HomeMy WebLinkAboutSFR Heating and A/C TOWN OF MONTVILLE
BUILDING DEPARTMENT
310 NORWICH-NEW LONDON TPKE.
UNCASVILLE, CONNECTICUT 06382
Mechanical PermifeL 860-848-7166 Fax 860-848-7231 Page: 1
Permit Number: MC1999-59 Printed: 7/1/99
Approved:
Applicant: Viglione Heating & Cooling Zoning:
, 259 Commerce Street Addition:
East Haven, Ct 06512 Block:028 Lot(s): 005-028
Parcel Number: PARC1999-264 Section:
25 Pheasant Run Township:
Oakdale, Ct 06370 Range:
Area:
Legal Description:
Heating Viglione Heating &Cooling
, 259 Commerce Street Voice: 203-467-8388
East Haven, Ct 06512 Fax:
Local License: State License: S-1 302380
Fees and Receipts:
Number Description Amount
FEE1999-1412 paid on building permit $0.00
Fees Total: $0.00
Furnace<100K Btu:
Ventilation Fans:
Mechanical Exhaust Hood:
Furnace>100K Btu:
Suspend/Reces/Floor Htr:
Floor Furnaces:
Incinerators:
Boilers/Compressors:
Air Handling Units:
Cubic Feet per Minute:
Evaporative Coolers:
Documentation: heating &NC for new house
Bu d' g Officials Signature V sate
i'-:-. Town of Montville
1 Building Department
310 Norwich-New London Tpke . , Uncasville, Ct . 06382 Tel . 848-7166
F
*****************************************************************************
r:ij APPLICATION FOR BUILDING PERMIT OR TRADES PERMIT, Please fill out166
-,
****T.
x
Owner: D j`�
1. �'^ 4 A 'V r'o-� Mai 1 ing Address : y� �--r- �;,
City: "1 r-' c:::/ State : G6evw . Zip Code 0 E4/66 Tel : 203 7y_r?9
2.
Job Location: 02� �&asa.vl ��N Ma
' " Map/Block/Lot :
! Contractor : 25-7 C54
) ,,,,,,_, ,-c -_,,-c ft- Mailing Address : ��. f/�
City : it' q kafre. /11t,yT1•ry C /' State :Cu
********,K�c1*************✓�r***** ********************k********************�***
Stick Built : Modular Home : Manufactured Home:
Commercial :
Addition : Garage : Car Port :
Shed: Remodeling : Roofing :
Siding: _ Fireplace : Chimney : Windows : _— Pool : Demolition:
Plumbing: Heating : x Electrical : Air Conditioning : a
Gas :
Patio: _ Porch : Desk :
Retaining Wall : -New: X Rep air Re
p /_ place
ment :
Job Discription/Materials used : o •-/ /
Size: P-5P-5--� lv, 67 �ri --
*11 Type of Heat : � r-1„...., �, r Fireplace
No. of Stories : 2 No . Rooms:
BreeLeway :
No . Baths : f
a_ a; _ . _V2,r
Use : .04,..•-e_.,/,` NQ _
I hereby certify that the proposed �/
Building Code and all other work will conform to the Basic
aooptPG' '� }1f the State of Connecticut , and
the Town of Montville and further attest
d
by the owner in fee and that I am authorizedttomakeeoposappliicationed workzforuahpers t
for such work as described above. permit
Owner/Agent Signature - ' /
` -Ccrl� Date C�`� / J�
If signed by Contractor , type of license/registration & No : .7d -Zd S/
******************************************************************�**********
Bui ; <:inc , .
1) _t 1rtP?nnt tl._p On i ,.
Co!istruci_jon Vlue
Building _ Fe.e
Plumbing -----..-_-_______
Heating
Electrical_
Air Cond .
