Permit No: H99-48 Code: 06
Owner: D'Amato Brothers Mailing Address: Quarry Road
City: Milford State: CT Zip: 06460 Tel: (203)874-5992
Job Location: 18 Pheasant Run Map/Block-Lot:
Contractor: Viglione H&C Mailing Address: 259 Commerce Street
City: East Haven State: CT Zip: 06512 Tel: (203)467-8388
Type of Permit: Heating & Air Conditioning
Job Description/Materials: Oil warm air heat with a/c.
Size: Type of Heat: Warm air Use: Dwelling
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAk**kAAAAAAAAAAAAAAAAAAAA*AAAAk**AAAAAAAAAA
Construction Value Fee
Building $: $:
Plumbing $: $:
Heating S: $:
Electrical $: $:
Air Conditioning$: $:
Other $: $:
Certificate of
Occupancy $: $:
Plan Review $: $:
State Ed ucation Fee $:
Total_$: Inc. wit Bldg. '- -git $:
y--
/ ,iii-i-'z=T-7(1 ,-.,-er..,,, /7,%5:(A;7
Building Officia Ignature Date
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAkAAAAAkAAAAA k*AAAAAAAA*kA*AAAAAAAAAkAA*AAAAAAA
Required Inspections
Footings prior to pouring concrete
Footing Drains/damp proofing prior to backfi l l
Framing
Town of Montville
Building Department
310 Norwich-New London Tpke. , Uncasville, Ct. 06382 Tel . 848-7166
*****************************************************************************
APPLICATION FOR BUILDING PERMIT OR TRADES PERMIT, Please fill out completely
Owner: -9'Amat 6`05 . Mailing Address: POC.(rC' PO ad
City: 1 I g-O(C, State: I Zip Code 0(04(00 Tel : a43
Job Location: 1g Phe(rcirit- P.U11 Map/Block/Lot:
Contractor: '1, " 1 111 ' 'J'• 44 1f I1 ( ailing Address: 5Q Commerc , S4-.
City: `5 fk Ver\ State: L. I Zip Code: laoSID. Tel : p)03-46 l -8388
******************************************************************************
Stick Built : )C Modular Home: Manufactured Home: Commercial :
Addition: Garage: Car Port : Shed: Remodeling: Roofing:
Siding: Fireplace: Chimney: Windows: Pool : `Demolition:
Plumbing: Heating: 10 Electrical : Air Conditioning: 3C Gas:
Patio: Porch: Deck: Retaining Wall : New: Repair/Replacement:
Job Discription/Materials used: 0\ 1 warm air reat W ►*h ac
Size: Type of Heat: Warm at ( Fireplace:
No.of Stories: 02. No. Rooms : C/ Breezeway:
No. Baths : Garage: \/€-S
Use: d AN2,4(()q
I hereby certify that the proposed work will conform to the Basic J
Building Code and all other Codes as adopted by the State of Connecticut, and
the Town of Montville and further attest that the proposed work is authorized
by the owner in fee and that I am authorized to make application for a permit
for such work as described above. J /
Owner/Agent Signature (/ Date ( I-S
If signed by Contractor, type of license/registration & No: 30a3$D Si
