HomeMy WebLinkAboutPlot Plan SepticNOTES:
1. TOPOGRAPHIC INFORMATION ON THIS PLAN COMPLIES WITH T-2 MAPPING
STANDARDS.
2. PROPOSED HOUSE AND SEPTIC SYSTEM TO BE STAKED IN THE FIELD BY
A LAND SURVEYOR LICENSED IN THE STATE OF CONNECTICUT.
3. BASE FOR LEVELS: ASSUMED DATUM.
4. THE PROPERTY IS SHOWN ON ASSESSORS MAP 37 - LOT 27.
5. THE PROPERTY IS LOCATED IN ZONING DISTRICT R-120.
6. THERE ARE NO WELLS LOCATED WITHIN 75' OF THE PROPOSED SEPTIC SYSTEM
LOCATED ON ABUTTING PROPERTIES.
7. TOTAL AREA OF PROPERTY - 219,274 S.F.f - (5.03 ACRES).
8. LIMITS OF INLAND WETLANDS WERE DELINEATED BY MICHAEL G. SCHAFFER C.S.S.
REFERENCE MAP:
PROPERTY SURVEY PREPARED FOR WILLIAM PIENIADZ, FELLOWS ROAD,
MONTVILLE, CONNECTICUT, DATE: 12/06/04, SCALE:1 "=30', PREPARED BY
ADVANCED SURVEYS, LLC,
LEGEND:
F.F.
FIRST FLOOR
EL.
ELEVATION
S.F.
SQUARE FEET
TYP.
TYPICAL
IPIN
IRON PIN
MON
MONUMENT
DH
DRILL HOLE
x106.5
EXISTING SPOT ELEVATION
x107.2
PROPOSED SPOT ELEVATION
- 100 - -
EXISTING CONTOURS
100
PROPOSED PROPOSED CONTOURS
BUILDING SETBACK LINE
TEST HOLE
o WL#5
INLAND WETLANDS FLAG
OLD
ME I S OF
x 104.5 :,
®'H#2INLAND
SHED
E
N/F
3
WILLIAM LARKIN &
JANET LARKIN
�a
VOL. 379 PG. 487
0�
(MAP 37 - LOT 35)
P
04.3 o
04.4
z
ELEV. 105.00
IPIN
SET
CL&P
o3755
CL&P
3754
IPIN CL&P FELLOWS Ham'
SET 3755s • ROAD
WL#30
WLa31
N 55 043'03 E -
e
315.02,
WL#28 HW _ --99_
2
\`I
WL425
60' WL#21 /
p i
_x.#23 j
o
M WETLANDS
� f 1
M
z
WL#2?,`` W
p � O
W' 0
" 4 �
N/F INSTALL1 MAINTAIN A CONTINUOUS 1
JAMES A. BAILLARGEON LINE OF''j'ILT FENCE (SEE DETAIL) q
VOL. 264 PG. 852 r,}
(MAP 37 - LOT 28) 25' WL#21 �
' O
SIN PROPOSED 655th S.F. AREA--\ WL#20
OF REGULATED INLAND
17'4011 162.04' 1A WETLANDS TO BE FILLED 1 REC.
17'
j x99.3 !
DH � x99.5 /
ri
REC.
N 51029'04" W -- #g _ - WI,#9
22.45' _---- WL#4A wI#3A 102= 4 ----
DH wL#5A PROPOSED WL#t0 S= 0.023± �o
SET \ h
CLEARING wL#7 wL#113
CL&P
3753
O GG
CUP
�F 37535
31
UNGC46PO4NP
(41orY savice
CONNEOr`/0"
LIMITS - _ INV. 101.0±
- Wb#11
100% RESERVE` V;IJ 12 # WITH PERFORATED
,- "�
1,250 GALLON 102 ,W,#5
wL#6 AREA ;r D -BOX END CAP
WL#6A SEPTIC TANK ~- - - / -_INV. 102.87IN r
/ INV .--102.710VT
INV. 103.85 IN
INV. 103.60 OUi' - �• a 15 +
L
J03 WL#.I ,
�. 28'-4'7VC SCHED. 40 \ 7 \
_ / ? . N/F
NiFmob. WL#7A S= 1/4",/FT.- #3 __ HENRY W. MALINOWSKY &
MAGNUS A. WADE & LIMITS OF 50' EVELYN MALINOWSKI
DOROTHY WADE 104. WL#3 REGULATED AREA /� �'` �.� VOL. 159 PG. 290
VOL. 259 PG. 852 �s6` 1®3 W (MAP 37 - LOT 26)
(MAP 37 - LOT 29) _DHO'd
IP
REC.
