HomeMy WebLinkAbout2003 - LP Heating and A/C Town of Montville
BUILDING DEPARTMENT
310 Norwich-New London Turnpike
Uncasville,CT 06382
(860)848-3030, Ext.382
Mechanical Permit
Permit Number: M2003-0061 Date: 27-May-03 Map/Lot: 074/038-000 Owner ID 117507
Job Location: 42 PINK ROW Unit
Job Description: Install AC Unit with Propane Heating Section
Owner: Contractor:
Martin Gottesdiener Titan Mechanical
C/O Kostin Ruffkess and Co 150 Batson Drive
400 Bayonet St Ste 306 Manchester
Ct. 06040-
New London
CT 06320 Telephone: (860)645-1617
Lic/Reg Type/No. S1 389112 Exp Date: 31-Aug-03
Tenant:
Self
Telephone:
Construction Values Permit Fees Construction Information
Building Value: $0.00 Building Fee: $0.00 Use Group: F-1
Plumbing Value: $0.00 Plumbing Fee: $0.00 Code: 1996 BOCA
Mechanical Value: $12,600.00 Mechanical Fee: $76.00 Construction Type: 5B
Electrical Value: $0.00 Electrical Fee: $0.00 Permit Code: C5
Other Value: $0.00 Other Fee: $0.00 Comments:
Total Value: $12,600.00 CO Fee: $0.00
Plan Review Fee: $0.00
State Ed Fee: $2.02
Total Fees: $78.02
It is the owners responsibility to schedule the following inspections(minimum 48 hours notice required):
❑ Footing-Prior to pouring concrete 0 Rough HVAC
❑ Backfill-Footing drains and waterproofing ❑ Fireplace Throat
❑ Concrete Slab-Prior to pouring concrete ❑ Chimney-One flue above thimble
❑ Rough Framing ❑ Firestopping/draftstopping
❑ Rough Electrical ❑ Insulation
❑ Electrical Service 0 Final Inspection
❑ Rough plumbing and leak test ❑ Certificate of Occupany
❑ Gas piping and test
Building Official's Signature: 41,
J
t
Town of Montville
't"' Building Department
310 Norwich-New London Tpke. Permit# �0 � �
Tel. 848-3030,Ext 82 Uncasville, CT 06382
Fax. 848-7231
Application for Commercial Trades Permit
•
F'fum6ing [] fECectricaf A techan"
:eating
—' Att.Conditioning
pots
Job Location 7 6 i.,i, _..g jd, 41 7/ Or 4) -
Job Description/Materials 4
116/1467,:----
Owner
,'1...,
Owner s_ / �
y 344. er 0.x'1 Mailing Address EPS /Vent-A- /(../L . //' A_
City L/ll��-44-- h, State (1 Pot) / Nef"/ 92,`7 /
Contractor '/���>t,t �/ /l -
�eCJ . Mailing Address /5 0 ZI ,-.�S-If'�. .L "? V`€,
City 1 1144 l(i 4 ep State f Zip .46lW Tel e10O /6- / /6/ 7
Contractor's License/Registration Type&Number 5-/
3� / — Exp.Date e? /31i/� 03
I hereby certify that the proposed work will conform to the Basic Building Code and all other codes as adopted by the
State of Connecticut and the Town of Montville and further attest that the proposed work is authorized by the owner in fee
and that I am authorized to make application for a permit for such work as described above.
Owner/Agent Signature ( ....-9 '
Date S / / / (�,.;;
Construction Value Fee
Building $ $
Plumbing $ $
Mechanical $ `24 $ 7 '
Electrical $
Other $ $
Certificate of Occupancy $
Plan Review Fee
State Education $
Total $ l Z r $ .,t.0
Town of 1 "ontville Building Departmc ` Receipt
*ofNoof
P
Date __ / L/__0
No. 02702
From:
Job Address: ffr J: -e ,0
Amount $
— t'a1.2 Cash Check Check #
1 / 4 circle one �iL��
Received by 41;,,...,,. ,/;
r./...„; .,00",,,,,-5 Permit # /
fr
•
STATE OF CONNECTICUT
WORKERS'COMPENSATION COMMISSION
Buildin: Permit Affidavit for Pro'e
Owners or Sole Pro rietors
(Conn. Gen. Stat. §31-286b)
Property located at 76
In the town of
C /il�
Name of building permit applicant ,/
/
Please check one:
1. I am the owner of the above property.
2. I am the sole proprietor of a business- •
—.Name of business
2B.Federal Employer Identification Number(FEIN
..........................
...........................•-..---......
Pursuant to §31-286b,"a
empty owner or sole intends•to act a.. ...n al
contractor or principal employer'mayproprietor[who] as a general _.
insurance or a"sworn no provide either a certificate of workers'compensation
compensation insurance for
�those�cmploycdon the job site in accordance proof of workers'
ccordance with this chapter."
Please check one:
1._I do not intend to act as a general contractor or principal employer.
[Sign and stop here]
Signature ofapplicant
2. I intend to act as a general contractor ornd i
r
provide a certificate of workers'compensation
�employer.Applicant mast either
below. insurance or sign the affidavit
Affidavit ... .... ... .
I hereby swear.and attest that I will require --....
contractor,subcontractor,or other wrker beforehe/sheh engagesof workers'
compensation insurance for every
accordance with the Workers'Com in work on the above property in
Compensation Act(Chapter 568).
I understand that pursuant to§31-275 C.G.S.,officers of a co
partnership may elect to be excluded from coverage by filingcorporation and thetapp in a
District Office;and that a sole proprietor of a business is nowaiver to haveith appropriate
files his intent to accept coverage. required coverage unless he
Signature of applicant
Subscribed and sworn to before me this
day of
200_
(Notary Public!Commissioner of the Superior Court)
,1fi,,,m, Y.„``P, r> '� '/ t,;•4`1k■ ,,,--,1/4, cJ, ,"4 ' ' `.. \i':'''.:1,1',.-� .. 4,1';::T'' 1 h.:•::t4 '41',:-.,":!1.,l,`l vi '�' r n,-,-..'..P3,-..,..'s!. ...-,'C's. 'S�tk , T :. ,Th.,:- o'
;' :.f,L }- ..f,+i. ^efl'$ r ■ .�+ f moi+. t,moi• f,IL.,.'-',,f f Yi}�'i,5. f":,._-,,,f Al
"`� 7 + f �' r�
4
-2 , ..+*t *.ti ..,1 N. .ter#"*- -v.
-17'rx •sr^'a �-�x.�� sr� .... tee. :. :.
'dy
_•a.,�..,:' .�,- '� � '��'e® :.a.,... ' ,an =..�., is
i , STATE OF CONNECTICUT + DEPARTMENT OF CONSUMER PROTECTION , r s`.,`
F
A.
i Beit known that
f i
MARK CONLOGUE {-r
9 y. ICE DR
BU4 ‘) CT 06013 i .;F
, k•-
Y has been certified by the Dap ! ent ? _ ns`umer Protection as a licensed t
.-# HEATING, PIPING & , Vii,i� t s r. LIMITED CONTRACTOR [,-y
i
f ; ' Z I' ;
\� ,' ,JS4.-\N; i:Uk
it TQANSTV may- I
f Effective: 09/01/2002 i k '
x' Expires: 08/31 a"r
2003r,c,,m,,,,rift„,.47 1 ZN%,
'
Jam s T.Fleming,Commissioner j "3
t , y
4
aL • ., 4 ,. Jt'' .G,,G)i, •.t 'G;A c W.1P',n Jkd , �+r :r 0 i #',1,1P<:'‘ ,Lil; -.t ,,.`: ' Op•n;tr:.i pc tc.'i'
TOWN OF MONTVILLE
FIRE MARSHAL'S OFFICE PEWZ.-/0 �h�/E/C
310 NORWICH NEW LONDON iT J
UNCASVILLE, CONNECTICUT 0
860-848-1175 A7/-1-k-AN/45.M/c /0A.0,01)/OC t()
41e41,7- SGN Q 5h c0,3T
�aES_her -" :";C./ ne et4 .e".
