HomeMy WebLinkAboutPlans
x511.6 x510.5 x509.6
LEGEND:
------------,----------------------, ---,
I I I 11 I I I I
F.F. EL. - 513.0I
FIRST FLOOR
EL.
568
S.F.
SEPTIC SYSTEM INVERTS
TYP.
TYPICAL
DH
DRILL HOLE
IP
IRON PIPE
REC.
RECOVERED
x510.5
(f) - 508.85 OUTLET AT HOUSE
---- -~- 508 ---- -----
ro
PROPOSED CONTOURS
• :
PROPOSED SPOT ELEVATION
BUILDING SETBACK LINE
(2) - 508.05 INLET @7 TANK
TEST PIT
I'
..- - _
9, _- __ -- 6
DEPTH - 28" PRESOAK - 9:30
10:35 - 8" 11:10 - 25 1/4"
( - 507.85 OUTLET @ TANK
10:40 -13" 11:15 - 26"
10:45 -17" 11:20 - 26 3/4"
PERC
10:50 -19 1/2" 11:25 - 27 1/4"
10:55 - 213/4" 11:30 - 27 3/4" DRY
(4) - 507.27 INLET @ D -BOX
11:00 - 23 1/4"
11:05 - 241/4"
xsla.6sob
_-
PERC RATE -1" - 8 MIN,
SERVE AREA
® - 507.17 INLET & TRENCH INVERT (BOTTOM TRENCH EL. -506.7)
• •
_
x509.3
- 506. INVERT (BOTTOM TRENCH EL. -505.9)
44 INLET &TRENCH
JOL
(7 - 505.95 INLET & TRENCH INVERT (BOTTOM TRENCH EL. -505.5)
- ,
4xso9.a
49
`
TP -166
_
3
510
.._
r TP -167
._..
38LF-4"PVC
't, D -BOX -TYP.
_.._.
_... TP -15
(ASTM -1785)
28LF-4"PVC
(SDR -35)(S
-EE DETAILS
500- -41
4
� A
1,500 GAL./ 2 -COMP.
50'
SEPTIC TANK
49
- _
(SEE DETAIL)
C/
'--------__
LOT # 14
510-
-'
-
BENCHMARK x508.9
-------
•
,
x509.0
NAIL IN 15" TREE
~
�'
PROPOSED
ELEV. - 510.47
_.. _.
FOOTING
DRAIN
502
_
IIP\
OUTLET
`
x509.1
/
cn
N
DH
if -
00
360.00t
PROPOSED
t
x509.6
UNDERGROUND
\
UTILITIES
110
, �d - '
'�sI
\SID
°0
SEE I
Li ,
�' ----- -----
_
15
PROPOSED
\�
W
WELL
LIMITS OF INLAND WETLANDS \
PER REFERENCE MAP #2
\
504
- -.• .
.
_..-.
_
\
'
o
'
o0
z
w
x507.0
s
x511.6 x510.5 x509.6
LEGEND:
------------,----------------------, ---,
I I I 11 I I I I
F.F. EL. - 513.0I
FIRST FLOOR
EL.
568
S.F.
SQUARE FEET
TYP.
TYPICAL
DH
DRILL HOLE
IP
IRON PIPE
REC.
RECOVERED
x510.5
TP -18
-_ .--.-
---- -~- 508 ---- -----
ro
PROPOSED CONTOURS
PROPOSED SPOT ELEVATION
BUILDING SETBACK LINE
TEST PIT
I'
..- - _
9, _- __ -- 6
DEPTH - 28" PRESOAK - 9:30
10:35 - 8" 11:10 - 25 1/4"
10:40 -13" 11:15 - 26"
10:45 -17" 11:20 - 26 3/4"
PERC
10:50 -19 1/2" 11:25 - 27 1/4"
10:55 - 213/4" 11:30 - 27 3/4" DRY
11:00 - 23 1/4"
11:05 - 241/4"
xsla.6sob
_-
PERC RATE -1" - 8 MIN,
SERVE AREA
_
x509.3
L
JOL
- ,
4xso9.a
TP -166
_
3
510
.._
r TP -167
._..
38LF-4"PVC
't, D -BOX -TYP.
_.._.