CHING GALLERIES
2B ELEV. 102.10
WL#13A WL#1B x103.4 -- - -
WL# 12A
WL#10A� N
#t4A WL#11A
/,--/"A
----_N 8025'42" W _
34.93'
o� e.
c` 1� WL#SB
WL#6B
WETLANDS
60'
LIMITS OF INLAND WETLANDS AS FLAGGED
BY MICHAEL G. SCHAFFER, C.S.S.
SIGNATURE
DATE
S 49035'46" W 518.11'
N/F
HENRY W. MALINOWSKY &
EVELYN MALINOWSKI
VOL. 159 PG. 290
(MAP 37 - LOT 26)
To ,:lu n , led -h nc b&ief, this map is substantially correct as noted hereon.
4,
Robert <t f.E.
Certlficati6i, :s --,;t valid without live signature and embossed (impression) type seal.
PROPOSED
WELL I
6
FILTER
FABRIC '
ANGLE 100 UP SLOPE
POST FOR STABILITY AND
}moo SELF CLEANING
COMPACTED
BACKFILL
NOT TO SCALE
2X2 5/8 16 GA, WIRE MESH
M
_
g
M _
O
'
2„
STANDARD D-DOX W/ELBOW
NOT TO SCALE
ME I S OF
x 104.5 :,
®'H#2INLAND
E
WETLANDS ``
1W. 104.44
i
o WL#sA
WL#2 x! ,� '' \
x104.8°
` 0.4x
BENCHMARK
DRILL HOLE
^h
p
04.3 o
04.4
fs
ELEV. 105.00
170'-4"PVC ASTM D 3034 SDR35
(TIGHT PIPE) FOOTING DRAIN
LIMITS OF
INLAND WETLANDS'l�q�
WL#1 ✓` FF �c --
x193.7.,
'`= .-.
OUTLET PIPE - 5.01±
\.
WL#9ax1:3.6
00
dFck " %
103.2x 144
BOTTOM OF ALL 4'x8'x12" HIGH
25' CONCRETE LEA
CHING GALLERIES
2B ELEV. 102.10
WL#13A WL#1B x103.4 -- - -
WL# 12A
WL#10A� N
#t4A WL#11A
/,--/"A
----_N 8025'42" W _
34.93'
o� e.
c` 1� WL#SB
WL#6B
WETLANDS
60'
LIMITS OF INLAND WETLANDS AS FLAGGED
BY MICHAEL G. SCHAFFER, C.S.S.
SIGNATURE
DATE
S 49035'46" W 518.11'
N/F
HENRY W. MALINOWSKY &
EVELYN MALINOWSKI
VOL. 159 PG. 290
(MAP 37 - LOT 26)
To ,:lu n , led -h nc b&ief, this map is substantially correct as noted hereon.
4,
Robert <t f.E.
Certlficati6i, :s --,;t valid without live signature and embossed (impression) type seal.
PROPOSED
WELL I
6
FILTER
FABRIC '
ANGLE 100 UP SLOPE
POST FOR STABILITY AND
}moo SELF CLEANING
COMPACTED
BACKFILL
NOT TO SCALE
2X2 5/8 16 GA, WIRE MESH
M
_
g
M _
O
'
2„
STANDARD D-DOX W/ELBOW
NOT TO SCALE
CAST
CONCRETE COVERS -
PLAN
CAPACITIES A B C
1250 GAL 61" 1 51" 148-
1500 GAL 69" 59" , 56-
4 x 4 12.6/12.6 GA. WLRE MESH
17 1/2" 6 x 6 6/6 GA. WIRE 'MESH
i..