******************************************************************************
Building Department Use Only
Construction Value Fee
Building A to
Plumbing
Heating
Electrical 12
Air Cond. * 1
Other
Certificate of Occupancy AIM
Plan Review Fee
State Education Fee
Total Fees
Cash/Check
:dE •HTG & CLG, INC. ,
PROJECT: G• :' 1.53-6"S1; --r-r- €
COMMERCE DRIVE CLIENT: DAMATO BROS
i HAVEN, CT 06512 DATE: 05/17/99
{ESIDENTIAL/LIGHT COMMERCIAL HVAC LOADS DESIGNER: STEVE VIGLIONE
CLIENT INFORMATION:
NAME: nAMATO BROS
ADDRESS :
CITY, STATE: MONTVILLE CONN
TOTAL BUILDING LOADS :
BLDG. LOAD AREA SEN. LAT. + SEN. = TOTAL
DESCRIPTIONS QUAN LOSS GAIN GAIN GAIN
3-C WINDOW DBL PANE CLR GLS METL FR 156 9, 048 0 4, 125 4, 125
12-I WALL R-19 +1/2"ASPHLT BRD (R-1 . 3) 1, 573 6, 922 0 2, 042 2, 042 j
11-C DOOR METAL POLYSTYRENE CORE 63 2 , 369 0 699 699
16-G CEILING R-30 INSULATION 768 2 , 028 0 1, 115 1, 115 1
19-A FLOOR/ENCL CRAWL HARDWD NO INS 1, 536 19, 170 0 0 0
SUBTOTALS FOR STRUCTURE : 4, 096 39, 537 0 7, 981 7, 981
PEOPLE
8 0 1, 840 2 , 400 4, 240 I
APPLIANCES 0 0 0 1, 200 1, 200
DUCTWORK 0 5, 396 0 670 670
INFILTRATION W.CFM: 163 . 8 S . CFM: 81 . 9 0 14, 418 2 , 284 1; 802 4, 086
VENTILATION DJ.CFM: 61 . 4 S . CFM: 61 .4. 0 5, 407 1, 713 1, 352 3, 065
SENSIBLE GAIN TOTAL
FEMP. SWING MULTIPLIER 15, 405
X 1 . 00
3UILDING LOAD TOTALS
64, 758 5, 837 15, 405 21, 242
LOAD SUMMARY FOR ZONE #1
;UPPLY CFM AT 91 . 20 DEG HTG DT: 328 CFM PER SQUARE FOOT: 0 . 427
;QUARE FT. OF ROOM AREA: 768 SQUARE FOOT PER TON: 821 . 976
'OTAL HEATING REQUIRED WITH OUTSIDE AIR: 35 . 615 MBH
TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 0 . 934 TONS
i
LOAD SUMMARY FOR ZONE #2
UPPLY .CFM AT 70 DEG HTG DT: 343 CFM PER SQUARE FOOT: 0 .447
QUARE FT. OF ROOM AREA: 768 SQUARE FOOT PER TON: 919 . 027
OTAL HEATING REQUIRED WITH OUTSIDE AIR: 29 . 142 MBH
OTAL COOLING REQUIRED WITH OUTSIDE AIR: 0 . 836 TONS .
,w�. -
1
/24 ,P
RESIDENTIAL AND LIGHT COMMERCIAL HVAC LOADS BY ELITE SOFTWARE *******
/,.ONE HTG & CLG, INC. EAST HAVEN, CT 06512
, REL 1536 SQ FT 05/17/99 PAGE 2
*********t************* BUILDING LOADS (CONTINUED) *************************
TOTAL BUILDING LOAD SUMMARY
3UPPLY:CFM AT 80 .40 DEG HTG DT: 671 CFM PER SQUARE FOOT: 0 .437
3QUARE FT. OF ROOM AREA: 1, 536 . SQUARE FOOT PER TON: 867 . 715
DOTAL HEATING REQUIRED WITH OUTSIDE AIR: 64 . 758 MBH
rOTAL COOLING REQUIRED WITH OUTSIDE AIR: 1 . 770 TONS
2ALCULATIONS ARE BASED ON 7TH EDITION OF ACCA MANUAL J.
ALL COMPUTED RESULTS ARE ESTIMATES AS BUILDING USE AND WEATHER MAY VARY.
BE SURE TO. SELECT A UNIT THAT MEETS BOTH SENSIBLE AND LATENT LOADS .
