Building / Trades Permit
Permit Number M2001-59 Permit Date 4/26/01 Permit Type Mechanical Permit Code R5
Job Street# 56 Job Location PHEASANT RUN Map/Lot 028/005-052
Job Description Heating &Air Conditioning
Owner Contractor
D'Amato Bros.
Viglione Heating &Cooling
Address P. O. Box 3063 Address 259 Commerce Street
City Milford State Ct. City East Haven State Ct.
Zip 06460 Telephone 203-874-5992 Zip 06512 Telephone 203-467-8388
Lic/Reg Number 302380
Lic/Reg Type S1 Exp Date: 8/31/01
Use Group R4 Code 1995 CABO Type Construction 5B
Building Value $0.00 Building Fee $0.00
Plumbing Value $0.00 Plumbing Fee $0.00
Mechanical Value $0.00 Mechanical Fee $0.00
Electrical Value $0.00 Electrical Fee $0.00
Other Value $0.00 Other Fee $0.00
Total Values $0.00 C/O Fee $0.00
Comments: Plan Review Fee $0.00
Paid on Building Permit State Ed Fee
$0.00
Total Fees $0.00
Building Official's Signature / Date /7- ?/ C
It is the owners respon t6 schedule the following required inspections(minimum 24 hours notice required):
Footings-prior to pouri g concrete
❑ Backfill -footing drains and waterproofing ❑ Fireplace Throat
❑ Concrete Slab, prior to pouring ❑ Fireplace Final
❑ Rough Framing ❑ Chimney -one flue above thimble
❑ Rough Electrical ❑ Firestopping/draftstopping
❑ Electrical Service ❑ Insulation
❑ Rough Plumbing and leak test ❑ Pool bonding
❑ Gas piping -pressure test and installation ❑ Final Inspection
▪ Rough HVAC ❑ Certificate of Occupancy-PRIOR to use or occupancy
•
kise 'god
Town of Montville Permit #/V,2cc 1-,5?
Building Department
310 Norwich-New London Tpke.
Tel. 848-7166 Uncasville, CT 06382 Fax. 848-7231
Application for Building or Trades Permit
Building Permit Trades Permit
❑New Construction ❑Accessory Structure ❑Flumfing 045hanicat
❑Action ❑gDemo&ition ❑Electrical ,/
❑Alteration ❑Other .?(eating
✓Air Conditioning
_gas Piping
Job Location O(p T\IAr\
mo n-M �ov
Job Description/Materials Fu<n 1 Oen ,tn d ; nota I d I war( '\ ct^L he a..ti
td�t h air Carl tion n
Owner pl\rnato 1bt(o1'he Mailing Address 0 .To)C 060 ?
CityrE rd State Cr Zip DCOlt6 Ci Tel ,,V3/ L
Contractor Vt. )(Ore /(,1,17 PC00/1 Mailing Address c ) Coryrr)ee e
City
E0 Ok 44a/en State Cr Zip 065 2 Tel c203/ X67/ g- >
Contractor's License/Registration Type&Number 5 1 302380 Exp. Date "/ /is7C1'S
New Home Construction Contractors:
Have you entered into a contract with a consumer for the proposed new home? ❑ Yes ❑ No
I hereby certify that the proposed work will conform to the Basic Building Code and all other codes as adopted by the
State of Connecticut and the Town of Montville and further attest that the proposed work is authorized by the owner in
fee and that I am authorized to make application for a permit for such work as described above.