4 I CONTINUOUS HOT f�'
oc I ASPHALT SEAL �J
" SCHED. #40
T &A PIPI IP
CROSS SECTION
1250/1500 GALLON
2 COMPARTMENT
SEPTIC TANK
NOT TO SCALE
NOTES:
1. THIS SEPTIC SYSTEM INSTALLATION INCLUDING ALL MATERIALS (PIPING, SEPTIC TANK,
STONE, FILL, ETC.) USED FOR THIS SEPTIC SYSTEM SHALL CONFORM TO THE CURRENT
EDITION/REVISION OF THE "TECHNICAL STANDARDS FOR SUBSURFACE SEWAGE DISPOSAL
SYSTEMS" REVISED JANUARY 1, 2004 OF THE CONNECTICUT PUBLIC HEALTH CODE BY THE STATE
OF CONNECTICUT DEPARTMENT OF PUBLIC HEALTH.
2. THE PROPOSED HOUSE SEWER FROM THE BUILDING TO THE SEPTIC TANK SHALL BE
SCHEDULE 40 PVC ASTM D 1785/ASTM D 2665 OR APPROVED EQUAL AND INDICATED IN TABLE NO.
2 OF "TECHNICAL STANDARDS FOR SUBSURFACE SEWAGE DISPOSAL SYSTEMS". ALL OTHER
SEWER PIPE FOR THIS SEPTIC SYSTEM SHALL BE 4" PVC ASTM D3034, SDR 35 WITH RUBBER
COMPRESSION GASKET OR BELL AND SPIGOT OR APPROVED EQUAL.
3. THERE ARE NO WELLS (POTABLE, GEOTHERMAL, OR IRRIGATION) WITHIN 75' OF THE
PROPOSED SEPTIC SYSTEM.
4. THERE SHALL BE NO STUMPS OR BOULDERS BURIED WITHIN 50' DOWN GRADIENT OF THE
SEPTIC SYSTEM. SHOULD ANY SIGNIFICANT VARIATIONS FROM THE 'FEST HOLE DATA BE
ENCOUNTERED DURING EXCAVATIONS (LEDGE, GROUNDWATER, MOTTLING, SOIL TYPE, ETC.),
THE DESIGN ENGINEER SHALL BE NOTIFIED PRIOR TO INSTALLATION OF THE SEPTIC SYSTEM.
5. ALL EXISTING UTILITIES ARE APPROXIMATE ONLY. THE CONTRACTOR SHALL VERIFY ALL
UTILITY LOCATIONS AND ELEVATIONS PRIOR TO ANY CONSTRUCTION. CONTRACTOR SHALL
CONTACT "CALL -BEFORE -YOU -DIG" AT 1-800-922-4455 AT LEAST 48 HOURS PRIOR TO ANY
EXCAVATION.
6. THE PROPOSED FILL FOR THIS SEPTIC SYSTEM SHALL MEET THE FOLLOWING SPECIFICATIONS:
A. 100% OF FILL SHALL PASS THROUGH A 3" SIEVE.
B. MAXIMUM % OF GRAVEL (BETWEEN #4 & 3" SIEVE) = 45 %.
C. GRADATION OF FILL WITHOUT THE GRAVEL SHALL MEET THE FOLLOWING CRITERIA:
SIEVE SIZE % PASSING (WET) % PASSING (DRY)
#4 100% 100%
#10 70-100% 70-100%
#40 10-50% 10-75%
#100 0-20% 0-5%
#200 0-5% 0-2.5%
D. * PERCENT PASSING THE #40 WET SIEVE CAN BE INCREASED TO NO GREATER THAN 75% IF THE
PERCENT PASSING THE #100 SIEVE DOES NOT EXCEED 10% AND THE #200 SIEVE DOES NOT
EXCEED 5 afro.
E. PERCOLATION RATE AFTER PLACEMENT AND COMPACTION SHALL BE FASTER THAN OR
EQUAL TO 20.0 MINUTES/INCH.
A WET OR DRY SIEVE ANALYSIS MAY BE REQUIRED PRIOR TO FILL PLACEMENT TO VERIFY THAT
IT MEETS THESE SPECIFICATIONS. THE FILL SHALL BE APPROVED BY THE UNCAS HEALTH
DISTRICT OR DESIGN ENGINEER PRIOR TO ITS PLACEMENT ON SITE.