Mem,
,,,o ____
,,„,,c ,,,/,./
Date: 5/5/03 `5',/,
_.... .....__
Case # FM02-0595
To: Mr. Vernon Vesey II
Building Official
310 Norwich New London Tpke.
Uncasville, CT 06382
Subject: Plan Review for T.G. Faria Corp. installation of a HVAC unit
Dear Vern,
The Town of Montville Fire Marshal's Office received and reviewed plans submitted by
Jeffrey Palmer of Titan Mechanical Contractors 150 Batson Drive Manchester CT 860-645-1617.
And see no reason not to issue a permit.
NOTE: Scheduling of Propane Hookup/Testing to and from building should also go through the Fire
Marshals Office.
Any items that might have been inadvertently overlooked in the plan review do not relieve the owner from
achieving code compliance.
A final inspection will be required by the Fire Marshal's Office prior to unit being operated/started.
Should you need further assistance or have any questions, please contact the undersigned.
Respectfu ,
4
Roy(Ed) S afer
Fire Inspector
cc: file
Titan
Mechanical
Contractors, Inc.
150 Batson Drive
Manchester,CT
06040-1694
v:860-645-1105
f:860-645-1176
www.titanmechanical.com
April 28, 2003
Re: HVAC Permit
To whom it may concern:
Jeffrey M. Palmer is authorized by the undersigned as agent of Titan Mechanical
Contractors, Inc. to procure the above referenced permit. This permit request is for
work to be done at:
Thomas G. Faria Corporation
385 Norwich-New London Tnpk.
Uncasville, CT 06382-0983
The job is to install one Packaged A.C. Unit with Propane Fired Heating Section. The
cost of this work is: Twelve thousand six hundred dollars, ($12,600.00).
Attached is a photo-copy of my current Connecticut contractor's license.
Signed: Date: y�94,-P
Printed Name and Title: Xi/041e C✓®/1)L
ppI. = a PPL Corporation company
CT License P-1#279991 S-1#303307
certificate is executed by Liberty Mutual Insurance Group as respects such insurance as is afforded by those co .anies.
Certificate of Insurance BM0068
This certificate is issued as a matter of information only a ifers no rights
afforded by the policies listed below. upon you the certificate holder. This certificate is n isurance policy and does not amend,extend,or alter the coverage
This is to certify that(Name and address of Insured)
41111.
TITAN MECHANICAL CONTRACTORS rte.
150 BATSON DRIVE fh4 - ;
f..,.. , m.._... ...timi...
MANCHESTER CT 06040 A
is,at the issue date of this certificate,insured by the Company tinder the policy(ies)listed below. The insurance afforded by the listed policy(ies)is subject to all their terms,exclusions and conditions
and is not altered by any requirement,term or condition of any contract or other document with respect to which this certificate may be issued.
Expiration Type Expiration Date(s) Policy Number(s)
Continuous* 12/31!2003 Limits of Liability
WA 1-11 D-254244-012 Coverage afforded ander WC law of Employers Liability
Extended the following states:
X Policy Term Bodily Injury By Accident
CT,MA,NY $100,000 Each Accident
Bodily Injury By Disease
$500,000 Policy Limit
Workers Compensation Bodily Injury By Disease
$100,000 Each P crsta
12/31/2003 YYI-111-254244-022 General Aggregate-Other than Prod/Completed Operations
General Liability $2,000,000
Products/Completed Operations Aggregate
Claims Made $2,000,000
X Occurrence
Bodily Injury and Property tyDamage Liability 1 Per
$1,000,000 Occurrence
Retro Date Personal and AdvertisingInjury Jm'Y Per Person/
$1,000,000 Organization
Other Liability Other Liability
12/31/2003 AS2-111-254244-042 Each Accident-Single Limit-B.I.and P.D.Combined
Automobile Liability $1,000,000
Each Person
X Owned
X Non-Owned Each Accident or Occurrence
X Hired
Each Accident or Occurrence
C l These policies include Deductible Endorsement with$250,000 deductible limit per occurence for Workers Compensation and$25,000 limit per occurence for General
O Liability with the provision that Liberty Mutual will advance payment of the deductible amount.
M
M
E
N
T
S
'If the certificate expiration date is continuous or extended term,you will be notified if coverage is terminated or reduced before the certificate expiration date. However,you will not be notified annually
of the continuation of coverage.
Special Notice-Ohio:Any person who,with intent to defraud or knowing that he/she is facilitating a fraud against an insurer,submits anapplication or files a claim containinga false or
deceptive statement is guilty of insurance fraud.
Important information to Florida policyholders and certificate holders:in the event you have any questions or need information about this certificate for any reason,please contact your local sales
producer,whose name and telephone number appears in the lower left corner of this certificate. The appropriate local sales office
Notice of cancellation: (not mailing address may also be obtained by calling this number.
applicable unless a number of days is entered below). Before the stated expiration date the company will not cancel or reduce the insurance afforded under the above
policies instil at least 30 days notice of such cancellation has been mailed to:
Office: DANVERS,MA Phone: 800-566-0323 f•., r
Certificate Holder:
Maria G.Abrantes
Authorized Representative
Date Issued: 04/24/2003 Prepared By: NT
TgA /LEz
77z4/LgR..
Tk•tle Ler
yex‘
SI 1>e
TYR OF(4)
E i
� E
uP
Dowist
(7. FAR/A
Town of Montville
Plans Approved for Construction
Approval shall not be construed
as a permit for,or approval of,
any violation of the provisions
o the Connecticut Building Cod
Copy O File Co'
`
J / e3 i
NO 3'0ExrEItoFZ c A--"Es g SWAL-4.