•
_
'* RESIDENTIAL AND LIGHT CQMMERC�`.?NL HVAC LOADS BY ELITE SOFTWARE ******* 4
JNE HTG & CLG, INC. x EAST HAVEN, CT 06512
,REL 1536 SQ FT 05/17/99 PAGE 3
x********************** ZONE # 1 ROOM LOAD SUMMARY *************************
M ROOM AREA HEATING COOLING
O. DESCRIPTION (SF) BTUH o TOT CFM BTU} o TOT CFM
• L
1 . WHOLE FIRST FL 768 32 , 912 100 . 0 374 7, 217 100 . 0 - 328
;ONE SUBTOTAL 768 32 , 912 100 . 0 374 7 , 217 100 . 0 328
'ENTILATION 2 , 703 676
,ATENT GAIN 3 , 319
;ONE TOTALS 35, 615 11, 212 0 . 934 TONS
.******* RESIDENTIAL AND LIGHT COMMERCIAL HVAC LOADS BY ELITE SOFTWARE *******
IIGLIONE HTG & CLG, INC . EAST HAVEN, CT 06512
;AMBREL 1536 SQ FT 05/17/99 PAGE 4
************************ ZONE # 2 ROOM LOAD SUMMARY *************************
2M ROOM AREA HEATING COOLING
O . DESCRIPTION (SF) BTUH o TOT CFM BTUH TOT CFM
2 . WHOLE SECOND FL 768 26, 439 100 . 0 343 6, 836 100 . 0 343
ZONE SUBTOTAL 768 ' 26 , 439 100 . 0 343 6, 836 160 . 0 343
VENTILATION 2 , 703 676
LATENT GAIN 2 , 516 4•
ZONE TOTALS ' 29 , 142. 10, 028 0 . 836 ,TONS
•
•
i
2/ ,
,
/` HTG . & CLG, INC. PROJECT: RANCH 1550 SQ FT
COMMERCE DRIVE CLIENT: DAMATO BROS
/ HAVEN, CT .06512 DATE: 05/07/99
DENTIAL/LIGHT COMMERCIAL HVAC LOADS DESIGNER: STEVE VIGLIONE
/ 7
CLIENT INFORMATION:
NAME: nAMATO BROS
ADDRESS : RD
CITY, STATE: MONTVILLE CONN
•
TOTAL BUILDING LOADS :
BLDG. LOAD •
AREA SEN. LAT. + SEN. . TOTAL _
DESCRIPTIONS QUAN LOSS GAIN GAIN GAIN
3-C WINDOW DBL PANE CLR GLS METL FR 153 8, 874 0 3 , 960 3, 960
12-I WALL R-19 +1/2"ASPHLT BRD (R-1 . 3) 1, 221 5, 373 0 1, 584 1, 584 _
11-A DOOR METAL FIBERGLASS CORE 84 3 , 964 0 1, 170 1, 170
16-G CEILING R-30 INSULATION 1, 550 4, 092 0 2 , 251 2, 251 _
19-F FLOOR/ENCL CRAWL CARPET NO INS 1, 550 13 , 516 0 0 0
SUBTOTALS FOR ' STRUCTURE : 4, 558 35, 819 0 8, 965 8, 965
PEOPLE
4 0 920 1', 200 2, 120
APPLIANCES 0 0 1, 200 0 1, 200
DUCTWORK 0 5, 037 0 599 599
INFILTRATION W.CFM: 165 . 3 S .CFM: 82 . 7 0 14, 549 2 , 305 1, 819 4, 124
VENTILATION W.CFM: 62 . 0 S . CFM: 62 . 0 0 5, 456 1, 729 1, 364 3, 093
SENSIBLE GAIN TOTAL
TEMP. SWING MULTIPLIER 13, 947
X 1 . 00
BUILDING LOAD TOTALS 60, 861 6, 154 13 , 947 20, 101
•
SUPPLY CFM AT 54 . 80 DEG HTG DT: 919 CFM PER, SQUARE FOOT: 0 .593
SQUARE FT. OF ROOM AREA: 1, 550 SQUARE FOOT PER TON: 925 . 327
TOTAL HEATING REQUIRED WITH OUTSIDE AIR: 60 . 861 MBH
TOTAL COOLING REQUIRED WITH OUTSIDE AIR: 1 .675 TONS
CALCULATIONS ARE BASED ON 7TH EDITION OF ACCA MANUAL J.
ALL COMPUTED RESULTS ARE ESTIMATES AS BUILDING USE AND WEATHER MAY VARY.
BE SURE TO SELECT A UNIT THAT MEETS BOTH SENSIBLE AND LATENT LOADS .
•
e
s
tv,:
AESIDENTIAL 'AND LIGHT COMMERCIAL HVAC LOADS BY ELITE SOFTWARE *******
/HTG & CLG, INC. EAST HAVEN, CT 06512
,1550 SQ FT 05/07/99 PAGE 2
******************* ZONE # 1 ROOM LOAD SUMMARY *************************
14 ROOM AREAHEACOOLING
NO— DESCRIPTION (SF) BTUH TOTG CFM BTUH o TOT CFM
1. RANCH 1550 . SQ FT 1, 550 55, 405 100 . 0 919 12, 583 100 . 0 919
•
ZONE SUBTOTAL 1, 550 55, 405 100 . 0 919 12, 583 100 . 0 919
VENTILATION 5, 456 1, 364
LATENT GAIN
• 6, 154
ZONE TOTALS- 60, 861 20, 101 1 . 675 TONS
•
•