7. APPROVED AGGREGATE SHALL BE STONE AGGREGATE OR OTHER PRODUCTS APPROVED BY
THE COMMISSIONER OF PUBLIC HEALTH. STONE AGGREGATE SHALL BE BROKEN STONE,
CRUSHED STONE, OR SCREENED GRAVEL MEETING THE CONNECTICUT DEPARTMENT OF
TRANSPORTATION FORM 814A (OR LATEST REVISION THERETO) SPECIFICATION M.01.01 FOR NO.4
STONE, FREE OF SILT, DIRT, OR DEBRIS, SHALL SHOW A LOSS OF ABRASION OF NOT MORE THAN
50% USING AASHTO METHOD T-96 AND CONFORM TO THE FOLLOWING:
SIEVE SIZE % PASSING
2 INCH 100%
1.5 INCH 90-100%
1 INCH 20-55%
3/4 INCH 0-10%
3/8 INCH 0-5%
8. NO DEVIATION FROM THE APPROVED DESIGN PLAN SHALL BE ALLOWED WITHOUT PRIOR
APPROVAL FROM THE UNCAS HEALTH DISTRICT AND THE DESIGN ENGINEER.
9. THE SEPTIC TANK SHALL BE PRECAST CONCRETE UNLESS OTHERWISE AUTHORIZED BY THE
DESIGN ENGINEER AND SHALL BE TESTED FOR WATER TIGHTNESS AFTER INSTALLATION.
10. SITE PREPARATION PROCEDURE FOR THE INSTALLATION OF THE PROPOSED SEPTIC SYSTEM:
A. STRIP ALL TOPSOIL, VEGETATION AND ORGANIC MATERIAL IN THE AREA OF AND 5'
SURROUNDING THE PRIMARY LEACHING GALLERIES.
B. USING A HEAVY RAKE OR EQUAL, THOROUGHLY SCARIFY AND ROUGHEN UP THE EXPOSED
SUBSOIL. PREVENT ANY VEHICULAR TRAFFIC, BACKHOE, TRUCKS, ETC. FROM
SMOOTHING/COMPACTING THIS EXPOSED SUBSOIL.
C. PLACE AND COMPACT SELECT FILL MATERIAL MEETING SPECIFICATIONS INDICATED ABOVE
(NOTE #6) IN LIFTS OF NOT GREATER THAN 12" IN THE AREA OF THE PROPOSED LEACHING
GALLERIES UP TO AT LEAST THE ELEVATION OF THE TOP OF THE LEACHING GALLERIES.
D. PERFORM AT LEAST 1 PERCOLATION TEST ON PLACED FILL. FILL MUST HAVE A PERCOLATION
RATE EQUAL TO OR FASTER THAN THAT AS INDICATED IN NOTE #6.D. IF PERCOLATION RATE IS
SLOWER THAN THAT RATE, ALL FILL SHALL BE REMOVED AND REPLACED WITH ACCEPTABLE
FILL MEET t ri PROPER. SPECIFICATIONS.
E. IN3-TA',L SEPTIC SYSTEM PER PLAN USFAG APPROVED AGGREGATE AS INDICA'.'ED IN NOTE #7.
F. COVER SYSTEM WITH A OF 6" OF LOAM IN LAWN AREAS, GRADE TO PREVENT
PONDING AND SEED WITH GRASS TO STABILIZE. THE FINISHED GRADE 10' FROM ANY PART OF
THE PROPOSED LEACHING GALLERIES SHALL BE AT LEAST THE SAME ELEVATION AS THE TOP OF
THE RESPECTIVE LEACHING GALLERY.
G. CLEANOUT MANHOLES AT THE INLET BAFFLE AND AT THE OUTLET FILTER OF THE SEPTIC
TANK OR ASSOCIATED RISERS AT THESE LOCATIONS IF REQUIRED SHALL BE LOCATED AT A
DEPTH NOT GREATER THAN 12" BELOW FINAL GRADE.