SLE, ANL /ri eiz,A7'EI) 7V R-7
arZ ReTTEA4
Privra-477o1.1 AiR SHALL I E ,f o o C►-i
o SMOKE ;55 e 31/4t,.L 3HurI oWN
YS7EM ScovveR., chive ` Pt lv' ACT1(/4J'1oA1
r �Nr
sow
/� c m
r • :
1
DETAILED SYSTEM LOAD REPORT
System:System 1
Location:Hartford, Connecticut Block Load 3.05
Prepared by:Aire Tech April 28,
Page:ge: 1
1
t TABLE 1.CALCULATION INFORMATION
Design Load: July 17:00
Db/Wb Temp 88.8/73.4 F
r Winter Design Temo • 3.0 F
f TABLE 2.LOAD COMPONENT SUMMARY
Design Cooling Loads Design 7
Sensible Latent Heating
Load Component Details (BTU/hr) (BTU/hr) (BTU/hr)
Solar Loads 0 sqft 0
Wall Transmission 3,380 sqft 5,703 - 23,099
Roof Transmission 3,324 sqft 11,919 - 29,843
Glass Transmission 0 sqft 0 - 0
Skylight Transmission 0 sqft 0 - 0
Partitions 0 sqft 0 - 0
lighting 2.00 W/sqft 22,682 - -
-
Other Electric 0.00 W/sqft 0 -
People 8 People 2,451 3,781
Infiltration 6,932 7,924 33,655
Miscellaneous 0 0
Slab 3,324 sqft - - 23,308
Pulldown/Warm-Up 0
Safety Factor 0/0/0 % 0 0 0
Total Zone Loads 49,688 11,705 109,905
-Ventilation Load 208 CFM 3,095 3,537 1-5,025
Supply Fan Load 2,557 CFM 2,843 - -
Plenum Load thru Wall 0 % 0
Plenum Load thru Roof 0 % 0
-
Plenum Load-Lights 0 % 0 - -
Reheat Load 0 -
Total Coil Loads 55.626 14.243 124.930
TABLE 3.WALL AND GLASS BREAKDOWN
Total Cooling Cooling Heating i
Net Area Transmission Solar Load Transmission
Component (sgft) (BTU/hr) (BTU/hr) (BTU/hr)
Walls: NE 1,216 1,894 - 8,310
E 0 0 - 0
SE 0 0 - 0
S 1,240 2,265 - 8,474
SW 0 0 - 0
W 924 1,544 - 6,315
NW 0 0 - 0
N 0 0 - 0
Glass: NE 0 0 -- 0 0
E 0 0 0 0
SE 0 0 0 0
S 0 0 0 0
SW 0 0 0 0
W 0 0 0 0
NW 0 0 0 0
N 0 0 0
nor 0 0I
0 0 0
i • a
J
SYSTEM SIZING SUMMARY
System: System 1
Location:Hartford, Connecticut Block Load 3.05
Prepared by:Aire Tech April 28,2003
Page: 1
[TABLE 1.SIZING DATA(COOLING) `
Total Coil Load 70,868 BTU/hr Load Occurs 1
55,626 BTU/hr Sensible Coil Load July 173.4
r Outdoor Db/Wb 88.8/73.4 F
Total Zone Sensible 49,688 BTU/hr Coil Conditions:
Supply Temperature 57.0 F
Entering Db/Wb 77.2/65.6 F
Supply Air(Actual) 2,557 CFM
Supply Air(Standard) 2,556 CFM Apparatus DewWb 57.0/56.5 F
point 55.9 F
Ventilation Air 208 CFM Bypass Factor 0.050
Direct Exhaust Air 0 CFM Resulting Zone RH 57. %
Reheat Required 0 BTU/hr
Total Coil Load 5.91 Ton
Floor Area 3,324 sqft Sensible Coil Load 4.64 Ton
Overall U-Value 0.118 BTU/hr/sqft/F SQFT/Ton 562.85
Vent Air 0.06 CFM/sqft Cooling 21.32 BTU/hr/sqft
Vent Air 25.00 CFM/Person Cooline
0.77 CFM/soft
TABLE 2.SIZING DATA(HEATING)
Heating Coil Load 124,930 BTU/br Heating 37.58 BTU/hr/sqft
Ventilation Load 15,025 BTU/br Heating 0.77 CFM/sqft
Total Zone Load 109,905 BTU/hr Floor Area 3,324 sqft
Ventilation Airflow 208 CFM Overall U-Value 0.118
Supply Airflow 2,557 CFM Vent Air 0.06 CFM/sqft
Vent Air 25.00 CFM/Person
[TABLE 3.INPUT DATA(WEATHER) `
Location Hartford,Connecticut t
Data Source User Defined Summer Dry-Bulb 91.0 F
Latitude 41.7 Degree Coincident Wet-Bulb 74.0 F
Elevation 15.0 ft Daily Range 22.0 F
Atmosuheric Clearness# 1.00 Winter Drv-Bnlh- 3.0 F
TABLE 4. INPUT(HVAC SYSTEM) -,i
System Name System 1 THERMOSTAT SETPOINTS
System Type Clg and Warm Air Ht Cooling(Occ.) 75.0 F
System Start 6:00 Cooling(Unoce.) 75.0 F
Duration 24 hrs Heating 70.0 F
SIZING SPECIFICATIONS RETURN AIR PLENUM
No
Supply 57.0 F FAN
Ventilation 25.00 CFM/person Configuration Blow-Thru
Exhaust 0.00 CFM Static Pressure
FACTORS 1.50 in.wg.
Coil Bypass 0.050
Safety(Sens) 0
Safety(Latent) 0
Heating Safety 0
r
[TABLE 5. TOP TEN COOLING COIL LOADS
Time Sensible Ton Total Ton Time Sensible Ton Total Ton
1) July 17:00 4.64 5.91 6) August 16:00 4.53 5.80
2) July 16:00 4.63 5.90 7) August 15:00 4.45 5.71
3) July 15:00 4.56 5.82 8) August 18:00 4.45 5.71
4) July 18:00 4.55 5.82 9) July 19:00 4.40 5.66
5) August 17:00 4.53 5.80 10) July 14:00 4.39
5.64
it a,. • +
SYSTEM SIZING SUMMARY
System:System 1
Location:Hartford, Connecticut Block Load 3.05
April 28,2003
Prepared by:Aire Tech
Page:2
[TABLE 6. ZONE SIZING DATA
Max.Cooling Design Airflow Max.Heating Design Flow
Sensible Rate Load Rate
Zone Name (BTU/hr) (CFM) Design Time (BTU/hr) (CFM)
Loading Dock 49,688 2,557 July 17:00 109,905 -
Total: 2,557 Total: .00
w 1
I.
036-21058-003-A-1102
421YORK® DESCRIPTION
Heating and Air Conditioning YORK®Predator units are convertible single packages
with a common footprint cabinet and common roof curb for
all 6-1/2 through 12-1/2 ton models.All units have two
compressors with independent refrigeration circuits to pro-
TECHNICA L vide two stages of cooling. The units were designed for
commercial applications and can be easily installed on a
roof curb,slab,or frame.
GUIDEAll Predator."" units are self-contained and assembled on
rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging.Every unit is completely
rA p PLCM Tii(j1 P TM charged,wired, piped,and tested at the factory to provide
a quick and easy field installation.
All units are convertible between side and down airflow. A
independent economizer design is used on side and down
discharge applications, as well as all tonnage sizes.
STANDARD EFFICIENCY Predator-T'" units are available in the following configura-
tions:cooling only, cooling with electric heat, and cooling
SINGLE PACKAGE AIR CONDITIONERS AND with gas heat. Electric heaters are available only as field-
installed accessories.
SINGLE PACKAGE GAS/ELECTRIC UNITS
DM 078, 090, 102, 120, 150
6-1/2, 7-1/2, 8-1/2, 10, 12-1/2 NOMINAL TONS
9.0 EER
te MYORK
7F i. Tested in accordance with:
L
'
_ _
DESIGN
1 s•
ell4
rt OW
CEN TIFIEO
L p1.c,CD TO 4,44.,
�
P C
94,
� .