__
Other —
Certificate of Occupancy __
41
Plan Review
Total _ -
Cash/Checl:
VIGLIONE HTG & CLG, INC. v l ���'
PROJECT: GAMBREL 1536 SQ FT
259 COMMERCE DRIVE . CLIENT: DAMATO BROS
EAST HAVEN, CT 06512 DATE: 05/17/99
RESIDENTIAL/LIGHT COMMERCIAL HVAC LOADS DESIGNER: STEVE VIGLIONE
CLIENT INFORMATION:
NAME: DAMATO BROS
ADDRESS : 2 5-/�9e, ScwA'r iii
CITY, STATE: MONTVILLE CONN
TOTAL BUILDING LOADS :
BLDG. LOAD
AREA SEN. LAT. + SEN. = TOTAL
DESCRIPTIONS QUAN LOSS GAIN GAIN GAIN
3-C WINDOW DBL PANE CLR GLS METL FR 156 9, 048 0 4, 125 4, 125
12-I WALL R-19 +1/2"ASPHLT BRD (R-1 . 3) 1, 573 6, 922 0 2, 042 2, 042
11-C DOOR METAL POLYSTYRENE CORE 63 2, 369 0 699 699
16-G CEILING R-30 INSULATION 768 2, 028 0 1, 115 1, 115
19-A FLOOR/ENCL CRAWL HARDWD NO INS 1, 536 19, 170 0 0 0
SUBTOTALS FOR STRUCTURE : 4, 096 39, 537 0 7, 981 7, 981
PEOPLE 8 0 1, 840 2, 400 4, 240
APPLIANCES 0 0 0 1, 200 1, 200
DUCTWORK 0 5, 396 0 670 670
INFILTRATION W.CFM: 163 . 8 S .CFM: 81 . 9 0 14, 418 2 , 284 1, 802 4, 086
VENTILATION WICFM: 61 .4 S .CFM: 61 .4 0 5, 407 1, 713 1, 352 3, 065
SENSIBLE GAIN TOTAL 15, 405
TEMP. SWING MULTIPLIER X 1 . 00
BUILDING LOAD TOTALS 64, 758 5, 837 15, 405 21, 242
LOAD SUMMARY FOR ZONE #1
SUPPLY CFM AT 91 . 20 DEG HTG DT: 328 CFM PER SQUARE FOOT: 0 .427
SQUARE FT. OF ROOM AREA: 768 SQUARE FOOT PER TON: 821 . 976
TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 35 . 615 MBH
TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 0 . 934 TONS
LOAD SUMMARY FOR ZONE #2
SUPPLY CFM AT 70 DEG HTG DT: 343 CFM PER SQUARE FOOT: 0 .447
SQUARE FT. OF ROOM AREA: 768 SQUARE FOOT PER TON: 919 . 027
TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 29 . 142 MBH
TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 0 . 836 TONS
•
•
******** RESIDENTIAL AND LIGHT COMMERCIAL HVAC LOADS BY ELITE SOFTWARE
*******
VIGLIONE HTG & CLG, INC . EAST HAVEN, CT 06512
GAMBREL 1536 SQ FT 05/17/99 PAGE 2
************************* BUILDING LOADS (CONTINUED) *************************
TOTAL BUILDING LOAD SUMMARY
SUPPLY CFM AT 80 . 40 DEG HTG DT: 671 CFM PER SQUARE FOOT: 0 .437
SQUARE FT. OF ROOM AREA: 1, 536. SQUARE FOOT PER TON: 867 . 715
TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 64 . 758 MBH
TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 1 . 770 TONS
CALCULATIONS ARE BASED ON 7TH EDITION OF ACCA MANUAL J.
ALL COMPUTED RESULTS ARE ESTIMATES AS BUILDING USE AND WEATHER MAY VARY.
BE SURE TO SELECT A UNIT THAT MEETS BOTH SENSIBLE AND LATENT LOADS .
******** RESIDENTIAL AND LIGHT COMMERCIAL HVAC LOADS BY ELITE SOFTWARE
*******
VIGLIONE HTG & CLG, INC. EAST HAVEN, CT 06512
GAMBREL 1536 SQ FT 05/17/99 PAGE 3
************************* ZONE # 1 ROOM LOAD SUMMARY *************************
RM ROOM AREA HEATING COOLING
NO. DESCRIPTION (SF) BTUH % TOT CFM BTUH o TOT CFM
1 . WHOLE FIRST FL 768 32, 912 100 . 0 374 7, 217 100 . 0 328
ZONE SUBTOTAL 768 32, 912 100 . 0 374 7, 217 100 . 0 328
VENTILATION 2, 703 676
LATENT GAIN 3, 319
ZONE TOTALS 35, 615 11, 212 0 . 934 TONS
******** RESIDENTIAL AND LIGHT COMMERCIAL HVAC LOADS BY ELITE SOFTWARE *******
VIGLIONE HTG & CLG, INC. EAST HAVEN, CT 06512
GAMBREL 1536 SQ FT 05/17/99 PAGE 4
************************* ZONE # 2 ROOM LOAD SUMMARY *************************
RM ROOM AREA HEATING COOLING
NO. DESCRIPTION (SF) BTUH o TOT CFM BTUH o TOT CFM
2 . WHOLE SECOND FL 768 26, 439 100 . 0 343 6, 836 100 . 0 343
ZONE SUBTOTAL 768 26, 439 100 . 0 343 6, 836 100 . 0 343
VENTILATION 2, 703 676
LATENT GAIN 2 , 516
ZONE TOTALS 29, 142
10, 028 0 . 836 TONS