_... TP -15
(ASTM -1785)
28LF-4"PVC
(SDR -35)(S
-EE DETAILS
1,500 GAL./ 2 -COMP.
50'
SEPTIC TANK
- _
(SEE DETAIL)
`- -
'--------__
510-
-'
-
BENCHMARK x508.9
-------
•
,
x509.0
NAIL IN 15" TREE
~
�'
PROPOSED
ELEV. - 510.47
DRIVEWAY
IIP\
x509.1
/
s
DH
if -
REC.
360.00t
PROPOSED
t
x509.6
UNDERGROUND
\
UTILITIES
110
, �d - '
'�sI
\SID
s
x511.6 x510.5 x509.6
LEGEND:
------------,----------------------, ---,
I I I 11 I I I I
F.F.
FIRST FLOOR
EL.
ELEVATION
S.F.
SQUARE FEET
TYP.
TYPICAL
DH
DRILL HOLE
IP
IRON PIPE
REC.
RECOVERED
x510.5
EXISTING SPOT ELEVATION
---- -~- 508 ---- -----
EXISTING CONTOURS
ro
PROPOSED CONTOURS
x509.0
PROPOSED SPOT ELEVATION
BUILDING SETBACK LINE
TEST PIT
CATCH BASIN
TYPE "C"
T.F.-508.9
INV. -504.9
LOCHDALE DRIVE
O1\
x509.3 18"CPP --�•
4"
TOPSOIL
CONNECTICUT APPROVED SUITABLE FILL
FILTER FABRIC 211
4" PERFORATED
PIPE q
O N
Cb
1" STONE (10vtio C4&
4`
TRENCH
CROSS SECTION
NOT TO SCALE
x510.2
FILTER
------------,----------------------, ---,
I I I 11 I I I I
(•.}
FABRIC
�
I 1 I 1 H I 1
+ Ch
I I 1 I i CA 1 I I I I
I I I I I I I I I I
I I i I i by I I I 1 I
I I I
51" `
ti
ANGLE 100 UP SLOPE
POST
59"
FOR STABILITY AND
TRACE OF GRAVEL
�I zo
SELF CLEANING
NO LEDGE
r\\\<<\77/7% awl
COMPACTED /
NO WATER
WATER @ 63"
BACKFILL !
MOTT.@28"
SILT FENCE
NOT TO SCALE
- 4" PVC ELBOW
(CUT FOR 4" OVERFLOW)
2X2 5/8 16 GA. WIRE MESH %
11/2" /
.a m
cv 2„
STANDARD D -BOX W/ELBOW
NOT TO SCALE
PER1�
�Fl��'RV
CE MAp #1) -�
LOT # 13
LOCHDALE ESTATES
10'-6"
KNOCKOUT INLET AND
OUTLET OPENINGS
CAST
CONCRETE COVERS -
CAPACITIES
------------,----------------------, ---,
I I I 11 I I I I
(•.}
I I I 1 l 1 I I I
I I I 1 1 I I i t I
I I I I I I i i I
I I I I I i t I I I
I I 1 I 1 i I I 1 I
1250 GAL
I 1 I 1 H I 1
+ Ch
I I 1 I i CA 1 I I I I
I I I I I I I I I I
I I i I i by I I I 1 I
I I I
CAST
CONCRETE COVERS -
CAPACITIES
A
B
C
1250 GAL
61"
51" `
48"
1500 GAL
69"
59"
56"
4 x 4 12.6/12.6 GA. WIRE MESH
171/2" 6 x 6 6/6 GA. WIRE MESH
INL .4
3 VENT----
`( LIQUID LEVEL
1
I
c CONTINUOUS HOT P
pq ASPHALT SEAL
" SCHED. #40
INT Fl BAEELPI
e
I
--- -.�-------------- a 7 --
CROSS
-- j--¢----c-
CROSS SECTION
1250/1500 GALLON
2 COMPARTMENT
SEPTIC TANK
NOT TO SCALE
OUTLET
OUTLET
FILTER
U DEVICE
EROSION AND SEDIMENT CONTROL PLAN:
1. CLEARING, GRUBBING, AND GRADING OF THE PROPOSED SITE
TO BE LIMITED TO AREAS ADJACENT TO THE PROPOSED HOUSE
AND SEPTIC SYSTEM.