E /
2. •
t(P)Iir
FTIF
t�'ST4NWP0
FOR DISTRIBUTION USE ONLY-NOT TO BE USED AT POINT OF RETAIL SALE
036-21058-003-A-1102
TABLE OF CONTENTS
DESCRIPTION 1 LIST OF TABLES
FEATURES 3 Tbl. # Pg. #
FACTORY INSTALLED OPTIONS 5 1 ACCESSORIES 7
FIELD INSTALLED ACCESSORIES 6 2 PRODUCT NOMENCLATURE 8
GUIDE SPECIFICATIONS 40 3 AIRFLOW ABBREVIATIONS 9
4 INSTALLATION ABBREVIATIONS 9
LIST OF FIGURES 5 ADDITIONAL OPTIONS ABBREVIATIONS 9
Fig. # Pg. # 6 PHYSICAL DATA 10
1 PREDATORY" COMPONENT LOCATION 3 7 STANDARD EFFICIENCY DM MODELS 11
2 UNIT 4 POINT LOAD 33 8 UNIT VOLTAGE LIMITATIONS 11
3 UNIT CENTER OF GRAVITY 33 9 COOLING CAPACITY 6-1/2 TON UNIT 12
4 UNIT 6 POINT LOAD 33 10 COOLING CAPACITY 7-1/2 TON UNIT 13
11 COOLING CAPACITY 8-1/2 TON UNIT 14
5 UNIT DIMENSIONS 34
12 COOLING CAPACITY 10 TON UNIT 15
6 PREDATORY" ROOF CURB DIMENSIONS . . 35 13 COOLING CAPACITY 12-1/2 TON UNIT 16
7 SUNLINETM TO PREDATORY" TRANSITION 14 ELECTRICAL DATA 6-1/2 TON-STD. EFF 17
ROOF CURBS 35
15 ELECTRICAL DATA 7-1/2 TON-STD. EFF 18
8 BOTTOM DUCT OPENINGS (FROM ABOVE) 36 16 ELECTRICAL DATA 8-1/2 TON-STD. EFF 19
9 REAR DUCT DIMENSIONS 36 17 ELECTRICAL DATA 10 TON-STD. EFF. 20
10 COOLING UNIT WITH GAS HEAT WIRING 230 18 ELECTRICAL DATA 12-1/2 TON-STD. EFF 21
VOLT DIAGRAM 37 19 ELECTRIC HEAT MULTIPLIERS 21
11 COOLING UNIT WITH/WITHOUT ELECTRIC 20 BLOWER PERF 6-1/2 TON SIDE DUCT 22
HEAT WIRING DIAGRAM 38
21 BLOWER PERF 7-1/2 TON SIDE DUCT 23
12 COOLING UNIT WITH GAS HEAT WIRING 460, 22 BLOWER PERF 8-1/2 TON SIDE DUCT 24
575 VOLT AND 50 HZ DIAGRAM 39
23 BLOWER PERF 10 TON SIDE DUCT 25
24 BLOWER PERF 12-1/2 TON SIDE DUCT 26
25 BLOWER PERF 6-1/2 TON DOWNSHOT 27
26 BLOWER PERF 7-1/2 TON DOWNSHOT 28
27 BLOWER PERF 8-1/2 TON DOWNSHOT 29
28 BLOWER PERF 10 TON DOWNSHOT 30
29 BLOWER PERF 12-1/2 TON DOWNSHOT 31
30 ADDITIONAL STATIC RESISTANCE 32
31 INDOOR BLOWER SPECIFICATIONS 32
32 4 POINT LOAD WEIGHT 33
33 6 POINT LOAD WEIGHT 33
34 UNIT WEIGHT 33
35 UNIT CLEARANCES 34
2 Unitary Products
036-21058-003-A-1102
"Simplicity"Control Board w/
Terminal Block Screw Connector for T-stat Disconnect Location Filter Access
S
for Hi-Voltage Wiring and Network Filter-Drier olid Core
Connection Connection (Optional Disconnect Switch) (2"Filters) ( )
Condenser
Section
-AO/Second model
nameplate inside •
hinged access
panel Belt-Drive
Blower Motor
Dual stage
cooling for lEe:t0r
='-:'''Alb easy adjustment
Compressor 1 and service.
#2 Access
r r(High-Eff I 'k �/CtCompressor w/crankcase , -t aheater)
Base Rails w/Forklift - Power Ventor Motor
Slots(3 Sides)&Lifting
Holes ---------hi.
heat-
RoofIs/\
curbs in eight-and ` r Two-stage gas fourteen-inch heights. \ ol°' ing warm,to comfort
Slide-Out Drain comfortable
Rood curbs for transi- Pan w/Steel 3/4"
tioning from York Sun- ,� temperature
line footprint to the DM
Tool-less FPT Connection
Series footprint are also door latch Side entry power Intelligent control board for
and control wiring C mpressor#1 Access(High-Eff
available(field-installed knockouts Compressor w/crankcase heater) safe and efficient operation
accessory)
FIGURE 1 : PREDATORTM COMPONENT LOCATION
FEATURES Service windows have been placed in both condenser
• Standard Efficiency—All standard efficiency units have section walls. Rotation of the cover allows easy access
a minimum EER of 9.0. Gas/electric units have elec—
tronic spark ignition and power vented combustion with Both the unit control board and ignition control board uti-
steady state efficiencies of 80%. lize flash codes to aid in diagnosis of unit malfunctions.
• Service Friendly—The Predator" incorporates a num- Unique alarm codes quickly identify the source of the
ber of enhancements which improve serviceability. unit alarm.
All units use the same standard filter size. This stan-
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor dardization removes any confusion on which filter sizes
airflow components, thus simplifying if maintenance and are needed for replacement.
9
adjustment. The non-corrosive drain pan slides out of the unit to per-
ing
Service time is reduced through the use of hinged, tool- mit easy cleaning. The drain pan is accessed by remov-
less panels. Such panels provide access to frequently On the drain pan cover plate on the rear of the unit.
inspected components and areas, including the control Once the plate is removed, the drain pan slides out
box, compressors,filters, indoor motor&blower, and the through the rear of the unit.
heating section. The panels are screwed in place at the All PredatorTm units have a second model nameplate
factory to prevent access by children or other unautho- located inside the control access door. This is to prevent
rized persons. It is recommended that the panels be deterioration of the nameplate through weathering.
secured with screws once service is complete.
Unitary Products
3
•
036-21058-003-A-1102
• Environmentally Aware — For improved Indoor Air • Nuisance Trip Protection and Strikes-To prevent
Quality, foil faced insulation is used exclusively through- nuisance trouble calls, the control board uses a
out the units. "three times, you're out" philosophy. The high and
• Balanced Heating — The PredatorTm offers "Ultimate low-pressure switches and the freezestats must trip
three times within two hours before the unit control
Heating Comfort" with a balance between 1st and 2nd
board will lock out the associated compressor.
stage gas heating. The 1st stage of a gas heat Preda-
tor" unit provides 60% of the heating capacity. Bal- •
On Board Diagnostics-Each alarm will energize a
anced heating allows the unit to better maintain desired trouble light on the thermostat, if so equipped, and
temperatures. flash an alarm code on the control board LED. Each
• high and low-pressure switch alarm as well as each
Convertible Airflow Design —The side duct openings freezestat alarm has its own flash code. The control
are covered when they leave the factory. If a side sup- board saves the five most recent alarms in memory,
ply/return is desired,the installer simply removes the two and these alarms can be reviewed at any time.
side duct covers from the outside of the unit and installs Alarms and programmed values are retained
them over the down shot openings. No panel cutting is through the loss of power.
required. Convertible airflow design allows maximum
field flexibility and minimum inventory. • Reliable—From the beginning—All units undergo com-
puter automated testing before they leave the factory.
• System Protection — Suction line freezestats are sup- Units are tested for refrigerant charge and pressure, unit
plied on all units to protect against loss of charge and coil amperage, and 100% functionality. For the long term —
frosting when the economizer operates at low outdoor air All PredatorTM units are painted with a long lasting, pow-
temperatures while the compressors are running. Every der paint that stands up over the life of the unit.The paint
unit has solid-core liquid line filter-driers and high and used has been proven by a 750 hour salt spray test.
low-pressure switches. Internal compressor protection is
•
standard on all compressors. Crankcase heaters are Flexible Placement — All models and configurations
share the same cabinet/footprint and thus the same roof
standard on reciprocating compressors. Scroll compres
sors do not require crankcase heaters. curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
• Advanced Controls - PredatorT" control boards have internal loads have been determined.
standardized a number of features previously available
To further simplify planning and installation, Predator."'as options or by utilizing additional controls.
cabinets are designed to fit your roof. With the optional
• Low Ambient - An integrated low-ambient control roof curb, the unit ductwork is designed to fit around 24"
allows all units to operate in the cooling mode down on-center joists or between 48"on-center joists.
to 0°F outdoor ambient without additional assis-
The drain pan can be rotated to drain to either the front
tance. Optionally, the control board can be pro-
or the rear of the unit. Additionally, the drain pan can be
grammed to lockout the compressors when the
Piped to drain through the roof curb. As it is sometimes
outdoor air temperature is low or when free cooling
is available. difficult to have a level installation,the drain pan features
a generous slope to ensure proper drainage.
• Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the •
Full Perimeter Base Rails—The permanently attached
base rails provide a solid foundation for the entire unit
standard controls. Compressor reliability is further
and protect the unit during shipment. The rails offer fork-
ensured by programmable minimum run times. For
lift access from 3 sides, and rigging holes are available
testing,the anti-short cycle delay can be temporarily
overridden with the push of a button. so that an overhead crane can be used to place the units
on a roof.
• Fan Delays-Fan on and fan off delays are fully pro-
• Easy Installation—Gas and electric utility knockouts are
grammable. Furthermore, the heating and cooling
supplied in the unit underside as well as the side of the
fan delay times are independent of one another. All
unit. A clearly identified location is provided to mount a
units are programmed with default values based
field supplied electrical disconnect switch. Utility con-
upon their configuration of cooling and heat.
nections can be made quickly and with a minimum
• Safety Monitoring-The control board monitors the amount of field labor.
high and low-pressure switches,the freezestats,the
gas valve, if applicable, and the temperature limit All units are shipped with 2"filters installed.
switch on gas and electric heat units. The unit con- Wide Range of Indoor Airflows—All indoor fan motors
trol board will alarm on ignition failures, compressor are belt-drive type providing maximum flexibility to han-
lockouts and repeated limit switch trips. dle most airflow requirements. For high static applica-
tions, factory installed alternate indoor fan motors are
4
Unitary Products
036-21058-003-A-1102
available. With the optional indoor fan motor, all units the two enthalpy or temperature inputs and positions the
can supply nominal airflow at a minimum of 1.5" ESP. dampers to provide the maximum efficiency possible.
• Warranty -All models include a 1-year limited warranty • Sideflow Economizer- (Without barometric relief) -All
on the complete unit. Compressors and electric heater features as the downflow economizer exist except you
elements each carry a 5-year warranty. Aluminized steel must order the barometric relief separately. You must
and stainless steel tubular heat exchangers carry a addi- order a 1 EH0408 if you are installing a power
tional 10-year warranty. exhaust. You can order a 1 RD0411 barometric relief
for sideflow economizer only.
FACTORY INSTALLED OPTIONS • Motorized Outdoor Air Damper - The motorized out-
YORK®offers several equipment options/accessories factory door air damper includes a slide-in/plug-in damper
installed,for the Predator"'line. assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
• Alternate Indoor Blower Motor- For applications with indoor fan motor is energized. The damper has a range
of 0%to 100%outdoor air entry. Factory installed option
high restrictions, units are offered with optional indoor
motors that provide higher static output and/or higher air or field installed accessory.
flow,depending upon the installer's needs. • Power Exhaust (Downflow only) - This accessory
• Coil Guard-Customers can purchase a coil guard kit to installs in the unit with a down flow economizer. Power
exhaust plugs into the connector in the unit bulkhead.
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering • Phase Monitors - Designed to prevent unit damage.
the space between the inner condenser coil and the The phase monitor will shut the unit down in an out-of-
main cabinet.This is not a hail guard kit. phase condition. (Standard on units with Scroll Compres-
• Convenience Outlet - (Non-Powered) - This option sors.)
locates a 120V GFCI single-phase outlet with cover on • Smoke Detectors-The smoke detectors stop operation
the corner of the unit housing the compressors. The of the unit by interrupting power to the control board if
installer must provide the 120V single-phase power smoke is detected within the air compartment.
source and wiring. Factory installed option only.
• Stainless Steel Heat Exchanger - For applications in
• Dirty Filter Switch -This kit includes a differential pres- corrosive environments, this option provides a full stain-
sure switch that energizes the fault light on the unit ther- less steel heat exchanger assembly.
mostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option • Technicoat Condenser Coils-The condenser coils are
or field installed accessory. coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
• Disconnect Switch - For gas heat units, a HACR
breaker sized to the unit is provided. For cooling units • Technicoat Evaporator Coil - The evaporator coil is
with electric heat, a switch sized to the largest electric coated with a phenolic coating for protection against
heat available for the particular unit is provided. Factory harsh environments.
installed option only.
• Novar® BAS Control - The Novar® ETC-3 building
• Downflow Economizer - (With barometric relief) - The automation system controller is factory installed. Incudes
economizer is provided with a single enthalpy input. The supply air sensor, return air sensor, dirty filter indicator
economizer is 2% low leakage type. The economizers switch, and air proving switch.
are shipped installed and wired. The installer needs only • Johnson Controls BAS Control-The Johnson Control
assemble and mount the outdoor air hood. The econo-
YK-UNT-1126 building automation system controller is
mizer has spring return, fully modulating damper actua factory installed. Includes supply air sensor, return air
tors and is capable of introducing up to 100%outdoor air.
As the outdoor air intake dampers open, the return air sensor,dirty filter indicator switch,and air proving switch.
dampers close. The changeover from mechanical refrig- • CPC BAS Control - The Computer Process Controls
eration to economizer operation is regulated by the stan- Model 810-3060 ARTC Advanced Rooftop building auto-
dard single enthalpy input. There is an optional input mation system controller is factory installed. Includes
dual dry bulb available.To meet regulated air standards, supply air sensor, return air sensor, dirty filter indicator
the economizer control accepts an optional CO2 input for switch, and air proving switch.
demand ventilation.
• Honeywell BAS Control - The Honeywell W7750C
With single enthalpy input,the economizer control moni- building automation system controller is factory installed.
tors outdoor air.The dual enthalpy kit provides a second Includes air supply sensor, return air sensor, dirty filter
input used to monitor the return air. With a dual input kit indicator switch, and air proving switch.
installed, the economizer control compares the values of
Unitary Products 5
036-21058-003-A-1102
• BAS Ready Economizer- The economizer is provided are included with the heaters. All heaters are intended
with a Belimo actuator that requires a 0-10V DC input for single point power supply.
from an external source(i.e.,field installed building auto-
• Flue Exhaust Extension Kit- In locations with wind or
mation system controller). Barometric relief or power
exhaust options are available.The economizer is 2%low weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can
leakage type with spring return and fully modulating
dampers capable of introducing up to 100% outside air. be installed to prevent the flue exhaust from entering
Also include 2"pleated filters. nearby fresh air intakes.
• Gas Heat High Altitude Kit — This kit converts a gas
FIELD INSTALLED ACCESSORIES
heat unit to operate at high altitudes,2,000 to 6,000 feet.
YORK®offers several equipment options/accessories for field Conversion kits are available for natural gas and pro-
installation,for the Predator'"Magnum line. pane.
• Gas Heat Propane Conversion Kit-This kit converts a
• -60°F Gas Heat Kit- For installations which require gas
heat units to perform in low ambient temperatures, a gas gas-fired heater from natural gas to propane. It contains
the main burner orifices and gas valve replacement
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas springs.
valve and controls will continue to function properly at •
Hail Guard - This kit includes a sloped hood which
extremely low temperatures. installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
• Barometric Relief- Zero to 100% capacity barometric
relief damper for use with sideflow economizer. accessory only.
• Manual Outdoor Air Damper - Like the motorized out-
• Burglar Bars-Mount in the supply and return openings door air damper, each manual outdoor air damper
to prevent entry into the duct work. includes a slide-in damper assembly with an outdoor air
• CO2 Sensor - Senses CO2 levels and automatically hood and filters. Customers have a choice of dampers
overrides the economizer when levels rise above the with ranges of 0% to 100% or 0% to 35% outdoor air
preset limits. entry.