11. FOR EXACT HOUSE DIMENSIONS, SEE BUILDING PLANS.
TEST HOLE & PERC DATA
PER UNCAS HEALTH DISTRICT -10/14/04
TH#I - 0"-9" TOPSOIL TH#3 - 0"-7" TOPSOIL
- 9"-28" BROWN SANDY LOAM - 7"-38" BROWN SANDY LOAM
- 28A 1" SAND & GRAVEL - 38"-69" GREY COMPACT SANDY TILL
- 41 "-66" GREY COMPACT SANDY TILL NO WATER, MOTT@38", NO LEDGE
WATER@41 "„ MOTT@41 ", NO LEDGE
TH#2 - 0"-3" TOPSOIL TH#4 - 0"-4" TOPSOIL
- Y-27" BROWN SANDY LOAM - 4"-26" BROWN SANDY LOAM
- 27"-68" GREY COMPACT SANDY TILL - 26"-30" SAND & GRAVEL
N4 WATER, MOTT@37", NO LEDGE - 30"-65" GREY COMPACT SANDY TILL
NO WATER, MOTT@26" , NO LEDGE
PERCOLATION TEST WAS PERFORMED BY DAVID COUGHLIN OF THE UNCAS HEALTH DISTRICT
ON 1-14-05.
PERCOLATION TEST PERCOLATION RATE = 20.0 MR- UTES/INCH
SANITARY DESIGN CRITERIA
DDnn1-%C11r-T1 A 79 7117 1 /1/1 1 & rr�rnr.
OUTLET L)hSIUN PERCOLATION RATE = 10.1-20.0 MINUTES/INCH
LEACHING AREA REQUIRED = 900 SF EFFECTIVE
DESIGN: 1,250 -GALLON SEPTIC TANK AND 2 ROWS OF 80' (56' AND 24') TOTALING 160'
FILTER E
FI� OF 4' WIDE, 8' LONG, 12" HIGH CONCRETE LEACHING GALLERIES WITH 12" OF I"
LT
U DEVJCE STONE SURROUNDING ALL SIDES (2' WIDTH OF STONE AT D -BOX).
LEACHING AREA PROVIDED: 2 x 84' x 5.9 SF/LF = 991.2 SF EFFECTIVE
100% RESERVE AREA PROVIDED (12" HIGH CONCRETE GALLERIES)
MINIMUM LEACHING SYSTEM SPREAD CALCULATION
HYDRAULIC GRADIENT = 5.0 %
DEPTH TO RESTRICTIVE LAYER = 37"
HYDRAULIC FACTOR = 26
FLOW FACTOR FOR 4 BEDROOMS = 2.0
PERCOLATION FACTOR FOR 10.1- 20.0 MINUTES/INCH = 1.5
MLSS REQUIRED = 78'
MLSS PROVIDED = 84'
l2" BROKEN STONE OR V SCREENED FINISHED GRADE
GRAVEL TYPICAL BOTH SIDES. LOAM & SHED, GR_kDE
48" TO PRE%-r.N PON-DNG PROJECT \TO. 04-142A
LIFTING HANDLES 4" DIA. HOLE DF`-`�'NN 'N 13Y- R.A.D.
DH
FILTER FABRIC DATE: 2/01;'05
REC. -
EE E SCALE, 1"=30'
_ SHEET 1 OF 1
N
6.Cr FL0W LINE REVISIoNs
m. KNOCKOUTS FOR TRENCH INSTALLATION �A -
4'x8"x 12" HIGH CONCRETE 18" MIN TO MOTTLING OR GROUNDWATER
LEACHING GALLERY 48" MIN. TO LEDGE%ROCK
END VIEW
12" HIGH GALLERY UNIT
NOT TO sCAU 30 15 C 30
GRAPHIC SCALE IN FEET
0
SEPTIC SYSTEM DESIGN PLAN
PREPARED FOR
WILLIAM PIENIADZ
FP���!�;
i
FELLOWS ROAD
MONTVILLE, CONNECTICUT
Robert J. Schuch, P.E.
CONSULTING ENGINEER
57 Sarah Drive Uncasviile, CT 06382
860-848-1539 Fax 860-848-1539
860-460-4369 rlschuc'h(a),snet.net
a„ -V
KNOCKOUT INLET AND
OUTLET OPENINGS
E
i
CAST
CONCRETE COVERS -
PLAN
CAPACITIES A B C
1250 GAL 61" 1 51" 148-
1500 GAL 69" 59" , 56-
4 x 4 12.6/12.6 GA. WLRE MESH
17 1/2" 6 x 6 6/6 GA. WIRE 'MESH
i..