2. DISTURBED AREAS TO BE LOAMED, SEEDED, AND MULCHED.
3. ALL TOPSOIL TO BE STOCKPILED ON SITE AND PROTECTED
WITH HAYBALES OR SILT FENCE.
4. ALL CUT AND FILL SLOPES ARE NOT TO EXCEED 3:1 SLOPES.
5. PRIOR TO SITE DISTURBANCE, THE REPRESENTATIVE OF THE
TOWN OF MONTVILLE SHALL BE NOTIFIED WHEN SEDIMENT
CONTROL MEASURES ARE IN PLACE SO THAT THE INSPECTION
CAN OCCUR.
6. THE CONTRACTOR WILL BE RESPONSIBLE FOR THE INSTALLATION
AND MAINTENANCE OF ALL REQUIRED SEDIMENT CONTROL
MEASURES THROUGHOUT CONSTRUCTION.
7. DUST CONTROL WILL BE ACCOMPLISHED BY SPRAYING WITH
WATER, AND IF NECESSARY THE APPLICATION OF CALCIUM CHLORIDE.
TEMPORARY VEGETATIVE COVER:
MULCHES APPLICATION RATE
PER 1000 S.F.
STRAW/HAY 70-90 lbs.
WOOD CHIPS 185-275 lbs.
PLANTING SCHEDULE:
SEEDING DATES:
APRIL 1------- JUNE 15
AUGUST 1 ------ SEPTEMBER 15
SEED MIXTURE:
45% RED FESCUE
45% KENTUCKY BLUE GRASS
10% PERENNIAL RYE
NOTES
FREE FROM WEEDS
AND COARSE MATTER
FREE OF COARSE MATTER
AIR DRIED, TREAT WITH
12lbs NITROGEN / TON
TEST HOLE DATA
TEST HOLE OBSERVATIONS PER UNCAS HEALTH DISTRICT
SUBDIVISION PLAN - 01/14/91
TP #15
0"-12" TOPSOIL
12"-32" DARK -YELLOWISH -BROWN FINESANDY LOAM
32"-87" OLIVE -GREY LOAMY SAND & GRAVEL
SOME STONES, COMPACT
NO LEDGE
WATER @ 79"
MOTT.@32"
TP #16
0"-10" TOPSOIL
10"-30" DARK -YELLOWISH -BROWN FINESANDY LOAM
30"-88" OLIVE -GREY LOAMY SAND & GRAVEL
SOME STONES, COMPACT
NO LEDGE
WATER @ 63"
MOTT.@39"
TP =166
TP #167
TP #168
0"-12" TOPSOIL
0"-12" TOPSOIL
0"-12" TOPSOIL
12"-30" LIGHT BROWN FINE SANDY LOAM
12"-30" LIGHT BROWN FINE SANDY LOAM
12"-33" LIGHT BROWN FINE SANDY LOAM
30"-8811 GREY -BROWN MEDIUM FINE SILTY
SAND 30"-90" GREY -BROWN MEDIUM FINE SILTY SAND
33"-82" GREY -BROWN FIRM FINE SILTY SAND
TRACE OF GRAVEL
TRACE OF GRAVEL
NO LEDGE
NO LEDGE
NO LEDGE
WATER @ 50"
NO WATER
WATER @ 63"
MOTT.@30"
MOTT.@33"
MOTT.@28"
PERC RATE DATA
PER ADVANCED SURVEYS, LLC - 02/23/02
DEPTH - 28" PRESOAK - 9:30
10:35 - 8" 11:10 - 25 1/4"
10:40 -13" 11:15 - 26"
10:45 -17" 11:20 - 26 3/4"
10:50 -19 1/2" 11:25 - 27 1/4"
10:55 - 213/4" 11:30 - 27 3/4" DRY
11:00 - 23 1/4"
11:05 - 241/4"
PERC RATE -1" - 8 MIN,
PERCOLATION RATE = 1-10 MIN./INCH RATE
4 BEDROOM RESIDENCE REQUIRES 660 SQ FT OF
EFFECTIVE LEACHING AREA
EFFECTIVE LEACHING AREA ---225 LF x 3.0 SF/LF = 675 SF
USE (3) 75' LONG - 48" WIDE TRENCHES
USE A 1,500 GAL. 2 -COMPARTMENT TANK W/OUTLET FILTER DEVICE
M.L.S.S. REQUIRED = 28x2.Ox1.2=67.2
M.L.S.S. PROVIDED = 75
PREPARE AREA OF PROPOSED SYSTEM AS FOLLOWS:
1. ADDITIONAL TESTHOLES WILL BE REQUIRED BEFORE THE
START OF CONSTRUCTION.