•
• Coil Guard-Field installed decorative wire coil guard. Power Exhaust-This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
• Dirty Filter Switch -This kit includes a differential pres- connector in the unit bulkhead. You must purchase
sure switch that energizes the fault light on the unit ther- 1 EH0408 barometric relief/power exhaust hood when
mostat, indicating that there is an abnormally high applying to a sideflow application.
pressure drop across the filters.
• Roof Curbs - The roof curbs have insulated decks and
• Enthalpy Accessory Control Kit-This kit contains the are shipped disassembled The roof curbs are available
required components to convert a single enthalpy econo- in 8"and 14"heights.
mizer to dual enthalpy.
For applications with security concerns, burglar bars are
• Economizer (Downflow with barometric relief) - Econo- available for the duct openings of the roof curbs.
mizer with relief damper and single enthalpy input (2%
low leakage damper). • Roof Curb Adaptor Single Piece Adapter (10" High) -
Roof curbs for transitioning from SunlineTM units to Pred-
Spring return fully modulating motor capable of introduc- atorT"' Magnum. Fits 7.5 to 12.5 SunlineT"" roof curbs
ing up to 100% outside air. For power exhaust, add the only.
power exhaust accessory.
• Smoke Detectors-The smoke detectors stop operation
• Economizer (Horizontal) - Horizontal economizers are of the unit by interrupting power to the control board if
designed to install in the lower return section on the side smoke is detected within the air compartment.
of the unit. It is specifically designed for horizontal return
• Thermostat-The units are designed to operate with 24-
applications. 1 EH0408 barometric relief/power
volt electronic and electro-mechanical thermostats. All
exhaust hood must be purchased separately. You
units (with or without an economizer) operate with two
may also order a 1RD0411 barometric relief if a
stage heat/two-stage cool or two-stage cooling only ther-
power exhaust isn't being installed. The horizontal
economizer is available with standard single enthalpy mostats, depending upon unit configuration.
control. Dual enthalpy may be added by installing the • Motorized Outdoor Air Damper - The motorized out-
dual enthalpy kit. door air damper includes a slide-in/plug-in p g-in damper
• Electric Heaters - The electric heaters range from 18 assembly with an outdoor air hood and filters. The out-
kW to 54kW and are available in all the voltage options door air dampers open to the preset position when the
of the base units. All heaters are dual staged. Cooling indoor fan motor is energized. The damper has a range
units include an adapter panel for easy installation of the of 0%to 100%outdoor air entry. Factory installed option
electric heaters. Necessary hardware and connectors or field installed accessory.
6
Unitary Products
SELECTED E.u I P t o N l i!- -1)A4-1)A4o 036-21058-003-A-1102
io 0 15D N iA aA
DM120N15A2AAA3
TABLE 2: PRODUCT NOMENCLATURE
Model Model Number
# Description Options
D Product Category D=Air Conditioner,Single Package
M Product Identifier M=Standard Efficiency
120 Nominal Cooling 078=6-1/2 Ton 102=8-1/2 Ton
Capacity MBH 090=7-1/2 Ton 120=10 Ton 150=12-1/2 Ton
N Heat Type C=Cooling Only N=Natural Gas,Aluminized Steel S=Natural Gas,Stainless Steel
15 Nominal Heating 00=No Heat Installed
Capacity 10=100 MBH Output Gas Heat 15=150 MBH Output Gas Heat 20=200 MBH Output Gas Heat
A=SM
B=SMNEC/BR Q=High Static MotorNEC/PE M=SM/BAS VEC/PE/2"Pleated
C=SMNEC/PE R=High Static Motor/MD Filters
(Downflow only) Y=High Static Motor/BAS
A Airflow D=SM/MD(Downflow only)
E=SM/Horiz EC S=High Static Motor/Horiz EC VECBR/2"Pleated Filters
N=High Static Motor L=SM/BAS VEC/BR/2"Pleated Z=High Static Motor/BAS
P=High Static MotorNEC/BR Filters VEC/PE/2"Pleated Filters
2 Voltage 2=208/230-3-60 4=460-3-60 5=575-3-60
A=None G=1 &3
N=2&3
B= 1 H=1 &4 P=2&4
A Installation C=2 J=1,2&3 Q=2,3&4
Options D=1 &2 K=1,2&4 R=3&4
•
E=3 L=1,3&4
F=4 M=1,2,3&4
M=None JH=JC,DFS,APS,TCC,PM&CG NH=NC,DFS,APS TCC,PM&CG
AB=PM JJ=JC,DFS,APS&TEC NJ=NC,DFS,APS&TEC
AC=CG JK=JC,DFS,APS,TEC&PM NK=NC,DFS,APS,TEC&PM
AD=DFS JL=JC,DFS,APS,TEC&CG NL=NC,DFS,APS,TEC&CG
AE=PM&CG JM=JC,DFS,APS,TEC,PM&CG NM=NC,DFS,APS,TEC,PM&CG
AF=PM&DFS JN=JC,DFS,APS,TEC&TCC NN=NC,DFS,APS,TEC&TCC
AG=CG&DFS JP=JC,DFS,APS,TEC,TCC&PM NP=NC,DFS,APS,TEC,TCC&PM
AH=PM,CG&DFS JQ=JC,DFS,APS,TEC,TCC&CG NQ=NC,DFS,APS,TEC,TCC&CG
CA=CC,DFS&APS JR=JC,DFS,APS,TEC,TCC,PM NR= NC, DFS,APS, TEC, TCC, PM
CB=CC,DFS,APS&PM &CG &CG
CC=CC,DFS,APS&CG HA=HC,DFS&APS TA=TCC
CD=CC,DFS,APS,PM&CG HB=HC,DFS,APS&PM TB=TCC&PM
CE=CC,DFS,APS,TCC HC=HC,DFS,APS,&CG TC=TCC&CG
CF=CC,DFS,APS,TCC&PM HD=HC,DFS,APS,PM&CG TD=TCC&DFS
CG=CC,DFS,APS,TCC&CG HE=HC,DFS,APS&TCC TE=TCC,PM&CG
CH=CC,DFS,APS,TCC,PM&CG HF=HC,DFS,APS,TCC&PM TF=TCC,PM&DFS
AA Additional Options CJ=CC,DFS,APS&TEC HG=HC,DFS,APS,TCC&CG TG=TCC,CG&DFS
CK =CC,DFS,APS,TEC&PM HH=HC,DFS,APS,TCC,PM&CG TH=TCC,PM,CG&DFS
CL=CC,DFS,APS,TEC&CG HJ=JC,DFS,APS&TEC TJ=TEC
CM=CC,DFS,APS,TEC,PM&CG HK=HC,DFS,APS,TEC&PM TK=TEC&PM
CN=CC,DFS,APS,TEC&TCC HL=HC,DFS,APS,TEC&CG TL=TEC&CG
CP=CC,DFS,APS,TEC,TCC&PM HM=HC,DFS,APS,TEC,PM&CG TM=TEC&DFS
