HomeMy WebLinkAboutASK008R1 - FLOOD VENT BUILDING HBUILDING H 2900 S.F.
FLOOD VENTS
5W X 1 H
IN LOWER
CRAWL SPACE
EL: 23'-0"
ASK-008
R1
3
ASK-008
R12
(1) 5W X 1H VENT COVERS 1000 SF PER
ATTACHED CHART, SO 3 VENTS ARE NEEDED
EXISTING
CRAWL SPACE
OXOBOXO BROOK
NORTH BANK
F.F.E. : 26'-10 3/8"
UPPER CRAWL SPACE
F.F.E. : 22' - 5"
FLOOD VENTS
5W X 1 H
IN UPPER
CRAWL SPACE
EL: 27'-4"
BLDG H LEVEL 1 EXIST
26' - 10 3/8"
BLDG HJ LEVEL 1 NEW
30' - 5"
EXISTING CRAWL SPACE
24'-0"
GRADE
EXISTING LOWER CRAWL SPACE BEYOND
VENTED ON SOUTH WALL ABOVE
OXOBOXO BROOK. SEE DRAWING BELOW.
METAL FRAMED WOOD FLOOR
CONCRETE SLAB
RAT SLAB22'-5"
27'-4"
B.O. FOOD VENT
BLDG H LEVEL 1 EXIST
26' - 10 3/8"
BLDG HJ LEVEL 1 NEW
30' - 5"
EXISTING LOWER CRAWL SPACE
OXOBOXO BROOK BELOW
CONCRETE SLAB
METAL FRAME WOOD FLOOR
RAT SLAB22' - 5"B.O. FLOOD VENT
23' - 0"DateDrawn byScaleREF:3/32" = 1'-0"3/9/2020 4:22:51 PMOXOBOXO LOFTS42 Pink Row Uncasville, CT 06382ASK-008 R13/9/20FLOOD VENT BUILDING HTGBLDG H3/32" = 1'-0"ASK-008 R1
1 BLDG H- CRAWL SPACE FLOOR PLAN
3/32" = 1'-0"ASK-008 R1
2 BLDG H EAST ELEVATION
3/32" = 1'-0"ASK-008 R1
3 BLDG H SECTION LOOKING NORTH
A
B
D E
C F
G H
J
K
L M
NORTH
SITE KEY PLAN