DA RS 11/01/2016 16066.01 No.Description Date 9 Permit ReviewComments 08/05/2019 9