CQ=CC,DFS,APS,TEC,TCC&CG HN=HC,DFS,APS&TEC TN=TEC,PM&CG
CR=CC,DFS,APS,TEC,TCC,PM HP=HC,DFS,APS,TEC,TCC&PM TP=TEC,PM&DFS
&CG HQ=HC,DFS,APS,TEC,TCC&CG TQ=TEC,CG&DFS
CV=CC,DFS,APS&2"PF HR=HC,DFS,APS,TEC,TCC,PM TR=TEC,PM,CG&DFS
CX=CC,DFS,APS,2"PF&TCC &CG TS=TEC&TCC
JA=JC,DFS&APS NA=NC,DFS&APS TT=TEC,TCC&PM
JB=JC,DFS,APS&PM NB=NC,DFS,APS&PM TU=TEC,TCC&CG
JC=JC,DFS,APS&CG NC=NC,DFS,APS&CG TV=TEC,TCC&DFS
JD=JC,DFS,APS,PM&CG ND=NC,DFS,APS,PM&CG TW=TEC,TCC,PM&CG
JE=JC,DFS,APS&TCC NE=NC,DFS,APS&TEC TX=TEC,TCC,PM&DFS
JF=JC,DFS,APS,TCC&PM NF=NC,DFS,APS,TCC&PM TY=TEC,TCC,CG&DFS
JG=JC,DFS,APS,TCC&CG NG=NC,DFS,APS,TCC&CG TZ=TEC,TCC,PM,CG&DFS
3 Product Generation 3=Third Generation
8
Unitary Products
036-21058-003-A-1102
TABLE 3: AIRFLOW ABBREVIATIONS TABLE 5: ADDITIONAL OPTIONS ABBREVIATIONS
ABBREVIATION MEANING ABBREVIATION MEANING
BR Barometric Relief APS Air Proving Switch
EC Economizer CC CPC Controller
VEC Vertical Economizer CG Coil Guard
MD Motorized Damper DFS Dirty Filter Switch
PE Power Exhaust HC Honeywell Controller
SM Standard Motor JC Johnson Controls Controller
BAS Building Automation System NC Novar Controller
TCC Technicoat Condenser Coil
TEC Technicoat Evaporator Coil
TABLE 4: INSTALLATION ABBREVIATIONS
ABBREVIATION MEANING
1 Disconnect
2 Convenience Outlet
3 Smoke Detector Supply Air
4 Smoke Detector Return Air
Unitary Products
9
036-21058-003-A-1102
•
TABLE 6: PHYSICAL DATA
Models
Component
078 090 102 120 150
Blower,Centrifugal(Dia.X Wd.in.) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15
Evaporator
Blower Motor,Standard(HP) 1-1/2 1-1/2 2 2 3
Motor,Optional(HP) 2 2 3 3 5
Rows 2 2 3 2 3
Evaporator Fins per Inch 15 15 15 15 15
Coil Height(in.) 30 32 24 40 40
Face Area(ft.2 each) 9.9 10.6 7.9 13.2 13.2
Condenser Propeller Dia.(in.,each) 24 24 24 24 24
Fan Motor(HP,each) 1/3 1/3 3/4 3/4 3/4
(2 per Unit) CFM,Nominal(each) 3400 3400 4400 4400 4400
Rows(each) 1 1 1 1 2
Condenser Fins per Inch 20 20 20 20 20
Coil
(2 per unit) Height(in.each) 24 28 36 44 44
Face Area(ft.2 each) 7.9 9.2 11.9 14.5 14.5
Refrigerant System 1 (Ib./oz.) 4/6 4/12 5/0 6/12 10/12
Charge System 2(Ib./oz.) 4/0 4/6 5/4 6/12 9/8
Quantity 2 2 2 2 2
Compressors
Type Recip Recip Recip Recip Recip
Size(Wd.x Ht.x Thickness in.) 25x20x2 25x20x2 25x20x2 25x20x2 25x20x2
Air Filters
Number Per Unit 4 4 4 4 4
10 Unitary Products
036-21058-003-A-1102
TABLE 7: STANDARD EFFICIENCY DM MODELS
Cooling Capacities
ARI Ratings* Sound Nominal Gas Heat Capacity
Size Model Electric Heat Gas Line
ze
(Tons) CFM Rating
MBH EER IPLV (dB)t Capacityt Input Output Seasonal Temp. in.StOD
(kW) Efficiency Rise ( )
(MBH) (MBH) (%) (°F)
Cooling
Only -
(078) Electric
6-1/2 Heat 77 9.0 9.45 2600 84 9,18,24,34 - - - - -
Gas Heat - 120 96 80 20-50 3/4
Gas Heat - 180 144 80 35-65 3/4
Cooling
Only
(090) Electric
7-1/2 Heat 86 9.0 10.15 3000 84 9.18,24,34
Gas Heat - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 30-60 3/4
Cooling
Only - -
(104) Electric
8412 Heat 98 9.0 3000 9,18,24,34 - - -
t
Gas Heal - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 10-40 3/4
Cooling
Only
Z
(120) Electric
10 Heat 120 9.0 9.10 4000 90 9,24,34 54 - - - - -
Gas Heat - 180 144 80 20-50 3/4
Gas Heat - 240 192 80 35-65 3/4
Cooling
Only - - -
-
(150) Electric
12-1/2 Heat 140 9.0 9.25 4500 90 9,24, .
i?
Gas Heat
- 180 144 80 10-40 3/4
Gas Heat - 240 192 80 25-55 3/4
" Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
t Rated in accordance with ARI 270 standard.
$ See Table 19.
;
TABLE 8: UNIT VOLTAGE LIMITATIONS
POWER RATING MIN. MAX.
208/230-3-60 187 252
460-3-60 432 504
575-3-60 540 630 k
{:
f
Unitary Products
11
036-21058-003-A-1102
TABLE 15: ELECTRICAL DATA 7-1/2 TON-STANDARD EFFICIENCY
OD Supply Blower Pwr Exh Min.Circuit MCA Max Fuse Size
Model Compressors Fan Ampacity wlPower Max Fuse wlPower
Motors Motor FLA Motor Electric Heater Actual Heater (Amps) Exhaust Size(Amps) Exhaust
Model No. kW Amps (Amps) (Amps)
Voltage RLA LRA FLA 1.5 HP 2 HP FLA 1.5 2 1.5 2 1.5 2 1.5 2
ea. ea. ea. HP HP HP HP HP HP HP HP
None - - 39.6 41.6 45.1 47.1 50 50 50 60
2TP04510925 6.8 18.9 39.6 41.6 45.1 47.1 50 50 50 60
208 13.5 130 1.5 6.2 8.2 5.5 2TP04511825 13.5 37.5 54.6 57.1 61.5 64.0 60 60 70 70
2TP04512425 18.0 50.0 70.2 72.7 77.1 79.6 80 80 80 80
2TP04513625 25.5 70.8 96.2 98.7 103.1 105.6 100 100 110 110
None - - 39.6 41.6 45.1 47.1 50 50 50 60
2TP04510925 9.0 21.7 39.6 41.6 45.1 47.1 50 50 50 60
230 13.5 130 1.5 6.2 8.2 5.5 2TP04511825 18.0 43.3 61.9 64,4 68.8 71.3 70 70 70 80
2TP04512425 24.0 57.7 79.9 82.4 86.8 89.3 80 90 90 90
2TP04513625 34.0 81.8 110.0 112.5 116.9 119.4 110 125 125 125
None - - 20.7 21.7 22.9 23.9 25 25 25 30
2TP04510946 9.0 10.8 20.7 21.7 22.9 23.9 25 25 25 30
460 7.1 54 0.8 3.1 4.1 2.2 2TP04511846 18.0 21.7 30.9 32.2 33.7 34.9 35 35 35 35
2TP04512446 24.0 28.9 40.0 41.2 42.7 44.0 40 45 45 45
2TP04513646 34.0 40.9 55.0 56.2 57.7 59.0 60 60 60 60
None - 15.8 17.0 17.6 18.8 20 20 20 20
2TP04510958 9.0 8.7 15.8 17.0 17.6 18.8 20 20 20 20
575 5.4 44 0.6 2.4 3.6 1.8 2TP04511858 18.0 17.3 24.7 26.2 26.9 28.4 25 30 30 30
2TP04512458 24.0 23.1 31.9 33.4 34.1 35.6 35 35 35 40
2TP04513658 34.0 32.7 43.9 45.4 46.1 47.6 45 50 50 50
* Maximum HACR breaker of the same AMP size is applicable.