4 I CONTINUOUS HOT f�'
oc I ASPHALT SEAL �J
" SCHED. #40
T &A PIPI IP
CROSS SECTION
1250/1500 GALLON
2 COMPARTMENT
SEPTIC TANK
NOT TO SCALE
NOTES:
1. THIS SEPTIC SYSTEM INSTALLATION INCLUDING ALL MATERIALS (PIPING, SEPTIC TANK,
STONE, FILL, ETC.) USED FOR THIS SEPTIC SYSTEM SHALL CONFORM TO THE CURRENT
EDITION/REVISION OF THE "TECHNICAL STANDARDS FOR SUBSURFACE SEWAGE DISPOSAL
SYSTEMS" REVISED JANUARY 1, 2004 OF THE CONNECTICUT PUBLIC HEALTH CODE BY THE STATE
OF CONNECTICUT DEPARTMENT OF PUBLIC HEALTH.
2. THE PROPOSED HOUSE SEWER FROM THE BUILDING TO THE SEPTIC TANK SHALL BE
SCHEDULE 40 PVC ASTM D 1785/ASTM D 2665 OR APPROVED EQUAL AND INDICATED IN TABLE NO.
2 OF "TECHNICAL STANDARDS FOR SUBSURFACE SEWAGE DISPOSAL SYSTEMS". ALL OTHER
SEWER PIPE FOR THIS SEPTIC SYSTEM SHALL BE 4" PVC ASTM D3034, SDR 35 WITH RUBBER
COMPRESSION GASKET OR BELL AND SPIGOT OR APPROVED EQUAL.
3. THERE ARE NO WELLS (POTABLE, GEOTHERMAL, OR IRRIGATION) WITHIN 75' OF THE
PROPOSED SEPTIC SYSTEM.
4. THERE SHALL BE NO STUMPS OR BOULDERS BURIED WITHIN 50' DOWN GRADIENT OF THE
SEPTIC SYSTEM. SHOULD ANY SIGNIFICANT VARIATIONS FROM THE 'FEST HOLE DATA BE
ENCOUNTERED DURING EXCAVATIONS (LEDGE, GROUNDWATER, MOTTLING, SOIL TYPE, ETC.),
THE DESIGN ENGINEER SHALL BE NOTIFIED PRIOR TO INSTALLATION OF THE SEPTIC SYSTEM.
5. ALL EXISTING UTILITIES ARE APPROXIMATE ONLY. THE CONTRACTOR SHALL VERIFY ALL
UTILITY LOCATIONS AND ELEVATIONS PRIOR TO ANY CONSTRUCTION. CONTRACTOR SHALL
CONTACT "CALL -BEFORE -YOU -DIG" AT 1-800-922-4455 AT LEAST 48 HOURS PRIOR TO ANY
EXCAVATION.
6. THE PROPOSED FILL FOR THIS SEPTIC SYSTEM SHALL MEET THE FOLLOWING SPECIFICATIONS:
A. 100% OF FILL SHALL PASS THROUGH A 3" SIEVE.
B. MAXIMUM % OF GRAVEL (BETWEEN #4 & 3" SIEVE) = 45 %.
C. GRADATION OF FILL WITHOUT THE GRAVEL SHALL MEET THE FOLLOWING CRITERIA:
SIEVE SIZE % PASSING (WET) % PASSING (DRY)
#4 100% 100%
#10 70-100% 70-100%
#40 10-50% 10-75%
#100 0-20% 0-5%
#200 0-5% 0-2.5%
D. * PERCENT PASSING THE #40 WET SIEVE CAN BE INCREASED TO NO GREATER THAN 75% IF THE
PERCENT PASSING THE #100 SIEVE DOES NOT EXCEED 10% AND THE #200 SIEVE DOES NOT
EXCEED 5 afro.
E. PERCOLATION RATE AFTER PLACEMENT AND COMPACTION SHALL BE FASTER THAN OR
EQUAL TO 20.0 MINUTES/INCH.