r
Owner/Agent Signature `d _ _ Date 9 /-Z V/ Ci/
Construction Value Fee
Building $
Plumbing $ $
Mechanical $ $
Electrical $ $
Other $ $
Certificate of Occupancy $
Plan Review Fee $
State Education $
Total $
$
If >; .JE HTG & CLG, INS. fi PROJEC i . G• c
--'. COMMERCE DRIVE CLIENT: DAMATO B
ROS
1 HAVEN, CT 06512 DATE: 05/17/99
xESIDENTIAL/LIGHT COMMERCIAL HVAC LOADS DESIGNER: STEVE VIGLIONE
CLIENT INFORMATION:
NAME : nAMATO BROS
ADDRESS :
; CITY, STATE : MONTVILLE CONN
TOTAL BUILDING LOADS :
BLDG. LOAD AREA SEN. LAT. + SEN. = TOTAL
DESCRIPTIONS QUAN LOSS GAIN GAIN GAIN
3-C WINDOW DBL PANE CLR GLS METL FR 156 9 , 048 0 4, 125 4, 125
12-I WALL R-19 +1/2"ASPHLT BRD (R-1 . 3) 1, 573 6, 922 0 2 , 042 2 , 042
11-C DOOR METAL POLYSTYRENE CORE 63 2 , 369 0 699 699
16-G CEILING R-30 INSULATION 768 2 , 028 0 1, 115 1, 115
19-A FLOOR/ENCL CRAWL HARDWD NO INS 1, 536 19 , 170 0 0 0
SUBTOTALS FOR STRUCTURE : 4, 096 39 , 537 0 7, 981 7, 981
1
PEOPLE 8 0 1, 840 2 , 400 4, 240
APPLIANCES 0 0 0 1, 200 1, 200
DUCTWORK 0 5 , 396 0 670 670
INFILTRATION W. CFM: 163 . 8 S . CFM: 81 . 9 0 14, 418 2 , 284 1, 802 4, 086
VENTILATION W'.CFM : 61 . 4 S . CFM: 61 . 4 0 5 , 407 1, 713 1, 352 3 , 065
SENSIBLE GAIN TOTAL - 15, 405
TEMP. SWING MULTIPLIER X 1 . 00
BUILDING LOAD TOTALS 64, 758 5 , 837 15 , 405 21, 242
LOAD SUMMARY FOR ZONE #1
SUPPLY CFM AT 91 . 20 DEG HTG DT: 328 CFM PER SQUARE FOOT: 0 . 427
SQUARE FT. OF ROOM AREA: 768 SQUARE FOOT PER TON: 821 . 976
TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 35 . 615 MBH
TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 0 . 934 TONS
LOAD SUMMARY FOR ZONE #2
SUPPLY CFM AT 70 DEG HTG DT: 343 CFM PER SQUARE FOOT: 0 . 447
SQUARE FT. OF ROOM AREA: 768 SQUARE FOOT PER TON: 919 . 027
TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 29 . 142 MBH
TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 0 . 836 TONS ,
4•
i
72/
SOFTWARE *******
� fRESIDENTIAL AND L .iT C�MMERCzAL HVAC LOADS ELITE
SONE HTG & CLG, INC EAST HAVEN, CT 06512
,SREL 1536 SQ FT 05/17/99 PAGE 2
*********************** BUILDING LOADS (CONTINUED) *************************
TOTAL BUILDING LOAD SUMMARY
SUPPLY CFM AT 80 .40 DEG HTG DT: 671 CFM PER SQUARE FOOT: 0 .437
SQUARE FT. OF ROOM AREA: 1, 536•, SQUARE FOOT PER TON: 867 . 715
TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 64 . 758 MBH
TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 1 . 770 TONS
CALCULATIONS ARE BASED ON 7TH EDITION OF ACCA MANUAL J.
ALL COMPUTED RESULTS ARE ESTIMATES AS BUILDING USE AND WEATHER MAY VARY.
BE SURE TO• SELECT A UNIT THAT MEETS BOTH SENSIBLE AND LATENT LOADS .
•
•
•
'
` 7 Oy
F' RESIDENTIAL AND LIC , COMMERCIL HVAC LOADS BY ELITE SOFTWARE
ONE HTG & CLG, INC. EAST , CT
06512
05/17/99 PAGE 3
3REL 1536 SQ FT ************************3
*********************** ZONE # 1 ROOM LOAD SUMMARY
AREA HEATING COOLING
M ROOM BTUH % TOT CFM BTUH % TOT CFM
O . DESCRIPTION (SF)
1. WHOLE FIRST EL 768 32 , 912 100 . 0 374 7 , 217 100 . 0 328
SONE SUBTOTAL 768 32 , 912 100 . 0 374 7 , 22177 100 . 0 328
IENTILATION 2 , 703
3 , 319
LATENT GAIN •
SONE TOTALS_
35 , 615 11, 212 0 . 934 TONS
******** RESIDENTIAL AND LIGHT COMMERCIAL HVAC LOADS BY ELITE SOFTWARE *******
EAST HAVEN, CT 06512
VIGLIONE HTG & CLG, INC . ZONE05/17/99 PAGE 4
GAMBREL 1536 SQ FT *************************
************************* # 2 ROOM LOAD SUMMARY
RM ROOM
AREA HEATING COOLING
NO . DESCRIPTION (SF) BTUH , TOT CFM BTUH TOT CFM
•
2 . WHOLE SECOND FL 768 26 , 439 100 . 0 343 6 , 836 100 . 0 343
ZONE SUBTOTAL 768 - 26 , 439 100 . 0 343 6 , 676 1.00 . 0 343
VENTILATION 2 , 703
2 , 516
LATENT GAIN
ZONE TOTALS
29 , 142. 10 , 028 0 . 836 TONS