18
Unitary Products
036-21058-003—A-1102
22 Oc., 0 N. V 00 CD M 0
V) I. N CO V m u) . N.
-
> O N N- 00 W m m O
> N N N
O a CO V O CD N CO V i- N o')
_ N CO a) m 0 0 N N t+)
CO `- •' - N N N N N N
d CO o 0 6V) 0)) /1.
O ,- N N
m 0 0 0 0 0
m I. in C') CI c) V CO m CD CO
3
v CD O O m CO v m u) n r) m U) ao v
uo V) o O
N N N
O = m u) 00 V m m O 0 N- CD o
u O n r N c)
m •
N N N N N
N O M CO V 0)
n' OOOjOO oo OOC) C)
V) V V V O n m co I. N co co N O m
76 comV V N inCOm u) O O r co ,
I. O O 0) m 0 0 V
N N CV
V a 0 u) O O h N O V O CD N 00 V
'- I 'n Cn CD O I. n O a0 m O O _ _ N c)
CO 7 7 7 `- . . . . . N N N N N ( ' '
2 O mm mCO m ,C., ,- n
CO 0 CD CV in
a I. O O N N co V V Cn Cn co
a
m m m m O O o o O o O O o O O
.N.. CO O I. n 0) u) c) V 0) COIn COj N N co co7 V V UN. ) upcoco N m CO V ' '
V
t` t O m o O
N N
c• _ CO N CD O m I. CD
N N O V. N O V
M cc). V V u) Cn O r` n O m O O N
m N N N Ni ' '
2 O N V N m cD V .- co co co O co Cn
0 N cc)) V in CO CO N- O m 0) o
.-- m m m m m m m m m m m m a c'
.N. Cn N CD N. c) V I• N m
N j m O co V N N CCS) V V c cocoN- CO 0) N O
CO 0) O
a N N
oO C. V O CD N m co co O co O V N O m a0 n
= O N N cc) V u1 u) CD I. CO m m 0 co
5 — m , . N N N
1— C C. In Lc, 10Co co IN CO m O O co N CV.) V Cn Cmn co co U)
00 0 0 CO CO CO m m m m 0) m m m m m m
0 x
L0 7 ^ o V m V O c^D Com) O CO IN. CND 2) Imn m n
0 CO c0 m m m o `- '— N V u] O N- O m
0 O = N m T o o. N CO CO CO O 0) CO CO O m O N
O CO 00 0 0 V 7 u) O n CD O
CO N N
Z 2 I. r I. N- O CD CD CD CO O In ill LO u) in u) V)
O a' N- CO N OO O UN0 00 V.
O m m o m rn m rn el
I .
N
V O N O C+) CV O CD O O t` O O N
N N. O O co o m m C) 0 CV 00 V N N c') V (C) CND N
0 a u) I. 0) N 0 0 O O O CV CO) I-- O V V V. CO
CO CO O m m O O .-
W m O O O O O
0 2 n m O N V In N- m N V O N m N V
Z a m o N c+) V u) CD I. m 0N o) V O I. O
CQ m CO N N- N I. n I. N- I. CO 00 00 CO CO c0 00 cn
G s m u) CD ch O V n O '- .- I. O u) I.
0fr
O N. I. c0 m m m 0 N N N V I°on
W7 a V 03 N I. c) m ID f") O 0) m 0) 0
^' O = N. I. CO CO m m O CV c) C') V in N
LL m x 0 0 0 0 0
w
0- O N I. N N N O c) c0 C') m V m V
Cy a V CD N- m o N C') Cn cD CD m N V 1
LL m CD CD CO CD I. N- I. I. N- n 1. c0 c0 CO "j
W v
cin V I. u) m m V Cn c) O
CD N O In N O m CO CO O m
0 O O m 0 0 N V O
—t n
m cv EL
p 2 N- IO. m m O o ^ N CINN- 000') 0
co V O
O O O O 3
T
N o
co V O co N O V O co N O
W a c') u') N- O O c) V) O CO m
J X CD CD CO (0 N- N- N- I. N- N- N
0
m 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 CD I
L.L. O O O O O O O o O O O O O O O O O L
Ia 0 N N N N N N N N 00) c) coNcoama)) co co) C') co) 2
Unitary Products
23
036-21058-003-A-1102
Prir.-,11,______Ok.
q, ____ -A - - _ __ 7:-.T.
11
_�
ij --- ; .
'11FRONT %'
LEFT FRONT
B C LEFT
A C D
A B
D E
F
FIGURE 2 : UNIT 4 POINT LOAD FIGURE 4 : UNIT 6 POINT LOAD
TABLE 32: 4 POINT LOAD WEIGHT
Location(lbs.) TABLE 33: 6 POINT LOAD WEIGHT
Model Locations(lbs.)
A B C D Model
DM078 228 195 285 333 A B C D E F
DM090 230 197 287 336 DM078 156 140 127 185 205 228
DM102 238 203 296 347 DM090 158 142 128 187 207 230
DM120 245 209 305 357 DM102 163 146 132 192 213 237
DM150 262 224 327 382 DM120 168 151 136 198 219 244
DM150 180 161 145 212 235 262
TABLE 34: UNIT WEIGHT
Model Shipping Weight(lbs.) Operating Weight(lbs.)
DM078 1046 1041
DM090 1056 1051
LEFT
FRONT DM102 1089 1084
DM120 1121 1116
DM150 1200 1195
FIGURE 3 : UNIT CENTER OF GRAVITY
Unitary Products
33
036-21058-003-A-1102
i
---r---TillIlliill"'I
II 30-11/32
50-314 ��, I See Detail
`` Power it' Control A
PW
Entry Entry
92-1/2 ;moi 97/8
1')
...-
4-1/4
4-1/4 i Power
r Entry
0 2-1/2
Convenience •
.' 1101
Power ��t��
11-1/2
1I Outlet .. �
Yit���� ��I' Entry For Baserail
7/8 ' Dimensions
/�-/16 FRONT See Detail B
�-�� Far Drain
59 24-3/16 6-3/ 6 . it Dimensions
LEFT \I See Detail C
j��� 27 8
_...-7 '�
FIGURE 5 : UNIT DIMENSIONS
DETAIL A Gas Pipe Inlet DETAIL B
2-3/8
5-1/4 r
Base , .
017-13/16 Pan
3-3/4
A
View of Wall Across from Coil
TABLE 35: UNIT CLEARANCES
3-9/16
Top* 72" I Right 12" DETAIL C
Front 36" Left 36" '_
Reart 36"
Bottom 0" O '_
* Units must be installed outdoors.Overhanging structure or j
shrubs should not obstruct condenser air discharge outlet. 5.318
allimmilimiim
t To remove the slide-out drain pan,a rear clearance of 60"is IIrequired.If space is unavailable,the drain pan can be
removed through the front by separating the corner wall. i
1= Units may be installed on combustible floors made from
wood or class A,B or C roof covering materials.
34
Unitary Products
Montville Fire
Marshal's Office
Memo
To: Mr.Vern Vesey II
From: Fire Inspector Roy(Ed) Shafer
Date: 06/04/03 FM02-0687
Re: Osterman Propane, Inc. Propane Line Test at Faria Corp.
Dear Vern,
Wednesday June 4,2003 I was requested by Osterman Propane who is the contractor to witness a required
pressure test on propane line from 2 above ground tanks to an HVAC Unit on outside of building, no
problems were observed on this test.
Any items that might have been inadvertently overlooked in the plan review do not relieve the owner
from achieving code compliance.
Should you need further assistance or have any questions,please contact the undersigned at the Town
of Montville Fire Marshal's Office at 860-848-1175.
Respectfully submitted,
Roy(Ed)Shafer Fire Inspector