A WET OR DRY SIEVE ANALYSIS MAY BE REQUIRED PRIOR TO FILL PLACEMENT TO VERIFY THAT
IT MEETS THESE SPECIFICATIONS. THE FILL SHALL BE APPROVED BY THE UNCAS HEALTH
DISTRICT OR DESIGN ENGINEER PRIOR TO ITS PLACEMENT ON SITE.
7. APPROVED AGGREGATE SHALL BE STONE AGGREGATE OR OTHER PRODUCTS APPROVED BY
THE COMMISSIONER OF PUBLIC HEALTH. STONE AGGREGATE SHALL BE BROKEN STONE,
CRUSHED STONE, OR SCREENED GRAVEL MEETING THE CONNECTICUT DEPARTMENT OF
TRANSPORTATION FORM 814A (OR LATEST REVISION THERETO) SPECIFICATION M.01.01 FOR NO.4
STONE, FREE OF SILT, DIRT, OR DEBRIS, SHALL SHOW A LOSS OF ABRASION OF NOT MORE THAN
50% USING AASHTO METHOD T-96 AND CONFORM TO THE FOLLOWING:
SIEVE SIZE % PASSING
2 INCH 100%
1.5 INCH 90-100%
1 INCH 20-55%
3/4 INCH 0-10%
3/8 INCH 0-5%
8. NO DEVIATION FROM THE APPROVED DESIGN PLAN SHALL BE ALLOWED WITHOUT PRIOR
APPROVAL FROM THE UNCAS HEALTH DISTRICT AND THE DESIGN ENGINEER.
9. THE SEPTIC TANK SHALL BE PRECAST CONCRETE UNLESS OTHERWISE AUTHORIZED BY THE
DESIGN ENGINEER AND SHALL BE TESTED FOR WATER TIGHTNESS AFTER INSTALLATION.
10. SITE PREPARATION PROCEDURE FOR THE INSTALLATION OF THE PROPOSED SEPTIC SYSTEM:
A. STRIP ALL TOPSOIL, VEGETATION AND ORGANIC MATERIAL IN THE AREA OF AND 5'
SURROUNDING THE PRIMARY LEACHING GALLERIES.
B. USING A HEAVY RAKE OR EQUAL, THOROUGHLY SCARIFY AND ROUGHEN UP THE EXPOSED
SUBSOIL. PREVENT ANY VEHICULAR TRAFFIC, BACKHOE, TRUCKS, ETC. FROM
SMOOTHING/COMPACTING THIS EXPOSED SUBSOIL.
C. PLACE AND COMPACT SELECT FILL MATERIAL MEETING SPECIFICATIONS INDICATED ABOVE
(NOTE #6) IN LIFTS OF NOT GREATER THAN 12" IN THE AREA OF THE PROPOSED LEACHING
GALLERIES UP TO AT LEAST THE ELEVATION OF THE TOP OF THE LEACHING GALLERIES.
D. PERFORM AT LEAST 1 PERCOLATION TEST ON PLACED FILL. FILL MUST HAVE A PERCOLATION
RATE EQUAL TO OR FASTER THAN THAT AS INDICATED IN NOTE #6.D. IF PERCOLATION RATE IS
SLOWER THAN THAT RATE, ALL FILL SHALL BE REMOVED AND REPLACED WITH ACCEPTABLE
FILL MEET t ri PROPER. SPECIFICATIONS.
E. IN3-TA',L SEPTIC SYSTEM PER PLAN USFAG APPROVED AGGREGATE AS INDICA'.'ED IN NOTE #7.
F. COVER SYSTEM WITH A OF 6" OF LOAM IN LAWN AREAS, GRADE TO PREVENT
PONDING AND SEED WITH GRASS TO STABILIZE. THE FINISHED GRADE 10' FROM ANY PART OF
THE PROPOSED LEACHING GALLERIES SHALL BE AT LEAST THE SAME ELEVATION AS THE TOP OF
THE RESPECTIVE LEACHING GALLERY.
G. CLEANOUT MANHOLES AT THE INLET BAFFLE AND AT THE OUTLET FILTER OF THE SEPTIC
TANK OR ASSOCIATED RISERS AT THESE LOCATIONS IF REQUIRED SHALL BE LOCATED AT A
DEPTH NOT GREATER THAN 12" BELOW FINAL GRADE.