2. REMOVE AND STOCKPILE TOPSOIL.
3. PLACE BANK RUN GRAVEL (LESS THAN 5% FINES) PLACED IN
6" LIFTS AND COMPACTED TO 95% DENSITY.
4. AFTER THE FILL IS PLACED AND COMPACTED A PREC TEST IS
TO BE PERFORMED. CONTACT THE UNCAS HEALTH DISTRICT.
PHONE: 1-860-823-1189,
5. EXCAVATE 4' WIDE TRENCHES AND PREPARE SURFACE.
6. FILL TRENCHES WITH I" WASHED STONE TO HEIGHT OF PIPE INVERTS
PLACE PIPE IN TRENCH, AND FILL TO 2" OVER TOP OF PIPE.
7. PLACE A 4' WIDE STRIP OF NON -WOVEN FILTER FABRIC ON TOP OF
THE ENTIRE LENGTH OF THE SYSTEM), AND BACKFILL WITH
NATIVE MATERIAL.
S. REPLACE TOPSOIL, SEED, & MULCH.
I . TOPOGRAPHIC INFORMATION ON THIS PLAN COMPLIES WITH T-2 MAPPING
STANDARDS,
2. PROPOSED HOUSE AND SEPTIC SYSTEM TO BE STAKED IN THE FIELD BY
A LAND SURVEYOR LICENSED IN THE STATE OF CONNECTICUT.
3. BASE FOR LEVELS: N.G.V.D. 1929.
4. PROPERTY IS LOCATED IIN THE, TOWN OF MONTVILLE ZONING DISTRICT R-40.
5. THERE ARE NO WELLS LOCATED WITHIN 75' OF THE PROPOSED SEPTIC SYSTEM
LOCATED ON ABUTTING PROPERTIES.
6. TOTAL AREA OF PROPERTY - 260,485 S.F.f - (5.98 ACRES
7. PROPERTY IS SHOWN ON ASSESSORS MAP 43, BLOCK 2, LOT 14,
8. PROPOSED HOUSE & SEPTIC SYSTEM ARE SHOWN IN THE SAME LOCATION AS
WAS APPROVED ON THE SUBDIVISION PLAN.
9. THE SEPTIC SYSTEM ON THE ABUTTING LOT #15 IS NOT WITH 75' OF THE
PROPOSED WELL,
REFERENCE MAPS:
1. LOT LAYOUT PHASE III, LOCHDALE ESTATES, PROPERTY OF BERNARD
BARNETT & HAROLD D. BATT, FORSYTH ROAD AND JEFFREY MANOR DRIVE,
MONTVILLE, CONNECTICUT, V=100', DEC. 2000, PREPARED BY TOTAL
TECHNOLOGY, INC.
2. GRADING AND EROSION CONTOL PLAN LOCHDALE ESTATES, PROPERTY OF
BERNARD BARNETT & HAROLD D. BATT, FORSYTH ROAD AND JEFFREY MANOR
DRIVE, MONTVILLE, CONNECTICUT, 1"=40', JAN.1992, REV. 5/20/92, SHEET 10 OF 23,
PREPARED BY TOTAL TECHNOLOGY, INC.
PROTECT N O 02-016 SEPTIC SYSTEM DESIGN PLAN
U��„N B': R.A.D. PREPARED FOR
DATE; 2/19/02
SCALE: l"=20'
SHEET 10F 1
REVISIONS
302 UNCAS HEALTH COMMENTS
20 10 0 20
GRAPHIC SCALE IN FEET
LOT #14 - LOCHDALE DRIVE
OAKDALE, CONNECTICUT
ADVANCED SURVEYS, LLC.
24 St. Regis Avenue Norwich CT. 06360
Phone & Fax (860) 859-1280