11. FOR EXACT HOUSE DIMENSIONS, SEE BUILDING PLANS.
TEST HOLE & PERC DATA
PER UNCAS HEALTH DISTRICT -10/14/04
TH#I - 0"-9" TOPSOIL TH#3 - 0"-7" TOPSOIL
- 9"-28" BROWN SANDY LOAM - 7"-38" BROWN SANDY LOAM
- 28A 1" SAND & GRAVEL - 38"-69" GREY COMPACT SANDY TILL
- 41 "-66" GREY COMPACT SANDY TILL NO WATER, MOTT@38", NO LEDGE
WATER@41 "„ MOTT@41 ", NO LEDGE
TH#2 - 0"-3" TOPSOIL TH#4 - 0"-4" TOPSOIL
- Y-27" BROWN SANDY LOAM - 4"-26" BROWN SANDY LOAM
- 27"-68" GREY COMPACT SANDY TILL - 26"-30" SAND & GRAVEL
N4 WATER, MOTT@37", NO LEDGE - 30"-65" GREY COMPACT SANDY TILL
NO WATER, MOTT@26" , NO LEDGE
PERCOLATION TEST WAS PERFORMED BY DAVID COUGHLIN OF THE UNCAS HEALTH DISTRICT
ON 1-14-05.
PERCOLATION TEST PERCOLATION RATE = 20.0 MR- UTES/INCH
SANITARY DESIGN CRITERIA
DDnn1-%C11r-T1 A 79 7117 1 /1/1 1 & rr�rnr.
OUTLET L)hSIUN PERCOLATION RATE = 10.1-20.0 MINUTES/INCH
LEACHING AREA REQUIRED = 900 SF EFFECTIVE
DESIGN: 1,250 -GALLON SEPTIC TANK AND 2 ROWS OF 80' (56' AND 24') TOTALING 160'
FILTER E
FI� OF 4' WIDE, 8' LONG, 12" HIGH CONCRETE LEACHING GALLERIES WITH 12" OF I"
LT
U DEVJCE STONE SURROUNDING ALL SIDES (2' WIDTH OF STONE AT D -BOX).
LEACHING AREA PROVIDED: 2 x 84' x 5.9 SF/LF = 991.2 SF EFFECTIVE
100% RESERVE AREA PROVIDED (12" HIGH CONCRETE GALLERIES)
MINIMUM LEACHING SYSTEM SPREAD CALCULATION
HYDRAULIC GRADIENT = 5.0 %
DEPTH TO RESTRICTIVE LAYER = 37"
HYDRAULIC FACTOR = 26
FLOW FACTOR FOR 4 BEDROOMS = 2.0
PERCOLATION FACTOR FOR 10.1- 20.0 MINUTES/INCH = 1.5
MLSS REQUIRED = 78'
MLSS PROVIDED = 84'
l2" BROKEN STONE OR V SCREENED FINISHED GRADE
GRAVEL TYPICAL BOTH SIDES. LOAM & SHED, GR_kDE
48" TO PRE%-r.N PON-DNG PROJECT \TO. 04-142A
LIFTING HANDLES 4" DIA. HOLE DF`-`�'NN 'N 13Y- R.A.D.
DH
FILTER FABRIC DATE: 2/01;'05
REC. -
EE E SCALE, 1"=30'
_ SHEET 1 OF 1
N
6.Cr FL0W LINE REVISIoNs
m. KNOCKOUTS FOR TRENCH INSTALLATION �A -
4'x8"x 12" HIGH CONCRETE 18" MIN TO MOTTLING OR GROUNDWATER
LEACHING GALLERY 48" MIN. TO LEDGE%ROCK
END VIEW
12" HIGH GALLERY UNIT
NOT TO sCAU 30 15 C 30
GRAPHIC SCALE IN FEET
0
SEPTIC SYSTEM DESIGN PLAN
PREPARED FOR
WILLIAM PIENIADZ
FP���!�;
i
FELLOWS ROAD
MONTVILLE, CONNECTICUT
Robert J. Schuch, P.E.
CONSULTING ENGINEER
57 Sarah Drive Uncasviile, CT 06382
860-848-1539 Fax 860-848-1539
860-460-4369 rlschuc'h(a),snet.net